<strong>Ion</strong> <strong>Exchange</strong> Resin Operational Information<br />

Drained<br />

bed level<br />

Figure 20. Examples of devices for obtaining a core sample.<br />

USING GRAIN THIEF<br />

Fluidized<br />

bed level<br />

USING SIPHON HOSE<br />

Slow backwash<br />

An example procedure to obtain a representative sample of a resin bed from the top of the bed to the<br />

bottom with minimum equipment expense is as follows:<br />

1. Build the device as shown in Figure 21. It is important that the lower stopper be rounded or it will not<br />

seat properly. A rubber ball may be substituted in place of the stopper, but its diameter must be larger<br />

than the pipe diameter. Other required equipment:<br />

• Clean 2–3 gal (approximately 10-L) plastic bucket<br />

• Plastic 1 qt (1-L) sample jars<br />

• Plastic storage bags for secondary leak containment<br />

Figure 21. Example of device for obtaining a sample from top to bottom of a resin bed.<br />

<strong>DOWEX</strong> <strong>Ion</strong> <strong>Exchange</strong> <strong>Resins</strong> 49 Water Conditioning Manual