06.03.2013 Views

Controls Start-Up, Operation, Service, and ... - Climayoreo

Controls Start-Up, Operation, Service, and ... - Climayoreo

Controls Start-Up, Operation, Service, and ... - Climayoreo

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

MINIMUM LOAD VALVE (MLVS, Configuration mode<br />

under sub-mode OPT1) — When this option is installed <strong>and</strong><br />

configured, the first stage of capacity is altered by energizing<br />

the Minimum Load valve relay. Once the control requires<br />

more capacity, the minimum load valve is deenergized <strong>and</strong><br />

normal capacity staging resumes with loaders <strong>and</strong> compressors.<br />

Similarly, the Minimum Load valve relay will be energized<br />

for the last stage of capacity to be used before the circuit<br />

is shut down.<br />

Configure Unit for Minimum Load Control — The chiller<br />

must be configured for minimum load control operation. This<br />

may be done using the Navigator. Set the Enable/Off/Remote<br />

Contact switch in the Off position.<br />

1. Press ESCAPE until ‘Select a Menu Item’ is displayed.<br />

2. Press to illuminate the Configuration mode LED.<br />

ENTER ENTER<br />

3. Press <strong>and</strong> to select ‘OPT1’. Press <strong>and</strong> then<br />

to select ‘MLV’.<br />

ENTER<br />

4. Press <strong>and</strong> enter the Password (use arrow<br />

ENTER<br />

keys <strong>and</strong> press for each digit) if required.<br />

ENTER<br />

5. Use to change the flashing ‘No’ to ‘Yes’. Press<br />

<strong>and</strong> the display says ‘MLV Yes’.<br />

The chiller is now configured for minimum load valve control.<br />

Test Minimum Load Relay Outputs — After the unit is configured,<br />

test the operation of the relay <strong>and</strong> solenoid valve using<br />

the <strong>Service</strong> Test mode.<br />

1. Switch the Enable/Off/Remote Contact switch to the<br />

‘Off’ position.<br />

2. Press ESCAPE on the Navigator to display ‘Select a Menu<br />

Item’ <strong>and</strong> press to illuminate the <strong>Service</strong> Test LED.<br />

ENTER<br />

3. Press <strong>and</strong> ‘TEST OFF’ will be displayed.<br />

ENTER<br />

4. Press (enter Password if required), <strong>and</strong> then<br />

ENTER to display ‘TEST ON’.<br />

5. Switch the EOR (Enable/Off/Remote Contact) switch to<br />

the “Enable” position.<br />

ENTER<br />

6. Press to select ‘COMP’ <strong>and</strong> press .<br />

ENTER<br />

7. Press to select ‘MLV OFF’. Press followed<br />

ENTER<br />

by <strong>and</strong> again. The minimum load valve output<br />

will be turned on. Both circuits’ solenoids are turned on at<br />

the same time.<br />

ENTER ENTER<br />

8. Press , followed by <strong>and</strong> again to turn<br />

the valve output off.<br />

Adjust Setting of Minimum Load Ball Valve — The minimum<br />

load ball valve must be adjusted to suit the application.<br />

Calibrate one circuit at a time as follows:<br />

1. Adjust the ball valve so that it is approximately half open.<br />

2. Operate the chiller in Manual Control mode, with one<br />

circuit operating, <strong>and</strong> all compressor loaders deenergized.<br />

3. Record the cooler ∆T (the difference between cooler<br />

entering fluid temperature <strong>and</strong> cooler leaving fluid<br />

temperature) at this fully unloaded condition.<br />

4. Use the Manual Control feature to enable the minimum<br />

load valve for the circuit that is operating.<br />

5. Observe <strong>and</strong> record the cooler ∆T with the minimum load<br />

valve energized.<br />

10<br />

6. Adjust the minimum load ball valve until the cooler<br />

temperature difference reading from Step 5 is equal to<br />

half of the temperature difference reading from Step 3.<br />

7. Open the ball valve to decrease the temperature difference<br />

or close the ball valve to increase the temperature<br />

difference (∆T). When the valve is adjusted correctly, the<br />

difference between cooler entering <strong>and</strong> leaving fluid temperatures<br />

when the minimum load control is energized<br />

must be at least half of the temperature difference when<br />

the minimum load control is deenergized. For example, if<br />

the difference between the cooler entering <strong>and</strong> leaving<br />

water temperature is 3° F with the valve deenergized,<br />

then the difference between cooler entering <strong>and</strong> leaving<br />

water temperature must be at least 1.5° F with the valve<br />

energized.<br />

Once the outputs have been tested <strong>and</strong> the ball valve<br />

adjusted, the installation is complete. Disable manual control<br />

<strong>and</strong> return chiller to desired operational status.<br />

CAPACITY CONTROL OVERRIDES — The following overrides<br />

will modify the normal operation of the routine.<br />

Deadb<strong>and</strong> Multiplier — The user configurable Deadb<strong>and</strong><br />

Multiplier (Z.GN, Configuration mode under sub-mode SLCT)<br />

has a default value of 2.0. The range is from 1.0 to 4.0. When<br />

set to other than 1.0, this factor is applied to the capacity Load/<br />

Unload Factor. The larger this value is set, the longer the control<br />

will delay between adding or removing stages of capacity.<br />

Figure 7 shows how compressor starts can be reduced over<br />

time if the leaving water temperature is allowed to drift a larger<br />

amount above <strong>and</strong> below the set point. This value should be set<br />

in the range of 3.0 to 4.0 for systems with small loop volumes.<br />

The Main Base Board (MBB) closely follows the rate of compressor<br />

cycling for each circuit.<br />

First Stage Override — If the current capacity stage is zero,<br />

the control will modify the routine with a 1.2 factor on adding<br />

the first stage to reduce cycling. This factor is also applied<br />

when the control is attempting to remove the last stage of<br />

capacity.<br />

Slow Change Override — The control prevents the capacity<br />

stages from being changed when the leaving fluid temperature<br />

is close to the set point (within an adjustable deadb<strong>and</strong>) <strong>and</strong><br />

moving towards the set point.<br />

Ramp Loading — (RL.S, Configuration mode under submode<br />

SLCT) — Limits the rate of change of leaving fluid<br />

temperature. If the unit is in a Cooling mode <strong>and</strong> configured<br />

for Ramp Loading, the control makes 2 comparisons before<br />

deciding to change stages of capacity. The control calculates a<br />

temperature difference between the control point <strong>and</strong> leaving<br />

fluid temperature. If the difference is greater than 4° F (2.2° C)<br />

<strong>and</strong> the rate of change (°F or °C per minute) is more than the<br />

configured Cooling Ramp Loading value (CRMP, Configuration<br />

mode under sub-mode SLCT), the control does not allow<br />

any changes to the current stage of capacity.<br />

Low Entering Fluid Temperature Unloading — When the<br />

entering fluid temperature is below the control point, the<br />

control will attempt to remove 25% of the current stages being<br />

used. If exactly 25% cannot be removed, the control removes<br />

an amount greater than 25%, but no more than necessary. The<br />

lowest stage will not be removed.<br />

Low Discharge Superheat — If a circuit’s discharge superheat<br />

is less than 15° F(8.3° C), the control does not increase the<br />

current capacity stage. If the discharge superheat is less than<br />

5° F(2.8° C) <strong>and</strong> decreasing, the circuit is unloaded every<br />

30 seconds until the superheat is greater than 5° F(2.8° C). The<br />

final capacity stage is not unloaded unless an alarm condition<br />

exists. This override is ignored for the first 3 minutes after a<br />

compressor is started.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!