Air Cooled ModelsTable 19 Indoor unit approximate refrigerant charge lb (kg.) R–22RefrigerantModel 60 Hz (50 Hz) Charge/Circuit75A 4.0 (1.8)114A (115A) 5.0 (2.3)125A (130A) 5.0 (2.3)199A 6.0 (2.7)245A 7.0 (3.2)290A 7.0 (3.2)380A 8.0 (3.6)Table 20Outdoor condenser approximate refrigerant charge lb (kg) per circuitModelFan SpeedControlLee-Temp(Includes Receiver)097 5 (2.3) 27 (12.3)108 6 (2.7) 33 (15.0)130 5 (2.3) 27 (12.3)104L 4 (1.8) 21 (9.5)175 7 (3.2) 38 (17.2)165L 5 (2.3) 27 (12.3)205L 7 (3.2) 38 (17.2)216 12 (5.4) 64 (29.0)291 15 (6.8) 75 (34.0)308L 11 (5.0) 58 (26.3)349 22 (10.0) 113 (51.3)408 20 (9.1) 101 (45.8)415L 15 (6.8) 75 (34.0)451 25 (11.3) 124 (56.3)480C 20 (9.1) 101 (45.8)488 30 (13.6) 149 (67.6)510C 30 (13.6) 149 (67.6)580 30 (13.6) 150 (68.0)820 39 (17.7) N/A830L 30 (13.6) 149 (67.6)Table 21 Liquid line charge lb/10 ft. (kg/.3m) R–22Line Size, OD CuCharge1/2” .73 (.33)5/8” 1.17 (.52)7/8” 2.44 (1.09)1-1/8” 4.16 (1.86)1-3/8” 6.33 (2.83)Total Charge per Circuit.(There are two circuits per system)Table 22= Unit Charge+ Condenser Charge+ Liquid Line ChargeRefrigerant control settings for air cooled units psi (kPa)ModelRefrigerantTypeLow PressureCut OutLow PressureCut InHigh PressureCut OutFan Speed Control R-22 15 (103.4) 35 (241.3) 360 (2482)Lee-Temp R-22 20 (137.9) 65 (448.2) 360 (2482)32