WARNING: The low and high alarms must be set in the same direction as the setpoint. The<br />

<strong>SUREFLOW</strong> does not allow a positive setpoint and a negative low alarm.<br />

Constraints There are a number of constraints that prohibit the user from incorrectly adjusting the<br />

setpoints. These are as follows:<br />

1. The magnitude of the LOW ALARM setpoint must be set at least 20 ft/min<br />

below the control SETPOINT (see Appendix C for relationship between<br />

pressure and velocity). The <strong>SUREFLOW</strong> will not allow the LOW ALARM<br />

setpoint to be set any closer. For example, if the control SETPOINT is set at<br />

-100 ft/min, the highest the LOW ALARM setpoint can be is -80 ft/min. This<br />

is done to prevent nuisance alarms from occurring during natural fluctuations<br />

of the system.<br />

2. The magnitude of the HIGH ALARM setpoint must be at set at least 20 ft/min<br />

above the control SETPOINT. The <strong>SUREFLOW</strong> will not allow the HIGH<br />

ALARM setpoint to be set any closer. For example, if your control<br />

SETPOINT is set at -100 ft/min, the lowest the HIGH ALARM setpoint can<br />

be is -120 ft/min. This is done to prevent nuisance alarms from occurring<br />

during natural fluctuations of the system.<br />

3. The alarm setpoints automatically follow the same alarm offsets when the<br />

<strong>SUREFLOW</strong> is placed in the REMOTE SETP mode. Consider a unit set up as<br />

follows:<br />

LOW ALARM SETPOINT HIGH ALARM<br />

-60 FT/MIN -100 FT/MIN -150 FT/MIN<br />

(-.00030 "H2O) (-.00085 "H2O) (-.00200 "H2O)<br />

When this unit is placed in the REMOTE SETP mode where the REMOTE<br />

SETP is set to 80 ft/min, the following conditions will be employed:<br />

REMOTE SETP REMOTE SETP REMOTE SETP<br />

LOW ALARM SETPOINT HIGH ALARM<br />

+40 FT/MIN +80 FT/MIN +130 FT/MIN<br />

(+.00010 "H2O) (+.00055 "H2O) (+.00150 "H2O)<br />

Notice the 40 ft/min difference between the LOW ALARM and SETPOINT<br />

was maintained in both the normal and setback modes of operation. Similarly,<br />

the 50 ft/min difference between the SETPOINT and the HIGH ALARM was<br />

also maintained in both modes.<br />

Setpoints Menu 23<br />