Controller Resetting Procedure<br />
(Following Fault Shutdown)<br />
Use the following procedure to restart the generator set<br />
after a fault shutdown. Refer to Resetting Emergency<br />
Stop Switches earlier in this section to reset the<br />
generator set after an emergency stop.<br />
1. Move controller alarm horn switch to the SILENCE<br />
position. If equipped, A/V annunciator alarm horn<br />
and lamp are activated. Move A/V annunciator<br />
alarm switch to SILENCE to stop alarm horn. A/V<br />
annunciator lamp stays lit.<br />
2. Disconnect generator set from load with line circuit<br />
breaker or automatic transfer switch.<br />
3. Correct cause of fault shutdown. See Safety<br />
Precautions section of this manual before<br />
proceeding.<br />
4. Start generator set by moving the generator master<br />
switch to OFF/RESET and then to the RUN<br />
position. If equipped, A/V annunciator alarm horn<br />
sounds and lamp goes out.<br />
5. Verify that the cause of the shutdown has been<br />
corrected by test operating generator set.<br />
6. Reconnect generator to load via line circuit breaker<br />
or automatic transfer switch.<br />
7. Move generator master switch to AUTO position for<br />
start-up by remote transfer switch or remote<br />
start/stop switch. If equipped, move A/V<br />
annunciator alarm switch to NORMAL.<br />
8. Move controller alarm horn switch to the NORMAL<br />
position.<br />
Place generator master switch in the AUTO<br />
position before silencing alarm horn.<br />
<strong>TP</strong>-<strong>5353</strong> 8/94 Operation 2-9