22.08.2015 Views

Model YCAV Air-Cooled Screw Compressor Liquid Chillers Style A

Model YCAV Air-Cooled Screw Compressor Liquid Chillers ... - DCES

Model YCAV Air-Cooled Screw Compressor Liquid Chillers ... - DCES

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Dimensions - SI - continuedFORM 201.21-EG1 (711)<strong>YCAV</strong>0247S/P, 0247E/V, 0267S/P38CONTROL ENTRY76 WIDE X 343 HIGH102 POWER ENTRY254 WIDE X 330 HIGHVIEW B-BPOWER ENTRY IS ON BOTTOM OF PANEL44305VIEW C-CCCBB540161(EDGE OFUNIT TO COOLERCONNECTION2239VIEW A-ANotes:1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensure rated performance, reliableoperation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airpatterns and possible diminished performance. Johnson Controls’ unit controls will optimize the operation without nuisance high pressure safetycutouts: however, the system designer MUST consider potential performance degradation.2. Access to the unit control center stipulates the unit is no higher when on spring isolators. Recommended minimum clearances: side to wall -2m; rear to wall - 2m control panel end to wall - 1.2m; top - no obstructions whatsoever; distance between adjacent units - 3m. No more thanone adjacent wall may be higher than the unit.116JOHNSON CONTROLS

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!