2 Exterior walls in one story building with framing<br />
constructed of non-combustible materials<br />
surface of which is applied with wood-fibercement<br />
sheet of thickness 1.5 cm. or more, or<br />
fire-protecting timber of thickness 0.9 cm. or<br />
more to receive the finishing of sheet metal shall<br />
be treated as fire-resisting construction.<br />
(Fire-door and Other Fire Protective Facilities)<br />
Article 109. By fire-door and other fire protective<br />
facilities mentioned in the provisions of Article<br />
64 of the Law shall mean any one of the items<br />
as described below :<br />
(1) Fire door A;<br />
(2) Fire door B;<br />
(3) Drencher installed in opening which has<br />
passed the inspection to be conducted by the<br />
National Fire Defence Agency.<br />
2 Fireproof- or fire-resisting exterior wall, wing wall<br />
and other similar construction that built cutting<br />
across an opening in a building or buildings and<br />
all parts of boundary line, center line of road<br />
and center line of exterior wall of each building<br />
constituting more than 2 houses within the same lot<br />
(building with total floor area less than 500 sq. m.<br />
considered as one house) located or separated at<br />
the distance 3 m. or less from the opening concerned<br />
in case of one story and 5 m., or less in<br />
2nd floor or above to the above mentioned center<br />
lines, shall be considered as the fire-facilities<br />
mentioned in the preceding paragraph.<br />
3 In ventilation opening of area 100 sq. cm. or<br />
less, the fire-resisting protection made of iron<br />
plate, mortar slab and other similar materials<br />
(including vent located in part 1 m. less from<br />
ground level protected by metal wire net of<br />
2 mm. mesh.) shall be considered as the firefacilities<br />
mentioned in paragraph 1.<br />
(Construction of Fire-door)<br />
Article 110. Fire door A mentioned in the preceding<br />
Article paragraph 1 item (1) shall mean one<br />
of the constructions describad in one.of the<br />
following items :<br />
(1) Frame shall be steel with steel plate of<br />
thickness 0.5 mm. or more applied on all faces;<br />
(2) Made of steel, with steel plate of thickness<br />
1.5 mm.or more;<br />
(3) Made of steel frame concrete or of reinforced<br />
concrete of thickness 3.5 cm. or more;<br />
(4) Door of dozo-construction *of thickness 15<br />
cm. or more;<br />
(5) That specified as having equal or superior<br />
fire-resisting quality by the Minister of Construction<br />
upon hearing the opinion of the<br />
Director of National Fire Defence Agency in<br />
addition to those given in the foregoing items.<br />
2 Fire-door B mentioned in the preceding Article<br />
paragraph 1 item (2) shall satisfy one of the<br />
following requirements in its construction :<br />
(1) Made of steel plate of thickness less than<br />
-27-<br />
1.5 mm.;<br />
(2) Made of steel frame concrete or reinforced<br />
concrete of thickness less than 3.5cm. ;<br />
(3) Door of dozo-construction of thickness less<br />
than 15 cm.;<br />
(4) Steel construction with wired glass inserted;<br />
(5) Fire-protecting timber frame with galvanized<br />
sheet iron applied on all faces;<br />
(6) Fire-protecting timber frame with interior<br />
faces applied with fire-protecting timber board<br />
of thickness 0.9 cm. or more, and its exterior<br />
face protected by application of galvanized<br />
iron sheet ;<br />
(7) That recognized as having equal or superior<br />
fire-resisting quality by the Minister of Construction<br />
upon hearing the opinion of the<br />
Director of National Fire Defence Agency and,<br />
in addition to those given in the foregoing<br />
items.<br />
3 Door for opening of 500sq.cm. or less in area<br />
made of fire-protecting timber frame insertion of<br />
wired-glass shall be considered as fire-door B in<br />
the preceding paragraph.<br />
4 The part of fire door coming in contact with<br />
frame or other fire door shall be of tongue and<br />
groove fit, or of, "jogibuchi" or door stop, so it<br />
shall be intact in place in case of fire, and shall<br />
be so installed that the hardware building fire<br />
door will not show where closed.<br />
5 Fire door mentioned in paragraph 1 item (1) or<br />
item (2), or paragraph 2 item (1) or item (4)<br />
shall be installed in opening where surrounding<br />
of opening (in case fixture is to be installed<br />
within 15cm. inside of fire door, that fixture<br />
shall be included) is constructed of non-combustible<br />
materials or fire-protecting timber.<br />
(Principal Important Materials for Fire Prevention)<br />
Article 111. Cement,metal lath, wire lath, wood-firecement<br />
sheet, fire-protecting timber, fire-protecting<br />
point, or other principal fire-resisting materials<br />
similar to them to be used in structural parts in<br />
addition to the principal parts of construction on<br />
the structural parts of fire-proof construction and<br />
fire-resisting construction or fire doors.<br />
(Fire-preventing Section)<br />
Article 112. Building that its principal part of<br />
construction is constructed of fireproof or noncombustible<br />
materials, and its floor area exceeding<br />
1500 sq. m. there shall be provided with fire<br />
fighting section at convenient part so that total<br />
floor area of part included in that section shall<br />
not exceed 1500 sq. m., and constituting either<br />
floor or wall of fireproof construction, or with<br />
fire door A. However, in the case of a part of<br />
building provided with sprinkler or in the indispensable<br />
case due to its use, such as seating<br />
room, theater, cinema, show house, place of review,<br />
auditorium or assembly hall, indoor sport