DT-5 - Características e Especificações <strong>de</strong> Geradores<<strong>br</strong> />
Para <strong>de</strong>terminação da potência aparente do<<strong>br</strong> />
gerador, <strong>de</strong>vemos levar em consi<strong>de</strong>ração o<<strong>br</strong> />
rendimento dos <strong>geradores</strong> indicado nos catálogos,<<strong>br</strong> />
para fatores <strong>de</strong> potência entre 0.8 e 1.0.<<strong>br</strong> />
Então, levando em consi<strong>de</strong>ração o fator <strong>de</strong><<strong>br</strong> />
potência, a potência aparente fica:<<strong>br</strong> />
S =<<strong>br</strong> />
Pg Pn x<<strong>br</strong> />
=<<strong>br</strong> />
Cos 100 x Cos<<strong>br</strong> />
Exemplos:<<strong>br</strong> />
Numa indústria <strong>de</strong>ve ser instalado um Grupo<<strong>br</strong> />
Gerador Diesel para fornecer eletricida<strong>de</strong> às suas<<strong>br</strong> />
instalações, on<strong>de</strong> existem as seguintes fontes<<strong>br</strong> />
consumidoras:<<strong>br</strong> />
a) Iluminação 80 kVA cos = 0,7<<strong>br</strong> />
b) Aquecimento 152 kVA cos = 1,0<<strong>br</strong> />
c) 01 motor trifásico <strong>WEG</strong> - IP54 - 40 cv – IV pólos<<strong>br</strong> />
d) 01 motor trifásico <strong>WEG</strong> - IP54 - 60 cv – IV pólos<<strong>br</strong> />
e) 01 motor trifásico <strong>WEG</strong> - IP54 - 75 cv – IV pólos<<strong>br</strong> />
Do catálogo <strong>de</strong> motores trifásicos <strong>WEG</strong> obteremos:<<strong>br</strong> />
Motor 40 cv (30 kW), cos = 0,85, η = 90,9%<<strong>br</strong> />
Motor 60 cv (45 kW), cos = 0,88, η = 90,8%<<strong>br</strong> />
motor 75 cv (55 kW), cos = 0,90, η = 91,9%<<strong>br</strong> />
Para <strong>de</strong>terminação da potência foi consi<strong>de</strong>rado<<strong>br</strong> />
serviço contínuo. Será analisado posteriormente a<<strong>br</strong> />
influência da partida dos motores.<<strong>br</strong> />
Para o cálculo da potência ativa e aparente nos<<strong>br</strong> />
motores geralmente indica-se a potência útil no<<strong>br</strong> />
eixo. A potência ativa consumida abtém-se<<strong>br</strong> />
dividindo a potência útil pelo rendimento;<<strong>br</strong> />
Dos valores da potência ativa e cos do motor,<<strong>br</strong> />
obtém-se a potência aparente total consumida por<<strong>br</strong> />
ele;<<strong>br</strong> />
Com os valores <strong>de</strong> potência ativa e potência<<strong>br</strong> />
aparente, <strong>de</strong>termina-se a potência reativa<<strong>br</strong> />
consumida pelo motor.<<strong>br</strong> />
Portanto, para o motor <strong>de</strong> 40 cv teremos:<<strong>br</strong> />
Pu (kW) x 100<<strong>br</strong> />
P (kW)=<<strong>br</strong> />
=<<strong>br</strong> />
<<strong>br</strong> />
30<<strong>br</strong> />
90,9<<strong>br</strong> />
= 33,0 kW<<strong>br</strong> />
P (kW) 33,0<<strong>br</strong> />
S (kVA)= = = 38,8 kVA<<strong>br</strong> />
cos 0,85<<strong>br</strong> />
Q=<<strong>br</strong> />
Q=<<strong>br</strong> />
2<<strong>br</strong> />
2<<strong>br</strong> />
S(kVA ) - P(kW )<<strong>br</strong> />
2<<strong>br</strong> />
(38,8 ) - (33,0 ) = 20,4 kVAr<<strong>br</strong> />
2<<strong>br</strong> />
Desta maneira, e para as <strong>de</strong>mais cargas, obteremos<<strong>br</strong> />
os seguintes resultados da Tabela 4.1.<<strong>br</strong> />
CARGA COS η%<<strong>br</strong> />
S<<strong>br</strong> />
(kVA)<<strong>br</strong> />
P<<strong>br</strong> />
(kW)<<strong>br</strong> />
Q<<strong>br</strong> />
(kVAr)<<strong>br</strong> />
Iluminação 0.70 - 80 56 57,1<<strong>br</strong> />
Aquecimento 1.00 - 152 152 -<<strong>br</strong> />
Motor 40 cv 0.85 90,9 38.8 33.0 20.4<<strong>br</strong> />
Motor 60 cv 0.88 90,8 56.3 49.5 26.8<<strong>br</strong> />
Motor 75 cv 0.90 91,9 66.4 59.8 28.9<<strong>br</strong> />
Tabela 7.1 - Quadro Geral <strong>de</strong> Potência.<<strong>br</strong> />
Assim, a potência aparente do gerador será a soma<<strong>br</strong> />
<strong>de</strong> todas as parcelas <strong>de</strong> potência ativa e reativa das<<strong>br</strong> />
cargas:<<strong>br</strong> />
2<<strong>br</strong> />
2<<strong>br</strong> />
S= (P+P+<<strong>br</strong> />
1 2<<strong>br</strong> />
..... +P<<strong>br</strong> />
n ) +(Q+Q+<<strong>br</strong> />
1 2<<strong>br</strong> />
... +Q<<strong>br</strong> />
n )<<strong>br</strong> />
S = (56+152+33,0+49,5+59,8 ) + (57,1+0+ 20,4+ 26,8+ 28,9 )<<strong>br</strong> />
S = 375 kVA<<strong>br</strong> />
O fator <strong>de</strong> potência geral será:<<strong>br</strong> />
350,3<<strong>br</strong> />
Cos = P = = 0,934<<strong>br</strong> />
S 375<<strong>br</strong> />
Escolhendo o mo<strong>de</strong>lo <strong>de</strong> gerador:<<strong>br</strong> />
7.1.1. Linha G i-Plus<<strong>br</strong> />
Do catálogo <strong>de</strong> <strong>geradores</strong> <strong>WEG</strong> Linha G i-Plus,<<strong>br</strong> />
obtemos o gerador GTA311AI27, para tensão <strong>de</strong><<strong>br</strong> />
440V, com potência <strong>de</strong> 377 kVA.<<strong>br</strong> />
O rendimento do gerador com carga nominal está<<strong>br</strong> />
indicado no catálogo como 90,7%.<<strong>br</strong> />
Portanto, a potência mínima <strong>de</strong> acionamento do<<strong>br</strong> />
gerador consi<strong>de</strong>rando carga nominal será:<<strong>br</strong> />
PN =<<strong>br</strong> />
Pg (kVA) x<<strong>br</strong> />
<<strong>br</strong> />
2<<strong>br</strong> />
cos<<strong>br</strong> />
377 x 0,934<<strong>br</strong> />
=<<strong>br</strong> />
0, 907<<strong>br</strong> />
PN = 388 (kW)<<strong>br</strong> />
2<<strong>br</strong> />
47