Bus cable<br />

Decentralized <strong>bus</strong><br />

supply DPSU<br />

Centralized <strong>bus</strong> supply<br />

PSU<br />

Distances and line<br />

lengths<br />

8/10<br />

Bus cable requirements as per IEC 189-2 (or equivalent)<br />

Cable type two-core, stranded (red/black)<br />

or 2x two-core, stranded (red/black)<br />

(white/yellow)<br />

or spiral quad<br />

Strands min. 5 / m<br />

Diameter min. 0.8 mm, max. 1.0 mm<br />

Wave resistance (ideal value) 120 Ω at 100 kHz<br />

Line resistance 20 Ω/km to max. 75 Ω/km<br />

Capacity, line to line max. 100 pF/m at 800 Hz<br />

Greater values require a proportional<br />

shortage of the perm. cable lengths.<br />

Cable screen not required (Synco devices without<br />

screen connection)<br />

Bus terminating resistor Not required<br />

Bus supply from Synco RMH / RMU controllers 30 V / 25 mA<br />

Controllers with DPSU, Decentral <strong>bus</strong> power supply: On max. 8 per line<br />

Bus devices without DPSU max. 2 per controller with DPSU<br />

Number of <strong>bus</strong> devices on one line max. 24 [8 + (8 x 2)]<br />

Centralized <strong>bus</strong> supply required if line has >24 <strong>bus</strong> devices<br />

or only RXB room controllers<br />

or third-party (EIB) devices<br />

or >2 devices without <strong>bus</strong> supply<br />

per device with <strong>bus</strong> supply<br />

Centralized <strong>bus</strong> supply: Devices with integrated throttle<br />

• EIB voltage supply, 320 mA, REG<br />

Type / Manufacturer SV/S 30.320.5 / ABB<br />

Supplier ID GH Q631 0038 R0111<br />

• EIB voltage supply, 640 mA, REG<br />

Type / Manufacturer SV/S 30.640.5 / ABB<br />

Supplier ID GH Q631 0048 R0111<br />

• Voltage, nominal <strong>bus</strong> supply DC 30 V<br />

(PSU output = DC 30 V / SELV)<br />

The indications for distances and line lengths in a network are designed for <strong>bus</strong> cables<br />

certified by either EIB or <strong>KNX</strong>.<br />

• The following applies to networks with centralized <strong>bus</strong> supply:<br />

Distance of two power supply units with integrated throttle min. 200 m<br />

Distance to <strong>bus</strong> unit of next neighboring PSU max. 350 m<br />

Distance between <strong>bus</strong> devices max. 700 m<br />

Total length of all lines on one line max.1000 m<br />

• For networks with decentralized <strong>bus</strong> supply, the distances are valid in addition in<br />

dependence of the number of controllers with Decentral <strong>bus</strong> power supply: On (DPSU).<br />

The following applies:<br />

Number of<br />

controllers with<br />

DPSU<br />

Controller with<br />

DPSU<br />

to <strong>bus</strong> device<br />

Maximum distance<br />

Bus device<br />

to <strong>bus</strong> device<br />

Total length of all lines<br />

on one line<br />

1 350 m 350 m max. 350 m<br />

2 350 m 700 m max. 700 m<br />

3 to 8 350 m 700 m max. 1000 m<br />

There is no minimum distance between controllers with DPSU.<br />

<strong>Siemens</strong> Building Technologies Data sheet <strong>Konnex</strong> <strong>bus</strong> Preliminary Editon 17.01.2003 CE1N<strong>3127</strong>en<br />