9. FAQ<br />
Advises to design <strong>an</strong>d installati<strong>on</strong><br />
1. Wet rooms set up<br />
The combining of wet rooms (bathroom,<br />
toilet <strong>an</strong>d kitchen) <strong>with</strong>in <strong>an</strong> apartment<br />
c<strong>an</strong> not <strong>on</strong>ly save <strong>on</strong> costs <strong>with</strong> less<br />
c<strong>on</strong>structi<strong>on</strong> <strong>an</strong>d installati<strong>on</strong> materials –<br />
fin<strong>an</strong>cial benefits, such as higher rental<br />
income or appropriati<strong>on</strong>, c<strong>an</strong> also be<br />
generated <strong>with</strong> greater utility space.<br />
A dist<strong>an</strong>ce of 6 meters between the<br />
flat stati<strong>on</strong> <strong>an</strong>d the furthest c<strong>on</strong>sumpti<strong>on</strong><br />
point should not be exceeded to<br />
rule out delay times when turning <strong>on</strong><br />
hot water. If more th<strong>an</strong> that, circulati<strong>on</strong><br />
pump should be added to maintain the<br />
end user comfort.<br />
2. Noise <strong>an</strong>d fire preventi<strong>on</strong><br />
The applicable noise <strong>an</strong>d fire preventi<strong>on</strong><br />
regulati<strong>on</strong>s must be c<strong>on</strong>cerned during<br />
flat stati<strong>on</strong> in wall installati<strong>on</strong>.<br />
The flat stati<strong>on</strong> should be installed in order<br />
to preserve fire preventi<strong>on</strong> secti<strong>on</strong>s.<br />
During design must be ensured that<br />
applicable regulati<strong>on</strong>s are complied <strong>an</strong>d<br />
additi<strong>on</strong>al measures are used to ensure<br />
that neither noise nor fire preventi<strong>on</strong><br />
are impaired.<br />
3. Heat insulati<strong>on</strong><br />
C<strong>on</strong>tinuous <strong>an</strong>d high quality insulati<strong>on</strong><br />
<strong>on</strong> hot pipelines is extremely import<strong>an</strong>t.<br />
This applies in particular to the distributi<strong>on</strong><br />
set up <strong>on</strong> <strong>system</strong>s <strong>with</strong> flat stati<strong>on</strong>s.<br />
As these pipes are in operati<strong>on</strong> around<br />
the clock the entire year l<strong>on</strong>g, solid<br />
insulati<strong>on</strong> <strong>with</strong>out gaps is indispensable.<br />
Depending <strong>on</strong> the local regulati<strong>on</strong>s,<br />
a minimum insulati<strong>on</strong> of 2/3 of the pipe<br />
diameter, but at least <strong>an</strong> insulati<strong>on</strong><br />
thickness of 30 mm, must be provided.<br />
Insulati<strong>on</strong> <strong>on</strong> the fittings at the distributi<strong>on</strong><br />
pipes is also ideal, as higher losses<br />
c<strong>an</strong> also occur because of the turbulent<br />
flows caused by the optimum heat<br />
tr<strong>an</strong>sfers. The use of factory m<strong>an</strong>ufactured<br />
insulating shells, offered by m<strong>an</strong>y<br />
m<strong>an</strong>ufacturers, is ideal for these kinds<br />
of valves. With m<strong>an</strong>ually produced<br />
insulating shells you must ensure that,<br />
in additi<strong>on</strong> to the shell‘s insulati<strong>on</strong><br />
thickness, they also close tightly <strong>an</strong>d no<br />
c<strong>on</strong>vecti<strong>on</strong> occurs in the gaps.<br />
4. Thermosiph<strong>on</strong><br />
<strong>with</strong> buffer c<strong>on</strong>necti<strong>on</strong><br />
Instead of fault pr<strong>on</strong>e n<strong>on</strong> return valves,<br />
the c<strong>on</strong>necti<strong>on</strong>s of the heat exch<strong>an</strong>ger‘s<br />
load lines <strong>an</strong>d the solar <strong>system</strong> <strong>on</strong> the<br />
buffer t<strong>an</strong>k should be provided <strong>with</strong><br />
a thermo siph<strong>on</strong>, whereby the siph<strong>on</strong><br />
