oom, factory or others of the similar cases shall<br />

be expected.<br />

2 In case apart of building coming under one of the<br />

items of Article 24 paragraph 1 of the Law that<br />

part and other parts shall be separated by wall<br />

made of fireproof construction or by wall with<br />

both faces made as fire-resisting construction, or<br />

provided with fire door A or fire door B (excluding<br />

the type mentioned in Article 110 paragraph<br />

2 item (3) and item (6). ><br />

3 In case a part of building coming under one of<br />

the items of Article 27 of the Law that part and<br />

other parts shall be separated by floor or wall<br />

made of fireproof construction and fire door A.<br />

(Fire Wall in Wooden Buildings, etc.)<br />

Article 113. Fire wall shall be constructed as required<br />

by the following items :<br />

(1) Self supporting structure of fireproof construction<br />

;<br />

(2) In wooden building, neither concrete construction<br />

nor masonry construction shall be<br />

allowed ;<br />

(3) Both ends and top of fire wall shall project<br />

out from exterior walls and roof not less than<br />

50cm. (in case exterior wall of a building<br />

located on both sides of fire wall and underneath<br />

of eave or ground for roof for distance<br />

of 1.8 m. or less are of fire-resisting construction,<br />

and at the same time there is no opening<br />

in the parts mentioned herein, that projecting<br />

part may be 10cm.). However, in case fireproof<br />

exterior wall or roof is of fire-resisting<br />

construction located at section of width 3.6 m.<br />

or more including fire wall, and at the same<br />

time there is no opening or the opening in that<br />

part is provided with fire door or sash window<br />

made of fire protecting timber with insertion<br />

of wired-glass is installed, that part shall be<br />

excepted ;<br />

(4) Opening in fire wall shall be less than 2.5<br />

m.sq. and it shall be provided with fire door A;<br />

(5) Space between fire wall and passing water<br />

pipe, electric wire conduct and other pipes shall<br />

be filled with mortar,<br />

(Principal Partition Wall, etc. for Building)<br />

Article 114. Partition wall between each unit of<br />

multifamily tenant housing or apartment house<br />

shall be built as fireproof or fire-resisting construction,<br />

and it shall be carried up to roof truss<br />

or ceiling space.<br />

2 Principal partitionwall in the part of a building<br />

used as school, hospital, medical office, (excluding<br />

those having no facilities for accommodation<br />

of patients), hotel, Japanese hotel, lodging house,<br />

dormitory or market as concerned in the matter,<br />

shall be built as fireproof or fire resisting con-<br />

-28-<br />

struction, and shall be carried up to roof truss or<br />

ceiling space.<br />

B When roof trusses of a building exceeding 300<br />

sq.m. in its building area are constructed of<br />

wood, a partition wall with its both sides built<br />

of fire-resisting construction shall be provided in<br />

roof truss space at points not exceeding 12 m.<br />

measured along the side wall girder.<br />

4 Passageway connecting two buildings of total<br />

floor area exceeding 200 sq. m., and of length 4m.<br />

or more with wooden trusses shall be provided<br />

with partition in roof truss space built of fireproof<br />

construction or fire-resisting construction<br />

on both faces.<br />

(Chimney built within Building)<br />

Article 115. Chimney built within building shall<br />

satisfy the structural requirements as described<br />

in the following items :<br />

(1) Vertical distance of projection of chimney<br />

built within a building to the face of roof shall<br />

not be less than 60cm.; however, in case of<br />

brick, stone or concrete block construction built<br />

without reinforcing steel members, the part<br />

projected up shall be not less than 90 cm;<br />

(2) In case there is a building at horizontal<br />

distance less than 1 meter from the top of a<br />

chimney, the chimney shall be carried up 60cm.<br />

or more above the eave of a building concerned;<br />

(3) Part of chimney built of metal or asbestos,<br />

going through roof truss space, ceiling space,<br />

floor space, etc., shall be covered with incombustible<br />

materials other than metal ;<br />

(4) Metal or asbestos chimney shall be built at<br />

least 15 cm. away from wooden or other combustible<br />

material, excepting that part covered<br />

with incombustible materials other than metals<br />

of thickness 10 cm. or more;<br />

(5) Part of chimney of fireplace built in with<br />

wall in a building that is in interior of house<br />

shall be constructed of reinforced concrete of<br />

thickness 15cm. or more, or plain concrete<br />

brick, stone or concrete block construction of<br />

thickness 25cm. or more, and in brick, stone<br />

or concrete block chimney shall be lined with<br />

earthenware pipes or with finish of cement<br />

mortar ;<br />

(6) In the case of fireplace built in with wall<br />

where bend is less than 120°, there shall be an<br />

opening at the bend ifor cleaning.<br />

(Quantity of Dangerous Materials)<br />

Article 116. Quantity of dangerous materials mentioned<br />

in Article 27 item (6) of the Law is as<br />

listed below :