Is fi re protection required for metal roofs?<br />

<strong>Sustainable</strong> <strong>Construction</strong> -<br />

For standalone buildings, the metal roof need not be fi re protected.<br />

However for buildings of different heights that abut each other,<br />

5m width of the roof over the lower part requires 1 hour fire resistance<br />

OR<br />

9m height of the external wall abutting the lower area requires at least 1<br />

hour fire resistance.<br />

This is to prevent vertical spread of fire<br />

through the roof from the lower part of the<br />

building to the higher part.<br />

In such cases, fire-rated ceiling board system<br />

can be used to provide the necessary fire<br />

protection.<br />

38<br />

Minimum 9m of<br />

external wall to<br />

be fire-rated<br />

Minimum 5m of<br />

roof to be fi red-rated