ELECTRICAL DATA <strong>LCA</strong>/<strong>LGA</strong>156/210<br />

Model�No. <strong>LCA</strong>/<strong>LGA</strong>156H <strong>LCA</strong>/<strong>LGA</strong>180<br />

Line�voltage�data���60�Hz���3�phase 208/230v 460v 575v 208/230v 460v 575v<br />

Condenser Full�load�amps − each (total) 2.4 (9.6) 1.3 (5.2) 1.0 (4.0) 2.4 (9.6) 1.3 (5.2) 1.0 (4.0)<br />

Fan�Motors (4) Locked�rotor�amps − each (total) 4.7 (18.8) 2.3 (9.6) 1.9 (7.6) 4.7 (18.8) 2.3 (9.6) 1.9 (7.6)<br />

Evaporator<br />

Blower<br />

Motor<br />

Motor<br />

Output<br />

Full�load�amps<br />

hp<br />

kW<br />

2 3 5<br />

1.5 2.2 3.7<br />

7.5 10.6 16.7<br />

2<br />

1.5<br />

3.4<br />

3<br />

2.2<br />

4.8<br />

5<br />

3.7<br />

7.6<br />

2<br />

1.5<br />

2.7<br />

3<br />

2.2<br />

3.9<br />

5 3 5 7.5<br />

3.7 2.2 3.7 5.6<br />

6.1 10.6 16.7 24.2<br />

3<br />

2.2<br />

4.8<br />

5 7.5<br />

3.7 5.6<br />

7.6 11.0<br />

3<br />

2.2<br />

3.9<br />

5<br />

3.7<br />

6.1<br />

7.5<br />

5.6<br />

9.0<br />

Locked�rotor�amps 46.9 66 105 20.4 26.8 45.6 16.2 23.4 36.6 66 105 152 26.8 45.6 66 23.4 36.6 54<br />

Optional<br />

Power�Exhaust<br />

Fans<br />

(No.)�Horsepower (W) (2) 1/3 (249) (2) 1/3 (249)<br />

Full�load�amps�(total) 4.8 2.6 2.0 4.8 2.6 2.0<br />

Locked�rotor�amps�(total) 9.4 4.8 3.8 9.4 4.8 3.8<br />

Service Outlet (2) 115 volt GFCI (amp rating) 15 15 15 15 15 15<br />

<strong>LCA</strong>/<strong>LGA</strong>156H AND <strong>LCA</strong>/<strong>LGA</strong>180H MODELS<br />

Compressors<br />

Rated load amps each (total) 13.5 (40.5) 7.4 (22.2) 5.8 (17.4) 17.3 (51.9) 9.0 (27.0) 7.1 (21.3)<br />

(3) Locked rotor amps each (total) 99 (297) 49.5 (148.5) 40 (120) 123.0 (369.0) 62.0 (186.0) 50.0 (150.00)<br />

Recommended With Exhaust Fans 70 80 80 40 40 45 30 30 35 90 100 110 50 50 50 40 40 45<br />

maximum<br />

fuse size (amps) Less Exhaust Fans 70 70 80 40 40 40 30 30 30 90 100 110 45 50 50 35 40 45<br />

�Minimum �Minimum Circuit<br />

With Exhaust Fans 66 69 75 36 37 40 28 29 31 81 87 96 41 44 48 33 35 39<br />

Ampacity Less Exhaust Fans 61 65 71 33 35 37 26 27 29 76 83 92 39 42 46 31 33 37<br />

<strong>LCA</strong>/<strong>LGA</strong>180S MODEL<br />

Compressors<br />

Rated load amps each (total) 16.7 (50.1) 8.6 (25.8) 6.0 (18.0)<br />

(3) Locked rotor amps each (total) 110.0 (330.0) 55.0 (165.0) 44.0 (132.0)<br />

Recommended With Exhaust Fans 90 100 110 45 50 50 35 35 40<br />

maximum<br />

− − − −<br />

fuse size (amps) Less Exhaust Fans<br />

90 90 110 45 45 50 30 35 40<br />

�Minimum �Minimum Circuit<br />

With Exhaust Fans 79 85 95 40 43 47 29 32 35<br />

Ampacity Less Exhaust Fans 74 81 90 38 41 45 27 30 33<br />

�Refer�to�National or Canadian�Electrical�Code�manual�to�determine�wire,�fuse�and�disconnect�size�requirements.<br />

