Features<br />
The numbered paragraphs following refer to Figure 2-7.<br />
1. Hourmeter. Hourmeter records generator set total<br />
operating hours for reference in scheduling<br />
maintenance.<br />
2. Oil Pressure Gauge. Gauge measures engine oil<br />
pressure.<br />
3. Water Temperature Gauge. Gauge measures<br />
engine coolant temperature.<br />
4. DC Voltmeter. Meter measures voltage of starting<br />
battery(ies).<br />
5. Emergency Stop (If equipped). Switch is used to<br />
instantly shut down the generator set in emergency<br />
situations. Reset switch after shutdown by rotating<br />
switch clockwise. Use the emergency stop switch<br />
for emergency shutdowns only. Use the<br />
switchgear-mounted operating controls to stop the<br />
set under normal circumstances. Local emergency<br />
stop switch is standard on <strong>20</strong>0-1600 <strong>kW</strong> models<br />
with Detroit Diesel Engine.<br />
6. Gauge Box Terminal Strips. Use terminal strips<br />
to connect switchgear control wiring to generator<br />
set governor control, crank relays, safety switches,<br />
gauge senders, etc.<br />
7. Connection Plug. Use plug to connect wiring<br />
harness from generator set governor control, crank<br />
relays, safety switches, gauge sender, etc., to<br />
gauge box terminal strips.<br />
8. Electronic Speed Switch. Switch signals engine<br />
control logic in switchgear to disconnect starter<br />
motor after start-up or shuts down the system if an<br />
overspeed fault occurs. Speed switch settings are<br />
adjustable for crank and overspeed.<br />
<strong>TP</strong>-<strong>5353</strong> 8/94 Operation 2-17