BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT WITH STANDARD GAS HEAT, WET INDOOR COIL & AIR FILTERS IN PLACE.<br />

FOR ALL UNITS ADD:<br />

1 − Any factory installed options air resistance (high gas heat, economizer, etc.). See table below<br />

2 − Any field installed accessories air resistance (duct resistance, diffuser, etc.). See Page 29<br />

Then determine from table the blower motor output and drive required.<br />

0.30 to 1.40 in. w.g. <strong>LGA</strong>180<br />

Air<br />

Volume<br />

cfm 0.30 0.40 0.50 0.60 0.70<br />

External Static (in. w.g.)<br />

0.80 0.90 1.00 1.10 1.20 1.30 1.40<br />

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

Low Static − 2 HP, Drive Kit A Standard Static − 3 HP, Drive Kit 1<br />

4800 577 1.13 620 1.31 662 1.48 702 1.66 742 1.83 777 2.01 811 2.18 842 2.36 872 2.54 902 2.72 932 2.89 960 3.07<br />

5000 585 1.25 628 1.43 670 1.60 710 1.78 750 1.95 783 2.13 815 2.30 848 2.50 880 2.70 910 2.88 940 3.05 968 3.23<br />

5500 605 1.45 648 1.65 690 1.85 728 2.05 765 2.25 800 2.45 835 2.65 865 2.85 895 3.05 925 3.25 955 3.45 983 3.65<br />

6000 630 1.75 670 1.95 710 2.15 748 2.38 785 2.60 818 2.83 850 3.05 880 3.25 910 3.45 940 3.68 970 3.90 998 4.13<br />

6500 650 2.05 690 2.28 730 2.50 768 2.75 805 3.00 838 3.23 870 3.45 900 3.70 930 3.95 958 4.18 985 4.40 1013 4.63<br />

7000 675 2.35 715 2.63 755 2.90 790 3.15 825 3.40 858 3.68 890 3.95 920 4.20 950 4.45 978 4.70 1005 4.95 1030 5.18<br />

7200 687 2.55 725 2.81 763 3.06 798 3.33 833 3.60 866 3.86 898 4.11 926 4.36 954 4.61 984 4.90 1013 5.19 1038 5.44<br />

1.50 to 2.50 in. w.g. <strong>LGA</strong>180<br />

Air<br />

Volume<br />

cfm 1.50 1.60 1.70 1.80<br />

External Static (in. w.g.)<br />

1.90 2.00 2.10 2.20 2.30 2.40 2.50<br />

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

High Static − 5 HP, Drive Kit 4 Field Furnished Drive<br />

4800 987 3.24 1014 3.42 1041 3.60 1064 3.78 1087 3.95 1112 4.13 1136 4.30 1159 4.50 1181 4.70 1204 4.88 1226 5.06<br />

5000 995 3.40 1020 3.60 1045 3.80 1070 3.98 1095 4.15 1118 4.33 1140 4.50 1163 4.70 1185 4.90 1208 5.10 1230 5.30<br />

5500 1010 3.85 1035 4.05 1060 4.25 1085 4.48 1110 4.70 1133 4.90 1155 5.10 1178 5.30 1200 5.50 1220 5.70 1240 5.90<br />

6000 1025 4.35 1050 4.58 1075 4.80 1098 5.00 1120 5.20 1145 5.43 1170 5.65 1193 5.88 1215 6.10 1235 6.33 1255 6.55<br />

6500 1040 4.85 1065 5.10 1090 5.35 1115 5.60 1140 5.85 1163 6.08 1185 6.30 1205 6.53 1225 6.75 1248 7.00 1270 7.25<br />

7000 1055 5.40 1080 5.68 1105 5.95 1130 6.20 1155 6.45 1178 6.70 1200 6.95 1220 7.20 1240 7.45 1263 7.73 1285 8.00<br />

7200 1063 5.68 1088 5.94 1113 6.19 1136 6.44 1159 6.69 1182 6.96 1204 7.23 1226 7.50 1248 7.77 1269 8.03 1289 8.28<br />

NOTE − Bold, italics − drive is capable of the values noted but will exceed motor horsepower.<br />

AIR RESISTANCE (in. w.g.) − Factory Installed Options<br />

Air Air Volume − cfm<br />

Gas Heat Exchanger<br />

Med. Heat High Heat<br />

Page 22<br />

Economizer<br />

Horizontal<br />

MERV 11<br />

Roof Curb<br />

Filter<br />

4800 .08 .10 − − − .08 .01<br />

5000 .09 .11 − − − .08 .01<br />

5500 .10 .13 − − − .10 .02<br />

6000 .12 .15 − − − .11 .02<br />

6500 .13 .17 .02 .13 .02<br />

7000 .15 .19 .04 .15 .03<br />

7200 .16 .20 .05 .16 .03