SPECIFICATIONS − <strong>LCA</strong>/<strong>LGA</strong> 240/300<br />
Model No. <strong>LCA</strong>/<strong>LGA</strong>240S �<strong>LCA</strong>/<strong>LGA</strong>300S<br />
Efficiency Type Standard (S) Standard (S)<br />
Gross Cooling Capacity � Btuh (kW) 248,000 (72.7) 301,600 (88.4)<br />
Cooling<br />
Ratings g<br />
�Net Cooling Capacity � Btuh (kW)<br />
Total Unit Power (kW)<br />
238,000 (69.7)<br />
26.4<br />
�284,000 (83.3)<br />
31.5<br />
�EER (Btuh/Watt) 9.0 �9.0<br />
�Integrated Part Load Value (Btuh/Watt) 10.0 �9.5<br />
Refrigerant Charge<br />
Furnished (R−22)<br />
Refrigerant Charge<br />
Furnished (R−410A)<br />
Refrigerant Charge<br />
Furnished (R−22)<br />
with Humiditrol option<br />
Circuit 1<br />
Circuit 2<br />
Circuit 3<br />
Circuit 4<br />
Circuit 1<br />
Circuit 2<br />
Circuit 3<br />
Circuit 4<br />
Circuit 1<br />
Circuit 2<br />
Circuit 3<br />
Circuit 4<br />
10 lbs. 0 oz. (4.54 kg)<br />
10 lbs. 0 oz. (4.54 kg)<br />
10 lbs. 0 oz. (4.54 kg)<br />
10 lbs. 0 oz. (4.54 kg)<br />
11 lbs. 4 oz. (5.10 kg)<br />
11 lbs. 4 oz. (5.10 kg)<br />
11 lbs. 4 oz. (5.10 kg)<br />
11 lbs. 4 oz. (5.10 kg)<br />
N/A N/A<br />
N/A N/A<br />
Model No. <strong>LGA</strong>240 <strong>LGA</strong>300<br />
Two Stage<br />
Heating<br />
CCapacity p iy<br />
Natural or<br />
Propane<br />
Gas at<br />
sea level)<br />
Heat Input Type<br />
Input (low) � Btuh (kW)<br />
Output (low) � Btuh (kW)<br />
Input (High) � Btuh (kW)<br />
Output (High) � Btuh (kW)<br />
Standard (S)<br />
169,000 (49.5)<br />
135,000 (39.6)<br />
260,000 (76.2)<br />
208,000 (60.9)<br />
Standard (S)<br />
169,000 (49.5)<br />
135,000 (39.6)<br />
260,000 (76.2)<br />
208,000 (60.9)<br />
High (H)<br />
305,000 (89.4)<br />
244,000 (71.5)<br />
470,000<br />
(137.7)<br />
376,000<br />
(110.2)<br />
A.G.A./C.G.A. Thermal Efficiency 80.0%<br />
Gas Supply<br />
Connections npt � in.<br />
Natural<br />
LPG/Propane<br />
1<br />
1<br />
Recommended Gas<br />
Supply Pressure � wc. wc in. in<br />
(kPa)<br />
Natural<br />
LPG/Propane<br />
7 (1.7)<br />
11 (2.7)<br />
Blower�wheel�nominal�dia.�x�width���in.�(mm) (2) 15 x 15 (381 x 381)<br />
3hp 3 hp<br />
(2.2 (2.2 kW)<br />
�Motor � &<br />
Drives<br />
Nominal motor output � hp (kW)<br />
Max. usable motor output � hp (kW)<br />
Voltage & phase<br />
(Drive kit #) RPM range<br />
3 (2.2)<br />
3.45 (2.6)<br />
208/230v, 460v or 575v-3ph<br />
(1 or 2) 685 � 865<br />
− − − −<br />
− − − −<br />
− − − −<br />
− − − −<br />
Evaporator<br />
Blower<br />
and<br />
Di Drive<br />
Selection<br />
5hp 5 hp<br />
(3.7 kW)<br />
�Motor � &<br />
Drives<br />
75hp 7.5 hp<br />
(5.6 kW)<br />
�Motor � &<br />
Drive<br />
Nominal motor output � hp (kW)<br />
Max. usable motor output � hp (kW)<br />
Voltage & phase<br />
(Drive kit #) RPM range<br />
Nominal motor horsepower (kW)<br />
Max. usable motor output � hp (kW)<br />
Voltage & phase<br />
(Drive kit #) RPM range<br />
5 (3.7)<br />
5.75 (4.3)<br />
208/230v, 460v or 575v-3ph<br />
(2) 685 − 865, (3) 850 − 1045 or (4) 945 − 1185<br />
7.5 (5.6)<br />
8.63 (6.4)<br />
208/230v, 460v or 575v-3ph<br />
(5) 945 � 1185<br />
10 hp<br />
(7.5 kW)<br />
�Motor � &<br />
Drive<br />
Nominal motor horsepower (kW)<br />
Max. usable motor output � hp (kW)<br />
Voltage & phase<br />
(Drive kit #) RPM range<br />
10 hp (7.5)<br />
11.5 (8.6)<br />
208/230v, 460v or 575v-3ph<br />
(6) 1045−1285 rpm (8) 1135−1365)<br />
Net face area � sq. ft. (m<br />
Page 4<br />
2 ) 22.3 (2.07) total<br />
Evaporator p<br />
Coil<br />
Tube diameter � in. (mm) & No. of rows<br />
Fins per inch (m)<br />
3/8 (9.5) � 3 (Standard Efficiency)<br />
3/8 (9.5) � 4 (High Efficiency)<br />
14 (551)<br />
3/8 (9.5) � 4<br />
Drain connection no. & size � in. (mm) fpt (1) 1 (25.4)<br />
Expansion device type Balanced Port Thermostatic Expansion Valve, removeable power head<br />
Condenser Net face area � sq. ft. (m2 Condenser<br />
Coil<br />
)<br />
Tube diameter � in. (mm) & No. of rows<br />
Fins per inch (m)<br />
56.5 (5.25) total<br />
3/8 (9.5) � 2<br />
20 (787)<br />
Diameter � in. (mm) & No. of blades (4) 24 (610) � 3<br />
Condenser<br />
Fans<br />
Total Air volume � cfm (L/s)<br />
Motor horsepower (W)<br />
Motor rpm<br />
15,450 (7290)<br />
(4) 1/3 (249)<br />
1075<br />
16,000 (7550)<br />
(4) 1/2 (373)<br />
Total Motor watts 1395 1800<br />
Filters<br />
(furnished)<br />
Type of filter<br />
No. and size � in. (mm)<br />
Disposable, commercial grade, pleated<br />
(6) 24 x 24 x 2 (610 x 610 x 51)<br />
Electrical characteristics 208/230v, 460v or 575v � 60 hertz � 3 phase<br />
�Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished by Lennox are<br />
shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate.<br />
�Rated in accordance with ARI Standard 340/360 and certified to ARI; 95�F (35�C) outdoor air temperature and 80�F (27�C) db/67�F (19�C) wb entering evaporator air; minimum external duct static<br />
pressure. Integrated Part Load Value tested at 80�F (27�C) outdoor air temperature. �Tested at conditions included in ARI Standard 340/360.<br />
NOTE � ARI capacity is net and includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.