08.01.2013 Views

400 Hz Ground Power Cables 5 kV Airfield Lighting Cables - Leoni

400 Hz Ground Power Cables 5 kV Airfield Lighting Cables - Leoni

400 Hz Ground Power Cables 5 kV Airfield Lighting Cables - Leoni

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>400</strong> <strong>Hz</strong>-Kabel für bewegliche Anwendungen<br />

<strong>400</strong> <strong>Hz</strong> <strong>Cables</strong> for mobile applications<br />

BETAjet® <strong>400</strong> FRNC-quadroflex<br />

Verdrillte flexible Andienkabel mit zentraler Steuerleitung<br />

BETAjet® <strong>400</strong> FRNC-quadroflex<br />

Twisted flexible power cables with control cores in the center cable<br />

Anwendung<br />

In mobilen Applikationen, bei extremen Klima verhält nissen und starker mechanischer<br />

Beanspruchung. Im Boden versenkte Kabelspender. Mobile <strong>400</strong> <strong>Hz</strong>-Diesel-<br />

generatoren. Aufgehängte Kabel an Passagierbrücken, usw. bei Zivil- und Militär-<br />

anlagen. Empfohlene maximale Länge wegen asymmetrischem Spannungsabfall<br />

15 m.<br />

Aufbau<br />

� Leistungsadern: Kupferlitze blank, feindrähtig, nach VDE 0295, IEC 60228,<br />

50 mm² Klasse 5, 70 mm² Klasse 6<br />

Aderisolation: Ethylen-Propylen-Rubber (EPR) vernetzt<br />

� Steueradern: 8 × 1 mm², Kupferlitze blank, feindrähtig, nach VDE 0295, IEC<br />

60228, Klasse 5<br />

Aderisolation: Polyolefin Copolymer<br />

Farben: Weiss mit schwarzem Ziffernaufdruck<br />

� Aussenmantel: Verschleissfestes Polyurethan (PUR)<br />

� Mantelfarbe: Orange<br />

Technische Daten<br />

� Nennspannung: U₀/U 115 / 200 V<br />

� Betriebsspannung: U₀/U max. 600 / 1000 V<br />

� Prüfspannung: <strong>400</strong>0 VAC, 50 <strong>Hz</strong><br />

� Betriebstemperatur: – 40 °C bis + 90 °C<br />

Normen / Materialeigenschaften<br />

� Halogenfrei: IEC 60754-1, EN 50267-2-1 (< 5 mg/g)<br />

� Keine korrosiven Gase: IEC 60754-2, EN 50267-2-2 (pH < 5)<br />

� Geringe toxische Gase: NES 02-713, NFC 20-454<br />

� Ölbeständigkeit: EN 60811-2-1 (24 h /100 °C)<br />

� Gute Abriebfestigkeit<br />

� UV-Beständigkeit<br />

� Flammwidrig: IEC 60332-1, EN 50265-1<br />

Application<br />

Suitable for use in high mobility applications, under extreme operational conditions of<br />

mechanical stress and climate, for in- and outdoor. In grounded pits. Mobile <strong>400</strong> <strong>Hz</strong><br />

diesel generator unit. Suspended cables for passenger bridges, etc. for civil and military<br />

applications. Recommended maximum cable length 15 m due to asymmetric voltage<br />

trop.<br />

Construction<br />

� <strong>Power</strong> conductors: Bare fine copper strands, according to VDE 0295, IEC 60228,<br />

50 mm² class 5, 70 mm² class 6<br />

Insulation: Cross-linked Ethylene-Propylene-Rubber (EPR)<br />

� Control cores: 8 × 1 mm², bare fine copper strands, according to VDE 0295,<br />

IEC 60228, class 5<br />

Insulation: Polyolefin copolymer<br />

Colour: White with numbers printed in black<br />

� Outer sheath: Abrasion resistant polyurethane (PUR)<br />

� Sheath colour: Orange<br />

Technical data<br />

� Nominal voltage: U₀/U 115 / 200 V<br />

� Rated voltage: U₀/U max. 600 / 1000 V<br />

� Test voltage: <strong>400</strong>0 VAC, 50 <strong>Hz</strong><br />

� Operation temperature: – 40 °C to + 90 °C<br />

Standards / Material properties<br />

� Halogen free: IEC 60754-1, EN 50267-2-1 (< 5 mg/g)<br />

� No corrosive gases: IEC 60754-2, EN 50267-2-2 (pH < 5)<br />

� Low toxic gases: NES 02-713, NFC 20-454<br />

� Resistance to oil: EN 60811-2-1 (24 h /100 °C)<br />

� Good resistance to abrasion<br />

� UV resistance<br />

� Flame retardant: IEC 60332-1, EN 50265-1<br />

<strong>Power</strong> conductor<br />

Insulation<br />

Outer sheath<br />

Control cores<br />

14 www.leoni-airport.com September 2009

Hooray! Your file is uploaded and ready to be published.