Water heater<br />
4.2.1 Termix Novi<br />
Domestic hot water (DHW)<br />
Substati<strong>on</strong><br />
type<br />
Novi Type 1<br />
Novi Type 2<br />
Heat exch<strong>an</strong>ger<br />
XB06-H-26<br />
IHPT 3.0<br />
XB06-H-40<br />
IHPT 3.0<br />
DHW Capacity<br />
kW<br />
EXTENSION OPTIONS:<br />
• Cover, grey-lacquered steel<br />
(Designed by Jacob Jensen)<br />
• Safety valve<br />
• GTU pressure equalizer, eliminates<br />
safety valve discharge piping<br />
• Ball valves <strong>on</strong> all c<strong>on</strong>necti<strong>on</strong>s<br />
• Booster pump (increases DH flow)<br />
• Circulati<strong>on</strong> pipe/c<strong>on</strong>necti<strong>on</strong> <strong>with</strong><br />
n<strong>on</strong>-return valve<br />
TECHNICAL PARAMETERS:<br />
Nominal pressure: PN 16<br />
DH supply temperature: T = 120 °C<br />
max<br />
DCW static pressure: p = 1.5 bar<br />
min<br />
Brazing material (HEX): Copper<br />
Weight incl. cover: 7-9 kg<br />
(incl. packing)<br />
Cover: Greylacquered<br />
steel<br />
DHW: Capacity examples<br />
Supply flow<br />
Primary °C<br />
33<br />
Return flow<br />
Primary °C<br />
Introducti<strong>on</strong> to the product r<strong>an</strong>ge<br />
Dimensi<strong>on</strong>s (mm):<br />
With insulati<strong>on</strong>:<br />
H 432 x W 300 x D 155<br />
With cover:<br />
H 442 x W 315 x D 165<br />
Pipes dimensi<strong>on</strong>s (mm):<br />
Primary: Ø 18<br />
Sec<strong>on</strong>dary: Ø 18<br />
C<strong>on</strong>necti<strong>on</strong>s sizes:<br />
DH + DCW + DHW: G ¾”<br />
(ext. thread)<br />
DHW °C<br />
Pressure loss<br />
Primary kPa*<br />
DHW Tap load<br />
l/min<br />
32.3 60 19.8 10/45 20 13,3<br />
40.3 60 20.7 10/45 29 16,6<br />
43 70 17.4 10/45 20 17,7<br />
53 70 18.5 10/45 29 21,8<br />
29 60 24.3 10/50 20 10,5<br />
60 24.6 10/50 29 12,6<br />
41 70 19.6 10/50 20 14,8<br />
50 70 20.8 10/50 29 18,0<br />
32.3 55 21.9 10/45 22 13,3<br />
38 55 22.2 10/45 30 15,7<br />
38 60 19.6 10/45 20 15,7<br />
48.7 60 19.6 10/45 32 20,1<br />
50 70 16.4 10/45 20 20,6<br />
57 70 17.1 10/45 32 23,3<br />
34 60 23.4 10/50 20 12,3<br />
44 60 24.1 10/50 32 15,9<br />
48 70 18.8 10/50 20 17,3<br />
61.5 70 19.4 10/50 32 22,2<br />