and at the same time more than 30cm. per<br />

100 sq. m. of floor area of that floor;<br />

(2) Total of widths of exits leading to or from<br />

escape stairs and special escape stairs in each<br />

floor shall be more than the values obtained by<br />

calculating by the following proportions per 100<br />

sq.m. of that floor in each floor: more than<br />

27 cm. in floors above ground level, more than<br />

36 cm. in ground floor.<br />

2 Regarding calculation of the required widths<br />

mentioned in the provisions of the preceding<br />

items, escape stairs and special escape stairways<br />

chiefly leading to escape-floor from one floor or<br />

two floors above ground level may be considered<br />

as those having the width of 1.5 times.<br />

3 In applying the provisions of tha preceding two<br />

paragraphs, open space in roof shall be considered<br />

same as other floors.<br />

(Exits to Outside of Building)<br />

Article 125. In escape-floor the walking distance<br />

leading from stairways to one of the exits to<br />

outside of a building shall be less than the value<br />

given in the provisions of Article 120.<br />

2 Doors in exits leading to outside of a building<br />

for use of audiences in theater, cinema, showhouse,<br />

place of viewing, or auditorium, or meeting<br />

place shall not be installed to open in.<br />

3 Total of widths of exits in escape-floor of department<br />

store leading to outside shall be more than<br />

the values obtained by calculation under the<br />

following proportion; 6 cm. per 100 sq. m. or<br />

total floor area of each floor, and at the same<br />

time more than 40cm. per 100 sq.m. in floor<br />

area of largest floor.<br />

4 The provisions of paragraph 3 of the preceding<br />

Article shall apply to the preceding paragraph<br />

mutatis<br />

mutandis.<br />

(Open Space in Roof)<br />

Article 126. Open space in roof shall be surrounded<br />

by parapet wall or wire fence of height 1.1 meters<br />

or more necessary for safety.<br />

2 In case the floors above 5th floor of a building<br />

are to be used as sales rooms of department<br />

store, an open space in roof available for refuge<br />

shall be provided.<br />

Section 2 Passages within Building Site<br />

Necessary for Escape and Defence<br />

against Fire<br />

(Scope of Application)<br />

Article 127. The provisions of this section shall<br />

aor-ly to the buildings mentioned in Article 35 of<br />

the Law.<br />

(Passageways within Building Site)<br />

Article 128. Building site shall be provided with<br />

passageways 1.5m. or more in width leading from<br />

outside escape stairways mentioned in Article 123<br />

paragraph 2, and with exits mentioned in Article<br />

-33-<br />

125 paragraph 1 to road, park, open space and<br />

other large vacant spaces.<br />

(Passageway in Site for large Scale Wooden<br />

Building) *-<br />

Article 129. If-a building with whole of its principal<br />

structural parts is constructed of wood and<br />

exceeding 1,000sq.m. in total floor* area or a<br />

part of principal structural part is wood construction<br />

when its total floor area (excluding<br />

floor area of the part, for which principal structural<br />

parts are fireproof and separated from other<br />

parts by means of fireproof walls and fire doors<br />

A if any; hereinafter the same in this Article)<br />

exceed 1,000 sq. m., it shall be surrounded by<br />

passage 3 m. wide or more (except the part<br />

bounded by a road). However, in- case the total<br />

floor area is less than 3,000 sq. m., the width of<br />

passageway along the boundary line of adjacent<br />

lot may be 1.5m. or more.<br />

2 In case there is a building composed of more<br />

than 2 houses or more in the same building site<br />

(excluding a building with its principal structural<br />

parts are either built or are of fireproof construction<br />

or with incombustible materials, and those<br />

with floor area exceeding 1,000 sq.m.), if its<br />

sum of total floor area exceeds 1,000 sq. m., the<br />

part constituting the total of total floor area over<br />

in 1,000 sq.m. shall be divided into section of<br />

building with total floor area kept within 1,000<br />

sq. m. and shall be surrounded by passageways 3<br />

m.or more in width (excluding parts bounded by<br />

road or boundary lines of adjacent lots.)<br />

B The exterior wall (if there are eaves, including<br />

underneath thereof) of fireproof construction and<br />

having fire floor at an opening liable to fire<br />

spread, if it is cut away effectively against fire<br />

door by means of buildings with total floor area<br />

kept within 1,000 sq. m. the provision of the<br />

preceding paragraph shall not apply to these<br />

buildings. However, in case the total of total<br />

floor of the building exceeds 3,000sq. m., the part<br />

constituting the total of that total floor area not<br />

exceeding 3,000 sq. m. shall be surrounded by<br />

passage (excluding the parts bounded by roads or<br />

boundary lines of adjacent lots) 3m. or more in<br />

width.<br />

4 Irrespective of the provisions of the preceding<br />

items, passageway may go through the corridor<br />

coming under the provisions of the following<br />

items. However, the passageway out through<br />

the corridor shall be more than 2.5m. in width<br />

and height :<br />

(1) Width not over 3 meters;<br />

(2) Not to be used except for passage or light<br />

transport.<br />

5 Passageways mentioned in each preceding paragraph<br />

shall lead and reach to the roads on which<br />

abuts the building site,