The fan control switch features normally<br />

open 230V contacts, and is wired to control<br />

the live supply to the fan motor . When the<br />

circuit is made, the fan will switch on when<br />

the heat anticipator has closed the fan<br />

switch contacts. When the thermostat or<br />

time switch shuts down the burner, the fan<br />

will continue to run until the thermal switch<br />

has cooled sufficiently to prevent the<br />

residual heat from damaging the heater or<br />

its controls.<br />

On start up the fan delay prevents air being<br />

circulated until the desired temperature is<br />

achieved<br />

Limit control (red button) SET at 100 c<br />

An adjustable high temperature manual<br />

reset limit control. If this control needs<br />

resetting the cause should be determined<br />

and rectified immediately.<br />

Caution<br />

The power supply to the fan must not be<br />

interrupted, the only time when power<br />

supply can be disconnected or interrupted is<br />

during servicing or in emergencies.<br />

If there is a requirement for the heater to be<br />

switched off over night then the gas valve<br />

circuit should be opened via a time switch,<br />

etc, as per the wiring instructions and<br />

diagrams supplied within section 6.0 of this<br />

manual.<br />

19