Water heater<br />

4.2.2 Termix One B<br />

Domestic hot water (DHW)<br />

Substati<strong>on</strong><br />

type Termix<br />

One-B<br />

Type 1<br />

w/AVTB 15<br />

Type 2<br />

w/AVTB 20<br />

Type 3<br />

w/AVTB 20<br />

5 to 10**<br />

households<br />

DHW: Capacity examples, 10 °C/50 °C<br />

DHW<br />

Capacity<br />

kW<br />

Supply<br />

flow<br />

Primary<br />

°C<br />

Return<br />

flow<br />

Primary<br />

°C<br />

EXTENSION OPTIONS:<br />

• Cover, grey-lacquered steel<br />

(Designed by Jacob Jensen)<br />

• Safety valve<br />

• GTU pressure equalizer, eliminates<br />

safety valve discharge piping<br />

• Circulati<strong>on</strong> set, D<strong>an</strong>foss MTCV <strong>an</strong>d<br />

check valve<br />

• Ball valves <strong>on</strong> all c<strong>on</strong>necti<strong>on</strong>s<br />

• Booster pump (increases DH flow)<br />

TECHNICAL PARAMETERS:<br />

Nominal pressure: PN 16<br />

DH supply temperature: T = 120 °C<br />

max<br />

DCW static pressure: p = 0.5 bar<br />

min<br />

Brazing material (HEX): Copper<br />

Weight incl. cover: 10-12 kg<br />

(incl. packing)<br />

Cover: Greylacquered<br />

steel<br />

Pressure<br />

loss<br />

Primary<br />

*kPa<br />

35<br />

DHW<br />

Tap load<br />

l/min.<br />

29.3 60 23.0 20 10.5<br />

38.2 60 25.2 45 13.7<br />

37.8 70 20.0 20 13.6<br />

34.7 60 24.4 20 12.4<br />

47.1 60 26.8 45 16.9<br />

45.1 70 21.3 20 1 6.2<br />

60 60 23.0 35 21.3<br />

66 60 24.0 45 23.8<br />

80 70 20.3 35 28.8<br />

90 70 21.0 45 32.3<br />

* Heat meter not incl.<br />

** Capacity for 10 households at 70 °C DH flow temperature<br />

(Please c<strong>on</strong>tact <strong>your</strong> local D<strong>an</strong>foss representative for capacity examples at other temperature c<strong>on</strong>diti<strong>on</strong>s)<br />

Introducti<strong>on</strong> to the product r<strong>an</strong>ge<br />

Dimensi<strong>on</strong>s (mm):<br />

Without cover:<br />

H 428 x W 312 x D 155 (type 1 + 2)<br />

H 468 x W 312 x D 155 (type 3)<br />

With cover:<br />

H 430 x W 315 x D 165 (type 1 + 2)<br />

H 470 x W 315 x D 165 (type 3)<br />

Pipes dimensi<strong>on</strong>s (mm):<br />

Primary: Ø 18<br />

Sec<strong>on</strong>dary: Ø 18<br />

C<strong>on</strong>necti<strong>on</strong>s sizes:<br />

DH + DCW + DHW: G ¾”<br />

(ext. thread)