height should corresp<strong>on</strong>d <strong>with</strong> 10 times<br />
the pipe diameter.<br />
5. Inflow speed <strong>with</strong> buffer t<strong>an</strong>k<br />
All supply pipes c<strong>on</strong>nected to a buffer<br />
t<strong>an</strong>k should be c<strong>on</strong>figured for a<br />
maximum inflow speed of 0.1 m/s; this<br />
prevents turbulences in the buffer t<strong>an</strong>k<br />
<strong>an</strong>d mixing of the different temperature<br />
layers.<br />
6. Temperature measurement<br />
in the buffer t<strong>an</strong>k<br />
When selecting the buffer t<strong>an</strong>k you<br />
must ensure measurement c<strong>on</strong>necti<strong>on</strong>s<br />
(as immersi<strong>on</strong> sensors) to measure the<br />
available water temperatures.<br />
The use of a heat c<strong>on</strong>ducti<strong>on</strong> paste<br />
is recommended when installing the<br />
temperature sensor for improved heat<br />
c<strong>on</strong>ductivity.<br />
7. Radiators in general areas<br />
The complete implementati<strong>on</strong> of<br />
hydr<strong>on</strong>ic c<strong>on</strong>cept must not be forgotten<br />
when heating general areas (e.g.<br />
corridors, laundry room, drying room,<br />
hobby room, etc.). This me<strong>an</strong>s:<br />
• Use of a differential pressure c<strong>on</strong>troller<br />
in the radiator c<strong>on</strong>necti<strong>on</strong> pipe<br />
• Radiator valve sets presetting<br />
• Use of a return temperature limiter<br />
A flat stati<strong>on</strong> is also a good soluti<strong>on</strong> if<br />
hot water is required in a general area<br />
(e.g. laundry room).<br />
70<br />
FAQ<br />
8. Rooms <strong>with</strong> more th<strong>an</strong> <strong>on</strong>e<br />
radiator<br />
With radiator <strong>system</strong>s <strong>with</strong> flat stati<strong>on</strong>s,<br />
all radiators should be equipped <strong>with</strong><br />
thermostatic valves. All radiator thermostats<br />
<strong>with</strong>in a room should be set to the<br />
same value to ensure a c<strong>on</strong>st<strong>an</strong>t room<br />
temperature.<br />
Fluctuating room temperature could be<br />
prevented by using high quality radiator<br />
thermostats.<br />
Some excepti<strong>on</strong>s are radiators in reference<br />
rooms which, in combinati<strong>on</strong> <strong>with</strong><br />
a room thermostat <strong>an</strong>d a z<strong>on</strong>e valve, are<br />
resp<strong>on</strong>sible for the heat supply for the<br />
entire apartment.<br />
9. C<strong>on</strong>necting pressure<br />
measurement pipes<br />
If a m<strong>an</strong>ometer or a measurement pipe<br />
is c<strong>on</strong>nected for pressure measuring,<br />
this c<strong>on</strong>necti<strong>on</strong> should be made, if possible,<br />
<strong>on</strong> vertical pipelines.<br />
If the pressure measurement c<strong>an</strong> <strong>on</strong>ly<br />
be made <strong>on</strong> a horiz<strong>on</strong>tal pipe because<br />
of structural c<strong>on</strong>diti<strong>on</strong>s, the c<strong>on</strong>necti<strong>on</strong><br />
must be made horiz<strong>on</strong>tally in the centre<br />
of the pipe.<br />
If these guidelines are not observed<br />
<strong>with</strong> the arr<strong>an</strong>gement of the pressure<br />
measurement pipes, trapped air<br />
(c<strong>on</strong>necti<strong>on</strong> above) or dirt build ups<br />
(c<strong>on</strong>necti<strong>on</strong> below) c<strong>an</strong> cause err<strong>on</strong>eous<br />
measurements.<br />
Commissi<strong>on</strong>ing<br />
of flat stati<strong>on</strong>s<br />
All flat stati<strong>on</strong>s must be submitted to<br />
commissi<strong>on</strong>ing after the whole <strong>system</strong><br />
is thoroughly rinsed. This should be<br />
documented as a test log (per unit).<br />
D<strong>an</strong>foss provides appropriate commissi<strong>on</strong>ing<br />
for D<strong>an</strong>foss flat stati<strong>on</strong>s.