NOTE���Extremes�of�operating�range�are�plus�and�minus�10%�of�line�voltage.<br />

NOTE � Where current does not exceed 100 amps, HACR type circuit breaker may be used in place of fuse (U.S. only).<br />

Model�No. <strong>LCA</strong>/<strong>LGA</strong>210<br />

Line�voltage�data���60�Hz���3�phase 208/230v 460v 575v<br />

Condenser<br />

Fan�Motors (4)<br />

Full�load�amps − each (total)<br />

Locked�rotor�amps − each (total)<br />

2.4 (9.6)<br />

4.7 (18.8)<br />

1.3 (5.2)<br />

2.3 (9.6)<br />

1.0 (4.0)<br />

1.9 (7.6)<br />

EEvaporator t<br />

Blower<br />

Motor<br />

Motor<br />

Output<br />

Full�load�amps<br />

Locked�rotor�amps<br />

hp<br />

kW<br />

3<br />

2.2<br />

10.6<br />

66<br />

5<br />

3.7<br />

16.7<br />

105<br />

7.5<br />

5.6<br />

24.2<br />

152<br />

3<br />

2.2<br />

4.8<br />

26.8<br />

5<br />

3.7<br />

7.6<br />

45.6<br />

7.5<br />

5.6<br />

11.0<br />

66<br />

3<br />

2.2<br />

3.9<br />

23.4<br />

5<br />

3.7<br />

6.1<br />

36.6<br />

7.5<br />

5.6<br />

9.0<br />

54<br />

Optional<br />

Power�Exhaust<br />

Power�Exhaust<br />

FFans<br />

(No.)�Horsepower (W)<br />

Full�load�amps�(total)<br />

Locked�rotor�amps�(total)<br />

4.8<br />

9.4<br />

(2) 1/3 (249)<br />

2.6<br />

4.8<br />

2.0<br />

3.8<br />

Service Outlet (2) 115 volt GFCI (amp rating) 15 15 15<br />

<strong>LCA</strong>/<strong>LGA</strong>210S MODELS<br />

Compressors<br />

(4)<br />

Rated load amps each (total)<br />

Locked rotor amps each (total)<br />

14.0 (56.0)<br />

92.0 (368.0)<br />

7.0 (28.0)<br />

46.0 (184.0)<br />

5.8 (23.2)<br />

44.0 (176.0)<br />

Recommended<br />

maximum fuse size (amps)<br />

With Exhaust Fans<br />

Less Exhaust Fans<br />

90<br />

90<br />

100<br />

100<br />

125<br />

110<br />

50<br />

45<br />

50<br />

50<br />

60<br />

60<br />

40<br />

35<br />

40<br />

40<br />

50<br />

45<br />

�Minimum �Minimum<br />

Circuit Ampacity<br />

With Exhaust Fans<br />

Less Exhaust Fans<br />

85<br />

80<br />

91<br />

87<br />

101<br />

96<br />

45<br />

43<br />

48<br />

46<br />

52<br />

50<br />

35<br />

33<br />

38<br />

35<br />

41<br />

39<br />

<strong>LCA</strong>/<strong>LGA</strong>210H MODELS<br />

Compressors<br />

(4)<br />

Rated load amps each (total)<br />

Locked rotor amps each (total)<br />

13.5 (54.0)<br />

120.0 (480.0)<br />

7.4 (29.6)<br />

49.5 (198.0)<br />

5.8 (23.2)<br />

40.0 (160.0)<br />

Recommended<br />

maximum fuse size (amps)<br />

With Exhaust Fans<br />

Less Exhaust Fans<br />

90<br />

90<br />

100<br />

100<br />

110<br />

110<br />

50<br />

45<br />

50<br />

50<br />

60<br />

60<br />

40<br />

35<br />

40<br />

40<br />

45<br />

45<br />

�Minimum �Minimum<br />

Circuit Ampacity<br />

With Exhaust Fans<br />

Less Exhaust Fans<br />

82<br />

78<br />

89<br />

84<br />

98<br />

94<br />

44<br />

41<br />

47<br />

44<br />

51<br />

49<br />

35<br />

33<br />

37<br />

35<br />

40<br />

38<br />

�Refer�to�National or Canadian�Electrical�Code�manual�to�determine�wire,�fuse�and�disconnect�size�requirements.<br />

NOTE���Extremes�of�operating�range�are�plus�and�minus�10%�of�line�voltage.<br />

NOTE � Where current does not exceed 100 amps, HACR type circuit breaker may be used in place of fuse (U.S. only).<br />

Page 16