8.3. Soft Dry Mode Operation<br />
• The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and<br />
then Soft Dry operation will start.<br />
• During Soft Dry operation, the Indoor Fan will operate at Lo- speed.<br />
• Once room temperature reaches below Soft Dry OFF temperature. Indoor Fan, Compressor and Outdoor Fan stop for 6<br />
minutes.<br />
Time Delay Safety Control<br />
• Once the compressor stops, it will not start for 3 minutes during Cooling operation.<br />
Anti-Freezing Control<br />
• Same as Anti-Freezing Control for Cooling Mode operation. (For Soft Dry region, 6 minutes waiting is valid during compressor<br />
stops.)<br />
Compressor Reverse Rotation Protection Control<br />
• Same as Compressor Reverse Rotation Protection Control for Cooling Mode Operation. (For Soft Dry region, 6 minutes waiting<br />
is valid during compressor stops.)<br />
Anti-Dew Formation Control<br />
• Same as Anti-Dew Formation Control for Cooling Mode operation.<br />
Automatic Fan Speed Mode<br />
When Automatic Fan Speed is selected at Remote Control during Soft Dry operation.<br />
• • Fan speed off and on at Lo- speed.<br />
• • Deodorizing Control.<br />