CASE NO. 1 - IMPROPER SOILS PREPARATION<br />

CASE STUDIES<br />

This case is a residential building located in Kingwood, Texas. It is a two story<br />

dwelling with a reinforced concrete slab-on-ground foundation. The foundation was<br />

measured to be significantly lower in the center of the building than around the<br />

perimeter, which, by itself, was not level. This condition is diagramed in Figure 1.<br />

There was a significant amount of foundation induced damage observed. <strong>Soil</strong> testing<br />

showed that there were fi 11 soils under the building which had a Plastic Index of<br />

from 38 to 52 percent. The soils near the perimeter had a Plasticity Index of from<br />

18 to 38 percent. The soils under the foundat 1 on were s 1 gni fi cantl y drier than<br />

those at the perimeter. The <strong>Soil</strong>s Engineer concluded that the problems with this<br />

foundation occurred because of soils swelling at the perimeter.<br />

The foundation was repaired using pressed, interconnected piles. There were-51 piles<br />

placed under the perimeter grade beams and 35 placed under interior grade beams at a<br />

cost in the neighborhood of $25,000, for the foundation repair only. The cost to<br />

fix the damage created by the repair process is not known, but would be extensive.<br />

The cause of this problem was the failure to construct a foundation that was appropriate<br />

for the soil conditions that existed and the improper use of fill soils.<br />

CASE NO. 2 - INADEQUATE DESIGN<br />

This case concerns a two-story residence 1 ocated in the city of Fulshear, Texas.<br />

This was a custom designed and constructed building for the owner. There was no<br />

previous building on this site. Shortly after the owners moved in, the walls began<br />

to show cracking, separations occurred, and some doors became difficult to close.<br />

The relative heights of the foundation slab were measured and the results are shown<br />

in Figure 2. Obviously, there was a significant amount of subsidence that occurred<br />

in the center part of the building. <strong>Soil</strong> testing showed the soils under the foundation<br />

to have low strengths and to be moisture sensitive; whereas, the soils around<br />

the perimeter had high PI's and good strengths. The concrete strength was only<br />

2,000 psi versus the 3,000 psi that was specified.<br />

The basics of the foundation design are shown in Figure 2. Of significance, the<br />

interior grade beam stiffeners were only 12 inches deep and 6 inches wide. There<br />

was no reference to a soil test indicated on the drawings. In our opinion, the<br />

design was not appropriate for the soil conditions at this site and the low concrete<br />

strength precluded repair. No attempt was made to repair this building. Instead,<br />

it was torn down.<br />

CASE NO. 3 - POOR DRAINAGE PRACTICES<br />

, The building that is the subject of this analysis is a two story dwelling which is<br />

located in the Village of Southside Place, which is an enclave of Houston, Texas.<br />

This was a custom designed and constructed building whose foundation was a reinforced<br />

concrete, grade-beam-stiffened, slab type of foundation supported on drilled<br />

piers. The foundation plans contained the Seal of an Engineer and a soil test was<br />

referenced on the plans. These soils had a very high plasticity index.<br />