Control loops 6<br />

6 Control loops<br />

An overview of the control loops in the installation can be found under the 'Control<br />

Loops' link in the navigation window. It always shows the actual (measured) value, the<br />

corresponding setpoint and the difference between them. To obtain the overview, the<br />

installation should have a structure for the house addresses that permits an optimum<br />

representation of the system using <strong>novaWeb</strong>. The requirements for such a structure for<br />

the house addresses are described in the programming manual for <strong>novaWeb</strong> <strong>EYW300</strong><br />

(document 7001050).<br />

Control Loops Actual Setpoint Diff<br />

Supply Air Temp 32.6 °C 34 °C -1.4 °C<br />

Cooling Water Temp 16.1 °C 16 °C 0.1 °C<br />

To facilitate the handling of your Control Loops the deviation (or difference) is shown<br />

with a green background for very small deviations, olive for small deviations and yellow<br />

for large deviations. Like this the user can see very fast if he needs to act on any of<br />

them.<br />

The distinction between very small, small and large deviation is made regardless of the<br />

type of control loop or the setpoint's unit (e.g. °C, Pa, rh).:<br />

Setpoint > 10 units<br />

Setpoint • 10 units<br />

Very small<br />

deviation<br />

Deviation < 5% of setpoint deviation < 0.5<br />

Border<br />

between very<br />

small and<br />

small<br />

5 % of setpoint 0.5<br />

Small<br />

deviation<br />

deviation < 10 % of<br />

setpoint<br />

deviation < 1<br />

Border<br />

between<br />

small and<br />

large<br />

10 % of setpoint 1<br />

Large<br />

deviation<br />

deviation > 10% of<br />

setpoint<br />

deviation > 1<br />