EYW300 novaWeb: Operation (7001049003) - sauter-controls.com ...
EYW300 novaWeb: Operation (7001049003) - sauter-controls.com ...
EYW300 novaWeb: Operation (7001049003) - sauter-controls.com ...
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>EYW300</strong> <strong>novaWeb</strong> <strong>Operation</strong><br />
Control loops 6<br />
6 Control loops<br />
An overview of the control loops in the installation can be found under the 'Control<br />
Loops' link in the navigation window. It always shows the actual (measured) value, the<br />
corresponding setpoint and the difference between them. To obtain the overview, the<br />
installation should have a structure for the house addresses that permits an optimum<br />
representation of the system using <strong>novaWeb</strong>. The requirements for such a structure for<br />
the house addresses are described in the programming manual for <strong>novaWeb</strong> <strong>EYW300</strong><br />
(document 7001050).<br />
Control Loops Actual Setpoint Diff<br />
Supply Air Temp 32.6 °C 34 °C -1.4 °C<br />
Cooling Water Temp 16.1 °C 16 °C 0.1 °C<br />
To facilitate the handling of your Control Loops the deviation (or difference) is shown<br />
with a green background for very small deviations, olive for small deviations and yellow<br />
for large deviations. Like this the user can see very fast if he needs to act on any of<br />
them.<br />
The distinction between very small, small and large deviation is made regardless of the<br />
type of control loop or the setpoint's unit (e.g. °C, Pa, rh).:<br />
Setpoint > 10 units<br />
Setpoint • 10 units<br />
Very small<br />
deviation<br />
Deviation < 5% of setpoint deviation < 0.5<br />
Border<br />
between very<br />
small and<br />
small<br />
5 % of setpoint 0.5<br />
Small<br />
deviation<br />
deviation < 10 % of<br />
setpoint<br />
deviation < 1<br />
Border<br />
between<br />
small and<br />
large<br />
10 % of setpoint 1<br />
Large<br />
deviation<br />
deviation > 10% of<br />
setpoint<br />
deviation > 1<br />
<strong>7001049003</strong> A Sauter Systems 17