Water heater<br />
4.2.2 Termix One B<br />
Domestic hot water (DHW)<br />
Substati<strong>on</strong><br />
type Termix<br />
One-B<br />
Type 1<br />
w/AVTB 15<br />
Type 2<br />
w/AVTB 20<br />
Type 3<br />
w/AVTB 20<br />
5 to 10**<br />
households<br />
DHW: Capacity examples, 10 °C/50 °C<br />
DHW<br />
Capacity<br />
kW<br />
Supply<br />
flow<br />
Primary<br />
°C<br />
Return<br />
flow<br />
Primary<br />
°C<br />
EXTENSION OPTIONS:<br />
• Cover, grey-lacquered steel<br />
(Designed by Jacob Jensen)<br />
• Safety valve<br />
• GTU pressure equalizer, eliminates<br />
safety valve discharge piping<br />
• Circulati<strong>on</strong> set, D<strong>an</strong>foss MTCV <strong>an</strong>d<br />
check valve<br />
• Ball valves <strong>on</strong> all c<strong>on</strong>necti<strong>on</strong>s<br />
• Booster pump (increases DH flow)<br />
TECHNICAL PARAMETERS:<br />
Nominal pressure: PN 16<br />
DH supply temperature: T = 120 °C<br />
max<br />
DCW static pressure: p = 0.5 bar<br />
min<br />
Brazing material (HEX): Copper<br />
Weight incl. cover: 10-12 kg<br />
(incl. packing)<br />
Cover: Greylacquered<br />
steel<br />
Pressure<br />
loss<br />
Primary<br />
*kPa<br />
35<br />
DHW<br />
Tap load<br />
l/min.<br />
29.3 60 23.0 20 10.5<br />
38.2 60 25.2 45 13.7<br />
37.8 70 20.0 20 13.6<br />
34.7 60 24.4 20 12.4<br />
47.1 60 26.8 45 16.9<br />
45.1 70 21.3 20 1 6.2<br />
60 60 23.0 35 21.3<br />
66 60 24.0 45 23.8<br />
80 70 20.3 35 28.8<br />
90 70 21.0 45 32.3<br />
* Heat meter not incl.<br />
** Capacity for 10 households at 70 °C DH flow temperature<br />
(Please c<strong>on</strong>tact <strong>your</strong> local D<strong>an</strong>foss representative for capacity examples at other temperature c<strong>on</strong>diti<strong>on</strong>s)<br />
Introducti<strong>on</strong> to the product r<strong>an</strong>ge<br />
Dimensi<strong>on</strong>s (mm):<br />
Without cover:<br />
H 428 x W 312 x D 155 (type 1 + 2)<br />
H 468 x W 312 x D 155 (type 3)<br />
With cover:<br />
H 430 x W 315 x D 165 (type 1 + 2)<br />
H 470 x W 315 x D 165 (type 3)<br />
Pipes dimensi<strong>on</strong>s (mm):<br />
Primary: Ø 18<br />
Sec<strong>on</strong>dary: Ø 18<br />
C<strong>on</strong>necti<strong>on</strong>s sizes:<br />
DH + DCW + DHW: G ¾”<br />
(ext. thread)