WARNING: The CONTROL OUTP function should not be used while experiments are<br />

being performed in the laboratory. A closed damper may create dangerously<br />

low air flows while an opened damper may create dangerously high air flows<br />

thus not maintaining a safe room pressure.<br />

ANALOG OUTP The ANALOG OUTP item is used to vary the analog output<br />

from the <strong>SUREFLOW</strong> unit. When this item is entered, a<br />

number will be shown on the display indicating the last<br />

analog output value. The value displayed ranges from 0 to<br />

255. The value 255 corresponds to the lowest voltage<br />

(current) output and 0 corresponds to the highest voltage<br />

(current) output. Pressing the ▲ arrow key will decrease<br />

the analog output and increase the value displayed. Pressing<br />

the ▼ arrow key will increase the analog output and decrease<br />

the value displayed.<br />

The ANALOG OUTP function can be used in conjunction<br />

with a volt meter to verify the analog output is correct.<br />

Escaping from this item is done only by pressing the MENU<br />

key. The analog output will return to the value<br />

corresponding to the measured room pressure when the<br />

MENU key is pressed.<br />

NO-FLO RELAY The NO-FLO RELAY item is used to change the state of the<br />

no-flow alarm relay. When this item is entered, the display<br />

will indicate either OPEN or CLOSED. The arrow keys are<br />

used to toggle the state of the relay. The ▲ arrow key is<br />

used to OPEN the alarm contact. The ▼ arrow key is used to<br />

CLOSE the alarm contact. When the contact is closed, the<br />

NO-FLO RELAY should be in an alarm condition.<br />

Escaping from this item is done only by pressing the MENU<br />

key. The <strong>SUREFLOW</strong> will return the NO-FLO RELAY to its<br />

state prior to entering this item when the MENU key is<br />

pressed.<br />

LOW RELAY The LOW RELAY item is used to change the state of the low<br />

alarm relay. When this item is entered, the display will<br />

indicate either OPEN or CLOSED. The arrow keys are used<br />

to toggle the state of the relay. The ▲ arrow key is used to<br />

OPEN the alarm contact. The ▼ arrow key is used to CLOSE<br />

the alarm contact. When the contact is closed, the LOW<br />

RELAY should be in an alarm condition.<br />

Escaping from this item is done only by pressing the MENU<br />

key. The <strong>SUREFLOW</strong> will return the LOW RELAY to its state<br />

prior to entering this item when the MENU key is pressed.<br />

40 Chapter 9