For the Fitter<br />
32<br />
Terminal Explanation<br />
W1/W2 DIN atmospheric sensor or atmospheric sensor specified in atmospheric sensor list on page 24.<br />
LF Power supply company control, main release<br />
The controlled outer conductor LF of the power supply company is connected to this terminal - it is<br />
used to start the timing element (not applicable if NW [Neckarwerke] is set for the parameter „ST“).<br />
LZ Power supply company control, additional release<br />
Only used if the power supply company provides a second controlled outer conductor in the daytime<br />
charging time, otherwise this terminal remains unused.<br />
VR/LL Forward/backward switchover:<br />
Operating time control if NW (Neckarwerke) is set for the parameter „ST“.<br />
KU Characteristic switchover (reduction by the value set for the parameter „Ab“).<br />
Z1 Z1 = Clocked control line (L)<br />
Z2 Z2 = Unclocked control line, connected to N; single-wire control possible.<br />
The mains-voltage clock signal is applied at these terminals.<br />
Terminal Z2 is internally connected to terminal N. The clocked outer conductor is applied as a<br />
control signal to terminal Z1.<br />
L Mains voltage 200 - 230 V +10 % -15 %, AC 50 Hz.<br />
N When connecting the device, make sure that the outer conductor is connected to terminal L.<br />
SH SH = Charging contactor (see connection diagram on page 3 for SH).<br />
Dimensions of ELFAMATIC µC 3000<br />
<strong>14</strong>:<strong>53</strong> <strong>14</strong>:<strong>53</strong><br />
VR LF LZ KU<br />
ED<br />
SH<br />
SYN<br />
107 mm<br />
ELFAMATIC μC<br />
3000<br />
M P + –<br />
45 mm<br />
90 mm<br />
6 mm<br />
54,8 mm<br />
44 mm