21.03.2013 Views

Service Manual, 20-300 kW FR II (TP-5353) - ImageEvent

Service Manual, 20-300 kW FR II (TP-5353) - ImageEvent

Service Manual, 20-300 kW FR II (TP-5353) - ImageEvent

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Controller Resetting Procedure<br />

(Following Fault Shutdown)<br />

Use the following procedure to restart the generator set<br />

after a fault shutdown. Refer to Resetting Emergency<br />

Stop Switches earlier in this section to reset the<br />

generator set after an emergency stop.<br />

1. Move controller alarm horn switch to the SILENCE<br />

position. If equipped, A/V annunciator alarm horn<br />

and lamp are activated. Move A/V annunciator<br />

alarm switch to SILENCE to stop alarm horn. A/V<br />

annunciator lamp stays lit.<br />

2. Disconnect generator set from load with line circuit<br />

breaker or automatic transfer switch.<br />

3. Correct cause of fault shutdown. See Safety<br />

Precautions section of this manual before<br />

proceeding.<br />

4. Start generator set by moving the generator master<br />

switch to OFF/RESET and then to the RUN<br />

position. If equipped, A/V annunciator alarm horn<br />

sounds and lamp goes out.<br />

5. Verify that the cause of the shutdown has been<br />

corrected by test operating generator set.<br />

6. Reconnect generator to load via line circuit breaker<br />

or automatic transfer switch.<br />

7. Move generator master switch to AUTO position for<br />

start-up by remote transfer switch or remote<br />

start/stop switch. If equipped, move A/V<br />

annunciator alarm switch to NORMAL.<br />

8. Move controller alarm horn switch to the NORMAL<br />

position.<br />

Place generator master switch in the AUTO<br />

position before silencing alarm horn.<br />

<strong>TP</strong>-<strong>5353</strong> 8/94 Operation 2-9

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!