Is fi re protection required for metal roofs?<br />
<strong>Sustainable</strong> <strong>Construction</strong> -<br />
For standalone buildings, the metal roof need not be fi re protected.<br />
However for buildings of different heights that abut each other,<br />
5m width of the roof over the lower part requires 1 hour fire resistance<br />
OR<br />
9m height of the external wall abutting the lower area requires at least 1<br />
hour fire resistance.<br />
This is to prevent vertical spread of fire<br />
through the roof from the lower part of the<br />
building to the higher part.<br />
In such cases, fire-rated ceiling board system<br />
can be used to provide the necessary fire<br />
protection.<br />
38<br />
Minimum 9m of<br />
external wall to<br />
be fire-rated<br />
Minimum 5m of<br />
roof to be fi red-rated