Page 10 of 34<br />

8. DVD Writer.<br />

9. 320 GB D<strong>at</strong>a-Hard –Disc.<br />

10. Ink-jet Printer.<br />

11. Multi-media Key-Board.<br />

12. Three- button optical mouse.<br />

13. Multi-media speaker.<br />

14. Oper<strong>at</strong>ing system- Windows XP processor with licenses.<br />

15. MS Office-2010 Antivirus with license.<br />

Incase of non-availability of specific brand of the above the firm shall take permission<br />

from the competent authority for the brand being purchased.<br />

DETAIL DESIGN DATA FOR E.T.P.<br />

1. Capacity :<br />

The capacity of Effluent Tre<strong>at</strong>ment Plant is 12.50 KLH (Average flow). The peak<br />

factor for the design purpose is to be taken as 1.5.<br />

2. Effluent characteristics (given by tendrer in previous offers)<br />

N<strong>at</strong>ure of Waste<br />

: Industrial effluent<br />

C.O.D. (Max.) : 1200<br />

B.O.D. (Max.)<br />

: 800 mg/l<br />

S.S.<br />

: 4000 mg/l<br />

T.D.S.<br />

: 6800 mg/l<br />

Oil & Grease<br />

: 5000 mg/l<br />

Av. <strong>Design</strong> flow r<strong>at</strong>e : 12.50 KLH<br />

Peak flow factor : 1.5<br />

Feed<br />

: Pumped to inlet-port of Oil-W<strong>at</strong>er Separ<strong>at</strong>or.<br />

3. Tre<strong>at</strong>ed W<strong>at</strong>er Standard :<br />

FINAL EFFULENT QUALITY SHOULD BE CONFORMING TO THE LATEST(AS<br />

ON DATE OF NOTIFICATION OF TENDER) NORMS OF UPPCB/CPCB.<br />

B.O.D. (Max.)<br />

: 30 mg/l<br />

C.O.D. (Max.)<br />

: 250 mg/l<br />

S.S.<br />

: 100 mg/l<br />

T.D.S.<br />

: 2100 mg/l<br />

Oil & Grease<br />

: 10 mg/l<br />

MECHANICAL & ELECTRICAL WORKS<br />

1. Fully Autom<strong>at</strong>ic Oil-W<strong>at</strong>er Separ<strong>at</strong>or<br />

No. of Unit : 1<br />

Type<br />

: Fully autom<strong>at</strong>ic in Cylindrical shape<br />

MOC of Shell<br />

: MS as per IS 2062, Sand blasted and epoxy painted<br />

Oil-W<strong>at</strong>er Interface Sensor : To be Provided.<br />

Electro-Pneum<strong>at</strong>ic Valve : to be Provided.<br />

Capacity<br />

: 12.50 KLH<br />

2. DAF Unit<br />

No. of Required<br />

: 01 Set<br />

Type<br />

: Rectangular with hopper bottom.<br />

MOC<br />

: Mild steel epoxy painted.<br />

Skid<br />

: Provided.<br />

S<strong>at</strong>ur<strong>at</strong>ion Tank<br />

: Provide.<br />

Pressure Gauge<br />

: Provided.<br />

Pressure relief valve : provided.