Air Cooled ModelsFigure 23 Lee-Temp control typical general arrangement diagramCondenser CoilInverted traps* on discharge andreturn lines to extend abovebase of coil by a minimumof 7-1/2" (190mm)Piping Assembly**Rotalock Valve**Head PressureControl WithIntegral CheckValveCheckValveLee-TempReceiverSight Glass1/4" (6.4mm)PressureRelief Valve**Traps* every25’ (7.6m) of rise onhot gas line onlyLiquid Returnfrom CondenserEvaporator CoilShutoff*ValveSightGlassSolenoidValvesExpansion ValveSensing BulbLiquidReturnHot GasBypass(optional)Filter DryerMufflerCylinderUnloaders(optional)External EqualizersServiceValvesHot GasDischargeMuffler***CompressorSingle circuit shownFactory PipingOptional PipingField Piping* Components are not supplied by<strong>Liebert</strong> but are recommended forproper circuit operation and maintenance** Components suppliedby <strong>Liebert</strong> and must befield-installed*** Components suppliedby <strong>Liebert</strong> and must befield-installed (DH/VH andDE/VE 245A, 290A and380A models only)DPN00680 Rev035