14.12.2012 Views

LGA/LCA/LHA - lennox

LGA/LCA/LHA - lennox

LGA/LCA/LHA - lennox

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

ELECTRICAL DATA − <strong>LHA</strong>180/240<br />

Reciprocating Compressors<br />

Model�No. <strong>LHA</strong>180H <strong>LHA</strong>240H<br />

Line�voltage�data���60�Hz���3�phase 208/230v 460v 575v 208/230v 460v 575v<br />

Unit Efficiency High (H) High (H)<br />

Compressors<br />

Rated load amps<br />

each (total)<br />

(2) Locked rotor amps each<br />

(total)<br />

Outdoor Coil<br />

Fan�Motors Fan�Motors<br />

(4)<br />

Indoor Coil<br />

Blower<br />

Motor<br />

Full�load�amps − each�(total)<br />

23.9<br />

(47.8)<br />

185.0<br />

(370.0)<br />

10.6<br />

(21.2)<br />

89.0<br />

(178.0)<br />

8.7<br />

(17.4)<br />

78.4<br />

(156.8)<br />

Page 18<br />

27.6<br />

(55.2)<br />

205.0<br />

(410.0<br />

11.6<br />

(23.2)<br />

104.0<br />

(208.0)<br />

10.4<br />

(20.8)<br />

78.4<br />

(156.8)<br />

2.4 (9.6) 1.3 (5.2) 1.0 (4.0) 2.4 (9.6) 1.3 (5.2) 1.0 (4.0)<br />

Locked�rotor�amps�(total) 4.7 (18.8) 2.3 (9.6) 1.9 (7.6) 4.7 (18.8) 2.3 (9.6) 1.9 (7.6)<br />

Motor Output<br />

hp 3 5 7.5 3 5 7.5 3 5 7.5 3 5 7.5 10 3 5 7.5 10 3 5 7.5 10<br />

kW 2.2 3.7 5.6 2.2 3.7 5.6 2.2 3.7 5.6 2.2 3.7 5.6 7.5 2.2 3.7 5.6 7.5 2.2 3.7 5.6 7.5<br />

Full�load�amps 10.6 16.7 24.2 4.8 7.6 11.0 3.9 6.1 9.0 10.<br />

6<br />

16.7 24.2 30.8 4.8 7.6 11.0 14.0 3.9 6.1 9.0 11.0<br />

Locked�rotor�amps 66 105 152 26.8 45.6 66 23.4 26.6 54 66 105 152 193 26.8 45.6 66 84 23.<br />

4<br />

36.6 54 66<br />

Rec. max. With Exhaust Fans 100 100 110 45 45 50 35 40 40 110 110 125 125 50 60 60 70 40 50 50 50<br />

fuse size<br />

(amps) Less Exhaust Fans 90 100 110 40 45 50 35 35 40 110 110 110 125 45 60 60 60 40 45 50 50<br />

�Minimum With Exhaust Fans 79 85 92 36 39 42 29 32 35 87 99 107 113 38 51 54 57 33 40 43 45<br />

Circuit<br />

Ampacity Less Exhaust Fans 74 80 88 34 37 40 27 30 33 82 95 102 109 36 48 52 55 31 38 41 43<br />

(No.)�Horsepower (W) (2) 1/3 (249)<br />

Optional<br />

Power�Ex- Full�load�amps�(total) 4.8 2.6 2.0 4.8 2.6 2.0<br />

haust<br />

Fans Locked�rotor�amps�(total) 9.4 4.8 3.8 9.4 4.8 3.8<br />

Service Outlet (2) 115 volt GFCI (amp rating)<br />

15 15 15 15 15 15<br />

�Refer�to�National or Canadian�Electrical�Code�manual�to�determine�wire,�fuse�and�disconnect�size�requirements.<br />

NOTE���Extremes�of�operating�range�are�plus�and�minus�10�%�of�line�voltage.<br />

NOTE � Where current does not exceed 100 amps, HACR type circuit breaker may be used in place of fuse (U.S. only).<br />

ELECTRICAL DATA − <strong>LHA</strong>180<br />

Scroll Compressors<br />

Model�No. <strong>LHA</strong>180H<br />

Line�voltage�data�−�60�Hz�−�3�phase 208/230V 460V 575V<br />

Compressors Number of Compressors 2 2 2<br />

Outdoor<br />

Fan Fan�Motors Motors<br />

Rated load amps − each (total) 28.8 (57.6) 14.7 (29.4) 10.8 (21.6)<br />

Locked rotor amps − each (total) 195 (390) 95 (190) 80 (160)<br />

Number of Motors 4 4 4<br />

Full load amps − each (total) 2.4 (9.6) 1.3 (5.2) 1.0 (4.0)<br />

Locked rotor amps − each (total) 4.7 (18.8) 2.4 (9.6) 1.9 (7.6)<br />

Indoor<br />

Motor Output − hp 3 5 7.5 3 5 7.5 3 5 7.5<br />

Blower<br />

Motor − kW 2.2 3.7 5.6 2.2 3.7 5.6 2.2 3.7 5.6<br />

Recommended maximum<br />

fuse size (amps)<br />

*Minimum Circuit<br />

Ampacity<br />

Optional Power<br />

Exhaust Fan<br />

Full�load�amps 10.6 16.7 24.2 4.8 7.6 11.0 3.9 6.1 9.0<br />

Locked�rotor�amps 66 105 152 26.8 45.6 66 23.4 26.6 54<br />

With Exhaust Fan 110 110 125 60 60 60 40 45 50<br />

Less Exhaust Fan 110 110 125 50 60 60 40 45 45<br />

With Exhaust Fan 90 96 104 46 49 52 35 37 40<br />

Less Exhaust Fan 86 92 99 44 46 50 33 35 38<br />

(Number)�Horsepower (W) (2) 1/3 (249) (2) 1/3 (249) (2) 1/3 (249)<br />

Full�load�amps 4.8 2.6 2.0<br />

Locked�rotor�amps 9.4 4.8 3.8<br />

Service Outlet 115 volt GFCI (amp rating) 15 15 15<br />

�Refer�to�National or Canadian�Electrical�Code�manual�to�determine�wire,�fuse�and�disconnect�size�requirements.<br />

NOTE�−�Extremes�of�operating�range�are�plus�and�minus�10�%�of�line�voltage.