The recorder sends messages for distribution by a remote e-mail server. The e-mail<br />

server is located by its IP address as set-up in the communications set-up options. When<br />

the recorder sends an e-mail message, it locates the e-mail server you have configured<br />

and uses SMTP (Simple Message Transfer Protocol) to send the message to the e-mail<br />

server. SMTP allows the recorder to send messages to an e-mail server without having<br />

its own e-mail address; because of this the e-mail server will not be able to send any reply<br />

back to the recorder.<br />

Factory<br />

Function: Unit Calibration and Alarm card setup<br />

Type: Menu selection<br />

Description: Calibration of analogue input card and configuration of Relay/Digital.<br />

Default: N/A<br />

From the Factory option on the General menu use the directional key to select, as<br />

shown in ”Setup’ on page 31, press the enter button to generate the sub menus. Use<br />

this menu route to calibrate the analogue card for input or output of analogue signal. The<br />

Drives item is for the 1.4 Mbyte floppy drive disk only. Reset Setup will reset to the factory<br />

settings, highlight and press enter button. Follow on-screen instructions during this procedure.<br />

Calibrate Input<br />

<strong>Recorder</strong><br />

Ethernet<br />

LAN<br />

Local Area Network<br />

Mail Server<br />

The type of Analogue card fitted in this recorder has the following menu screens,<br />

within the Calibrate Input option. Up to 6 analogue channels are available. Individual<br />

input channels can be switched on or off by selecting Inputs and entering a tick or a cross<br />

in the Calibrate option.<br />

Select Analogue In ‘All’ to identify which channels require calibration using a ✓.<br />

‘F’ indicates the input is calibrated to the factory setting. If any power loss should<br />

occur the unit will retain the calibration settings at the time of power loss.<br />

Input channels can be calibrated individually, indicated by the disappearance of the<br />

‘F’. The other inputs are not effected and will calibrate to the factory settings.<br />

40 43-TV-25-20 GLO Issue 5 06/04 UK<br />