13.2.2 Freeze Prevention Control<br />
1 .Frequency of the compressor<br />
For prevention of freezing of the indoor evaporator, the frequency of the compressor will be changed according<br />
to the indoor piping temperature.<br />
2 .Indoor Fan Control<br />
Indoor fan speed changes according to the indoor piping temperature.<br />
13.2.3 Dew Prevention Control<br />
To prevent dew formation at indoor unit discharge area.<br />
This control starts if all conditions continue for 20 minutes:<br />
- Operated with Cooling or Soft Dry Mode.<br />
- Indoor intake temperature is between 25� and 29�.<br />
- Outdoor air temperature is less than 30�.<br />
This control stopped then receive air swing change signal from Remote Control.<br />
13.2.4 Overload Protection For Cooling Operation<br />
The frequency for the compressor will change according to the outdoor piping temperature.<br />
RE9JKE, RE12JKE<br />
13.3 Indoor Piping <strong>Air</strong> Temperature Control (Heating)<br />
9�.<br />
8�.<br />
6�.<br />
0�.<br />
13.3.1 Indoor Fan Control<br />
1. Indoor fan is controlled by the indoor piping temperature.<br />
� Manual Fan Speed<br />
Piping Temperature(�)<br />
K0 K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11<br />
16 19 24 32 32 36 36 39 54 54 57 60<br />
38<br />
Outdoor pipe Temp.<br />
63�.<br />
61�<br />
60�<br />
58�<br />
RE15JKE<br />
Max:40 Hz Min 30Hz<br />
56