Chapter 5<br />

Setpoints Menu<br />

The <strong>SUREFLOW</strong> <strong>Room</strong> <strong>Pressure</strong> <strong>Controller</strong> is a very versatile device which may<br />

be adjusted to control and alarm at different setpoints to meet your specific<br />

application. This Chapter is a guide to the SETPOINTS menu of the<br />

<strong>SUREFLOW</strong>. This menu is used to select the control, remote, low alarm, high<br />

alarm, and no-flow alarm setpoints.<br />

Adjusting the setpoints is done by using the keypad operations detailed in<br />

Chapter 4 of this manual. The setpoints may also be adjusted using the RS-485<br />

Communications port and the RS-232 Serial Port. Data in the setpoint menu is<br />

stored by pressing the SELECT key after a data change has been made. The unit<br />

will respond that data is saved by indicating "Saving Data" on the display<br />

and sounding three beeps.<br />

If you are unfamiliar with the keystroke procedure to program the controller,<br />

please read Chapter 4, "Structure of Instrument," for a detailed explanation.<br />

Access Code An access code is used to prohibit unauthorized access to the SETPOINTS menu. If<br />

you attempt to enter the SETPOINTS menu when the access code is enabled, "Enter<br />

Code" flashes on and off on the display. To enter the menu, enter the SETPOINTS<br />

menu access code found in Appendix E.<br />

Description of<br />

the SETPOINTS<br />

Menu Items<br />

If the access code is entered correctly, the SETPOINTS menu will be accessed.<br />

Item<br />

SETPOINT<br />

Description<br />

The SETPOINT function is used to set the control setpoint.<br />

The <strong>SUREFLOW</strong> controller will maintain this room pressure<br />

during normal operating conditions.<br />

REMOTE SETP The REMOTE SETP function is used to set a remote control<br />

setpoint. This function instructs the <strong>SUREFLOW</strong> to control at<br />

the REMOTE SETP setpoint. A REMOTE SETP condition<br />

is initiated when the REMOTE SETP contact input has been<br />

closed, or a command is received through the RS-485<br />

network.<br />

LOW ALARM The LOW ALARM function is used to set the LOW ALARM<br />

setpoint. A low room pressure alarm condition is initiated<br />

when the magnitude of the room pressure falls below or<br />

goes in the opposite direction of the LOW ALARM setpoint.<br />

21