DOWEX Ion Exchange Resins WATER CONDITIONING MANUAL
DOWEX Ion Exchange Resins WATER CONDITIONING MANUAL
DOWEX Ion Exchange Resins WATER CONDITIONING MANUAL
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>Ion</strong> <strong>Exchange</strong> Resin Operational Information<br />
Drained<br />
bed level<br />
Figure 20. Examples of devices for obtaining a core sample.<br />
USING GRAIN THIEF<br />
Fluidized<br />
bed level<br />
USING SIPHON HOSE<br />
Slow backwash<br />
An example procedure to obtain a representative sample of a resin bed from the top of the bed to the<br />
bottom with minimum equipment expense is as follows:<br />
1. Build the device as shown in Figure 21. It is important that the lower stopper be rounded or it will not<br />
seat properly. A rubber ball may be substituted in place of the stopper, but its diameter must be larger<br />
than the pipe diameter. Other required equipment:<br />
• Clean 2–3 gal (approximately 10-L) plastic bucket<br />
• Plastic 1 qt (1-L) sample jars<br />
• Plastic storage bags for secondary leak containment<br />
Figure 21. Example of device for obtaining a sample from top to bottom of a resin bed.<br />
<strong>DOWEX</strong> <strong>Ion</strong> <strong>Exchange</strong> <strong>Resins</strong> 49 Water Conditioning Manual