RMG 4 I <strong>KNX</strong><br />

Switch actuators<br />

<strong>KNX</strong> SYSTEMS<br />

Actuators C load 4–12 channels MIX 2<br />

RMG 4 I <strong>KNX</strong> RME 4 I <strong>KNX</strong><br />

Description<br />

Common functions<br />

■ 4-way C load switching actuator MIX 2<br />

■ With current recognition<br />

■ For higher lamp loads<br />

■ Up to two extension modules MIX 1 or MIX<br />

2 can be connected to one basic module<br />

■ Device and <strong>KNX</strong> bus module can be<br />

swapped independently of each other<br />

■ Removable <strong>KNX</strong> bus module enables devices<br />

to be changed without repro-gramming<br />

6<br />

■ Manual set-up and use of switching actuators<br />

is possible without <strong>KNX</strong> bus module<br />

■ LED switching status display for each channel<br />

■ Manual operation on device (even without<br />

bus connection)<br />

■ Switching functions: E.g. On/Off, pulse, On/<br />

Off delay, staircase light with warning<br />

■ Logical links: e.g. lock, AND, release, OR<br />

Product selection Technical data<br />

Type Article number<br />

RMG 4 I <strong>KNX</strong> 4930210<br />

RME 4 I <strong>KNX</strong> 4930215<br />

Connection example<br />

RMG 4 I <strong>KNX</strong><br />

L N<br />

3 4 5 6<br />

C1 C2<br />

7 8 9 10<br />

C3<br />

<strong>KNX</strong><br />

C4<br />

N LL<br />

httpAdditional technical data at:<br />

www.theben.de/product/ Article number<br />

RMG 4 I <strong>KNX</strong><br />

■ Basic module MIX 2<br />

■ Can be upgraded to maximum of<br />

12 channels<br />

RME 4 I <strong>KNX</strong><br />

■ Extension module MIX 2<br />

■ For upgrading to maximum of<br />

12 channels<br />

RMG 4 I <strong>KNX</strong> RME 4 I <strong>KNX</strong><br />

Operating voltage <strong>KNX</strong> Bus voltage, (< 10 mA) –<br />

Operating voltage 110–240 V AC<br />

Frequency 45–65 Hz<br />

Stand-by consumption 1,3 W 0,0 W<br />

Width 4 modules<br />

Type of contact<br />

NO contact, 16 A (at 250 V AC, cos φ = 1),<br />

16 A (at 250 V AC, cos φ = 0.6)<br />

Ambient temperature –5 °C…+45 °C<br />

Protection rating IP 20<br />

Protection class II in accordance with EN 60 730-1<br />

RME 4 I <strong>KNX</strong><br />

L N<br />

3 4 5 6<br />

C1 C2<br />

7 8 9 10<br />

C3 C4<br />

N LL