Z855 – Z875 Z895 – Z8125 SERIES
Z855 – Z875 Z895 – Z8125 SERIES
Z855 – Z875 Z895 – Z8125 SERIES
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
TECHNICAL APPENDIX<br />
SIZING OF ETHYLENE-PROPYLENE RUBBER (EPR) CABLES<br />
STAR-DELTA START<br />
Temperature 10°C 15°C 20°C 25°C 30°C 35°C 40°C 45°C 50°C 55°C 60°C<br />
Section (mm 2 )<br />
Max current - (A)<br />
1,5 47 45 43 42 41 39 37 35 33 31 36<br />
2,5 63 61 58 57 55 52 50 47 45 41 35<br />
4 85 82 78 76 74 71 67 64 60 56 48<br />
6 110 107 101 99 96 92 87 83 78 72 62<br />
10 155 151 143 140 135 129 122 117 110 102 87<br />
16 207 201 190 187 180 172 163 156 147 136 117<br />
25 274 267 253 248 239 229 217 207 195 181 155<br />
35 340 331 313 307 296 284 269 257 242 224 192<br />
50 423 412 390 382 368 353 334 320 301 279 239<br />
70 523 509 482 473 455 436 414 395 373 345 295<br />
95 599 583 522 541 521 500 474 453 427 395 338<br />
120 700 682 645 633 609 584 554 529 499 462 395<br />
400 V - 3 % voltage drop - 30 °C ambient temperature - cos ϕ = 0,85 dim-cavi_sd-epr_b_te<br />
70