❽ Check the calibration. Escape back to the<br />

normal operating level, and verify that<br />

measured room pressure on the <strong>SUREFLOW</strong> is<br />

close to the velocity measured by the air<br />

velocity meter. Use the following steps to<br />

escape to the normal operating level for<br />

verification:<br />

❾ If the velocities do match, go to step 10. If<br />

the <strong>SUREFLOW</strong> velocity does not match the<br />

air velocity meter measurement, the<br />

SENSOR SPAN function must be repeated.<br />

Obtain direct access to the SENSOR SPAN<br />

item using the following keystrokes:<br />

Repeat steps 3 through 6 to adjust the SENSOR<br />

SPAN.<br />

32 Chapter 7<br />

MENU<br />

CALIBRATION<br />

CONTROL<br />

MENU<br />

VELOCITY<br />

100 FT/MIN<br />

MENU<br />

SETPOINTS<br />

CONFIGURE<br />

▼<br />

SETPOINTS<br />

CONFIGURE<br />

▼<br />

CONFIGURE<br />

CALIBRATION<br />

SELECT<br />

CALIBRATION<br />

SENSOR SPAN