Guide Specifications – continuedgasket sealed outer doors. Provide main powerconnection(s), control power connections, <strong>com</strong>pressorand fan motor start contactors, currentoverloads, and factory wiring.2. Power supply shall enter unit at a single location,be 3 phase of scheduled voltage, and connectto individual terminal blocks per <strong>com</strong>pressor.Separate disconnecting means and/or externalbranch circuit protection (by Contractor) requiredper applicable local or national codes.B. Exposed <strong>com</strong>pressor, control and fan motor powerwiring shall be routed through liquid tight conduit.2.07 ACCESSORIES AND OPTIONSSome accessories and options supercede standard productfeatures. Your YORK representative will be pleasedto provide assistance.A. Microprocessor controlled, Factory installed Acrossthe-Linetype <strong>com</strong>pressor motor starters as standard.B. Outdoor Ambient Temperature Control1. Low Ambient Control: Permits unit operation to0°F (-18°C) ambient. Standard unit controls to32°F (0°C) ambient.C. Power Supply Connections:1. Single Point Power Supply: Single point TerminalBlock for field connection and interconnectingwiring to the <strong>com</strong>pressors. Separate externalprotection must be supplied, by others, in thein<strong>com</strong>ing power wiring, which must <strong>com</strong>ply withthe National Electric Code and/or local codes.2. Single Point: Single point Non-Fused Disconnect(s)and lockable external handle (in <strong>com</strong>pliance withArticle 440-14 of N.E.C.) can be supplied to isolatethe unit power voltage for servicing. Separateexternal fusing must be supplied, by others, in thein <strong>com</strong>ing power wiring, which must <strong>com</strong>ply withthe National Electric Code and/or local codes.3. Single Point Circuit Breaker: Single point TerminalBlock with Circuit Breaker and lockable externalhandle (in <strong>com</strong>pliance with Article 44014 ofN.E.C.) can be supplied to isolate power voltagefor servicing. In<strong>com</strong>ing power wiring must <strong>com</strong>plywith the National Electric Code and/or localcodes.D. Pressure & Temperature Transducers and Sensors1. Discharge Pressure Transducers: Permits unit tosense and display discharge pressure.2. Suction Pressure Transducers: Permits unit tosense and display suction pressure.3. Suction Temperature Sensors: Permits units tosense and display suction temperature.E. Control Power Transformer: Converts unit powervoltage to 120-1-60 or 120-1-50 for 50Hz units (500VA capacity). Factory mounting includes primary- andsecondary-wiring between the transformer and thecontrol panel.F. Motor Current Module: Capable of monitoring <strong>com</strong>pressormotor current. Provides extra protectionagainst <strong>com</strong>pressor reverse rotation, phase-loss andphase imbalance. Options consists of one module perelectrical system. (Factory mounted)G. Power Factor Correction Capacitors: Provided to correctunit <strong>com</strong>pressor factors to a 0.90-0.95.H. Condenser Coil Environmental Protection:1. Pre-Coated: Epoxy coated aluminum fin stock toguard from corrosive agents and insulate againstgalvanic potential. For mild seashore or industriallocations2. Copper Fin: Provide copper fins in lieu of aluminum.3. Post-Coated Dipped: Dipped-cured coating oncondenser coils for seashore and other corrosiveapplications (with the exception of strong alkalis,oxidizers, and wet bromine, chlorine and fluorinein concentrations greater than 100ppm).I. Protective Condensing Unit Panels (Factory or FieldMounted):1. Louvered Panels (condenser coils only): Paintedsteel as per remainder of unit cabinet, over externalcondenser coil faces.2. Wire Panels (full unit): Heavy gauge, welded wiremesh,coated to resist corrosion, to protect condensercoils from incidental damage and restrictunauthorized access to internal <strong>com</strong>ponents.3. Louvered Panels (full unit): Painted steel as perremainder of unit cabinet, to protect condensercoils from incidental damage,visually screeninternal <strong>com</strong>ponents, and prevent unauthorizedaccess to internal <strong>com</strong>ponents.4. Louvered/Wire Panels: Louvered steel panelson external condenser coil faces, painted as perremainder of unit cabinet. Heavy gauge, weldedwire-mesh, coated to resist corrosion, aroundbase of machine to restrict unauthorized access.J. Service Isolation valves: Service suction and discharge(ball type) isolation valves are added to unit46JOHNSON CONTROLS

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!