Bus cable<br />
Decentralized <strong>bus</strong><br />
supply DPSU<br />
Centralized <strong>bus</strong> supply<br />
PSU<br />
Distances and line<br />
lengths<br />
8/10<br />
Bus cable requirements as per IEC 189-2 (or equivalent)<br />
Cable type two-core, stranded (red/black)<br />
or 2x two-core, stranded (red/black)<br />
(white/yellow)<br />
or spiral quad<br />
Strands min. 5 / m<br />
Diameter min. 0.8 mm, max. 1.0 mm<br />
Wave resistance (ideal value) 120 Ω at 100 kHz<br />
Line resistance 20 Ω/km to max. 75 Ω/km<br />
Capacity, line to line max. 100 pF/m at 800 Hz<br />
Greater values require a proportional<br />
shortage of the perm. cable lengths.<br />
Cable screen not required (Synco devices without<br />
screen connection)<br />
Bus terminating resistor Not required<br />
Bus supply from Synco RMH / RMU controllers 30 V / 25 mA<br />
Controllers with DPSU, Decentral <strong>bus</strong> power supply: On max. 8 per line<br />
Bus devices without DPSU max. 2 per controller with DPSU<br />
Number of <strong>bus</strong> devices on one line max. 24 [8 + (8 x 2)]<br />
Centralized <strong>bus</strong> supply required if line has >24 <strong>bus</strong> devices<br />
or only RXB room controllers<br />
or third-party (EIB) devices<br />
or >2 devices without <strong>bus</strong> supply<br />
per device with <strong>bus</strong> supply<br />
Centralized <strong>bus</strong> supply: Devices with integrated throttle<br />
• EIB voltage supply, 320 mA, REG<br />
Type / Manufacturer SV/S 30.320.5 / ABB<br />
Supplier ID GH Q631 0038 R0111<br />
• EIB voltage supply, 640 mA, REG<br />
Type / Manufacturer SV/S 30.640.5 / ABB<br />
Supplier ID GH Q631 0048 R0111<br />
• Voltage, nominal <strong>bus</strong> supply DC 30 V<br />
(PSU output = DC 30 V / SELV)<br />
The indications for distances and line lengths in a network are designed for <strong>bus</strong> cables<br />
certified by either EIB or <strong>KNX</strong>.<br />
• The following applies to networks with centralized <strong>bus</strong> supply:<br />
Distance of two power supply units with integrated throttle min. 200 m<br />
Distance to <strong>bus</strong> unit of next neighboring PSU max. 350 m<br />
Distance between <strong>bus</strong> devices max. 700 m<br />
Total length of all lines on one line max.1000 m<br />
• For networks with decentralized <strong>bus</strong> supply, the distances are valid in addition in<br />
dependence of the number of controllers with Decentral <strong>bus</strong> power supply: On (DPSU).<br />
The following applies:<br />
Number of<br />
controllers with<br />
DPSU<br />
Controller with<br />
DPSU<br />
to <strong>bus</strong> device<br />
Maximum distance<br />
Bus device<br />
to <strong>bus</strong> device<br />
Total length of all lines<br />
on one line<br />
1 350 m 350 m max. 350 m<br />
2 350 m 700 m max. 700 m<br />
3 to 8 350 m 700 m max. 1000 m<br />
There is no minimum distance between controllers with DPSU.<br />
<strong>Siemens</strong> Building Technologies Data sheet <strong>Konnex</strong> <strong>bus</strong> Preliminary Editon 17.01.2003 CE1N<strong>3127</strong>en<br />
HVAC Products 17.01.2003