SPECIFICATIONS − <strong>LHA</strong> 180/240<br />

Units with Reciprocating Compressors<br />

Model No. <strong>LHA</strong>180H <strong>LHA</strong>240H<br />

Efficiency Type High (H) High (H)<br />

Gross Cooling Capacity � Btuh (kW) 185,000 (54.2) 233,000 (68.3)<br />

Cooling<br />

�Net Cooling Capacity � Btuh (kW) 180,000 (52.7) 226,000 (66.2)<br />

Ratings Total Unit Power (kW) 18.0 21.5<br />

High<br />

Temperature p<br />

Heating Ratings<br />

Low<br />

Temperature p<br />

Heating Ratings<br />

Refrigerant<br />

Charge<br />

Furnished<br />

(HCFC-22)<br />

Indoor Coil Blower<br />

and and<br />

Drive Selection<br />

�EER (Btuh/Watt) 10.0 10.5<br />

�Integrated Part Load Value (Btuh/Watt) 11.2 11.5<br />

*Total Heating Capacity � Btuh (kW) 188,000 (55.1) 220,000 (64.5)<br />

*Total Unit Power (kW) 16.7 20.2<br />

*C.O.P. 3.3 3.2<br />

*Total Heating Capacity � Btuh (kW) 108,000 (31.6) 118,000 (34.6)<br />

*Total Unit Power (kW) 13.2 15.0<br />

*C.O.P. 2.4 2.3<br />

Circuit 1 24 lbs. 8 oz. (11.11 kg) 26 lbs. 0 oz. (11.79 kg)<br />

Circuit 2 24 lbs. 8 oz. (11.11 kg) 26 lbs. 0 oz. (11.79 kg)<br />

Blower�wheel�nominal�dia.�x�width���in.�(mm) (2) 15 x 15 (381 x 381)<br />

Nominal motor output � hp (kW) 3 (2.2)<br />

3 hp (2.2 kW)<br />

�Motor �Motor &<br />

Drives Drives<br />

Max. usable motor output � hp (kW)<br />

Voltage & phase<br />

3.45 (2.6)<br />

208/230v, 460v or 575v-3ph<br />

(Drive kit #) RPM range (1 or 2) 685 � 865<br />

Nominal motor horsepower (kW) 5 (3.7)<br />

5 hp (3.7 kW)<br />

�Motor �Motor &<br />

Drives<br />

Max. usable motor output � hp (kW)<br />

Voltage & phase<br />

5.75 (4.3)<br />

208/230v, 460v or 575v-3ph<br />

(Drive kit #) RPM range (2) 685 − 865, (3) 850 − 1045 or (4) 945 − 1185<br />

Nominal motor horsepower (kW) 7.5 (5.6)<br />

7.5 hp (5.6 kW)<br />

�Motor �Motor &<br />

Drive<br />

Max. usable motor output � hp (kW)<br />

Voltage & phase<br />

8.63 (6.4)<br />

208/230v, 460v or 575v-3ph<br />

(Drive kit #) RPM range (5) 945 � 1185<br />

Nominal motor horsepower (kW) 10 hp (7.5)<br />

10 hp (7 (7.5 5 kW)<br />

�Motor �Motor & Max. usable motor output � hp (kW) 11.5 (8.6)<br />

Drive Voltage & phase 208/230v, 460v or 575v-3ph<br />

<strong>LHA</strong>240H ONLY (Drive kit #) RPM range (6) 1045−1285 rpm (8) 1135−1365 rpm<br />

Net face area � sq. ft. (m 2 ) 22.3 (2.07)<br />

Tube diameter � in. (mm) & No. of rows 3/8 (9.5) � 3 3/8 (9.5) � 4<br />

Indoor Coil Fins per inch (m) 14 (551)<br />

Drain connection no. & size � in. (mm) fpt (1) 1 (25.4)<br />

Outdoor Coil<br />

OOutdoor tdoor<br />

Fans<br />

Expansion device type Balanced Port Thermostatic Expansion Valve, removeable power head<br />

Net face area � sq. ft. (m 2 ) 57.0 (5.30)<br />

Tube diameter � in. (mm) & No. of rows 3/8 (9.5) � 2<br />

Fins per inch (m) 20 (787)<br />

Expansion device type Balanced Port Thermostatic Expansion Valve, removeable power head<br />

Diameter � in. (mm) & No. of blades (4) 24 (610) � 3<br />

Total Air volume � cfm (L/s) 15,450 (7290)<br />

Motor horsepower (W) (4) 1/3 (249)<br />

Motor rpm 1075<br />

Total Motor watts 1395<br />

Filters Type of filter Disposable, commercial grade, pleated<br />

(furnished) No. and size � in. (mm) (6) 24 x 24 x 2 (610 x 610 x 51)<br />

Electrical characteristics 208/230v, 460v or 575v � 60 hertz � 3 phase<br />

�Rated in accordance with ARI Standard 340/360 and certified to ARI. Integrated Part Load Value tested at 80�F (27�C) outdoor air temperature.<br />

Cooling Ratings� 95�F (35�C) outdoor air temperature and 80�F (27�C) db/67�F (19�C) wb entering indoor coil air.<br />

High Temperature Heating Ratings� 47�F (8�C) db/43�F (6�C) wb outdoor air temperature and 70�F (21�C) entering indoor coil air.<br />

Low Temperature Heating Ratings� 17�F (-8�C) db/15�F (-9�C) wb outdoor air temperature and 70�F (21�C) entering indoor coil air.<br />

NOTE � ARI capacity is net and includes indoor blower motor heat deduction. Gross capacity does not include indoor blower motor heat deduction.<br />

�Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors<br />

furnished by Lennox are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service<br />

factor limitations outlined on the motor nameplate.<br />