Parameter<br />
P314<br />
Verification Time of the<br />
Serial Communication<br />
Description / Notes<br />
This parameter has the function to enable or disable, as well as to set the verification time<br />
of the serial communication. This protection acts when the serial communication between<br />
the master and the Soft-Starter is interrupted generating the respective indication or<br />
introducing an action as set at parameter P313.<br />
Note:<br />
Enable this function only if there is a cyclic serial communication with a master.<br />
Set the verification time according to the time of the telegrams sent by the master.<br />