TRIP<br />

INDICATON<br />

WINDOW<br />

AMP SETTING<br />

POINTER<br />

AMP SETTING<br />

CONTROL<br />

(BLUE DIAL)<br />

RED TEST<br />

BUTTON<br />

(Push To Test)<br />

LOAD VOLTAGE OUT<br />

LINE VOLTAGE IN<br />

CLEAR<br />

COVER<br />

(SHOWN<br />

CLOSED)<br />

STOP<br />

BUTTON<br />

(RED)<br />

BLUE RESET SCREW<br />

(Shown in AUTO position as<br />

shipped from the factory)<br />

TELEMECANIQUE OVERLOAD RELAY<br />

Page 38<br />

DETAIL SHOWING RESET BUTTON<br />

ADJUSTED TO MANUAL POSITION<br />

Lift clear cover and turn adjustment screw<br />

counterclockwise. Reset screw will pop out<br />

when pointer is in M (manual position). Close<br />

cover to lock reset screw into position.<br />

Lift clear cover to adjust relay amp setting according to value given on the blower motor nameplate.<br />

Proper relay amp setting equals motor nameplate FLA X service factor of 1.15 X .95.<br />

Cover must also be lifted to adjust control mode from automatic reset to manual reset (see detail<br />

above) and to test the control.<br />

Control must be in the manual reset mode to perform a test. Use a pointed object to press the small<br />

red test button. A yellow marker should appear in the trip indication window to the right of the amp<br />

setting control. Press the blue reset screw to reset the relay.<br />

The red STOP button opens the normally closed contacts which power the blower motor. This button<br />

stops blower motor operation as long as it is pressed in.<br />

FIGURE 8<br />

SIEMENS OVERLOAD RELAY<br />

BLUE RESET BUTTON IN<br />

FACTORY-SET AUTO MODE<br />

(Turn clockwise to H for<br />

manual reset)<br />

GREEN TRIP INDICATOR<br />

(Flush with surface −− not tripped;<br />

Above surface −− tripped)<br />

RED TEST BUTTON<br />

AMP ADJUSTMENT DIAL<br />

Adjust relay amp setting according to value given on the blower motor nameplate. Proper relay amp<br />

setting equals motor nameplate FLA X service factor of 1.15 X .95.<br />

Use small slotted screwdriver to adjust control mode from automatic reset (A) to manual reset (H).<br />

Control must be in the manual reset mode (H) to perform a test. Press the red test button. Green trip<br />

indicator should pop out. Press the blue reset screw to reset the relay.<br />

FIGURE 9