A Guide Fire on Protection Fire Protection and Performance-based and Performance-based Fire Engineering Fire Engineering<br />
Cementitious spray-fi reproofi ng<br />
How can the surface appearance of the<br />
spray-fireproofing be improved?<br />
1. Hand troweling may be applied to some sprayapplied<br />
fireproofing products to improve the<br />
surface appearance of the products.<br />
2. Surface decorative paint may be used as an<br />
overspray on spray-applied fireproofing products<br />
for sealing, surface colouring or to increase light<br />
reflection.<br />
Other important considerations:<br />
a) Primed/Painted Steel Substrates<br />
Spray-fireproofing obtains its maximum bond when<br />
applied to unprimed/unpainted structural steel.<br />
Priming of interior structural steel is generally<br />
unnecessary. The use of non-compatible primer<br />
may result in bond failure. Designers should consult<br />
the product manufacturer for guidance.<br />
b) Experienced fireproofing applicators<br />
To ensure the fireproofing is properly carried out, it is recommended that the manufacturer<br />
confirm the applicator has been properly trained and has the experience to meet the<br />
qualification of an approved applicator for the spray-fireproofing product.<br />
c) Track records<br />
The applicator and manufacturer are to provide a list of local project references for review by<br />
the designers.<br />
53<br />
Unpainted steel member