Three-Phase<br />

Electric<br />

Panel<br />

Q3D Series<br />

ACCESSORIES<br />

APPLICATIONS<br />

• Protection and control of a three-phase submersible electric<br />

pump.<br />

SPECIFICATIONS<br />

• Manual control through an<br />

control<br />

Auto/Man selector switch.<br />

• Automatic control through an<br />

external enable contact.<br />

• Supply voltage: 3 x 400 V ±10 %.<br />

Frequency: 50/60 Hz.<br />

24 V AC low voltage auxiliary circuit.<br />

Power: 0.37 to 37 kW.<br />

Direct start.<br />

Protection class: IP 54.<br />

• Ambient temperature: -5 to +40 °C<br />

(limit specified by EN Standard<br />

60439-1).<br />

• Maximum relative humidity: 50% at<br />

+40°C, provided that no<br />

condensation occurs (limit specified<br />

by EN standard 60439-1).<br />

Wall mounted.<br />

Metal enclosure.<br />

• Power, pump running, thermal<br />

overload and dry running indicator<br />

lights.<br />

• Manual-reset thermal relay for<br />

overload protection, sensitive to<br />

phase failure.<br />

• Ready for installation of dry running<br />

float or pressure switch (to<br />

be ordered separately).<br />

Can be equipped with electronic<br />

protection module with electrodes.<br />

OPTIONAL<br />

ACCESSORIES<br />

• SLD series 24V level kit.<br />

Probe module for protection against<br />

dry running (set of three electrodes<br />

included in the supply).<br />

Float.<br />

Pressure switch.<br />

• VR3 three-phase module for<br />

overvoltage protection (lightning<br />

protector).<br />

PANEL RATED APPLICATION DIMENSIONS WEIGHT<br />

TYPE POWER RANGE A x B x C WITH<br />

PACKING<br />

kW HP A mm kg<br />

Q3D/03 0,37 0,5 0,9-1,5<br />

Q3D/05 0,5 0,75 1,4-2,3<br />

Q3D/11 1,1 1,5 2,0-3,3<br />

Q3D/15 1,5 2,0 3,0-5,0<br />

Q3D/22 2,2 3,0 4,5-7,5 300 x 400 x 200 15<br />

Q3D/30 3 4,0 6,0-10,0<br />

Q3D/40 4 5,5 9,0-12,0<br />

Q3D/55 5,5 7,5 9,0-15,0<br />

Q3D/92 9,2 12,5 14,0-23,0<br />

Q3D/110 11 15 20,0-32,0<br />

Q3D/150 15 20 28,0-38,0<br />

400 x 500 x 200 20<br />

Q3D/220 22 30 35,0-50,0<br />

Q3D/300 30 40 45,0-63,0 400 x 600 x 200 27<br />

Q3D/370 37 50 60,0-80,0<br />

Line protection to be provided by the user.<br />

For proper selection, make sure that the ampere input of the electric motor matches the values specified in the table.<br />