<strong>EYW300</strong> <strong>novaWeb</strong> <strong>Operation</strong><br />

E-mail messages 12<br />

12.1.3 Content<br />

The content of the e-mail notification explains the error in a full text message such as:<br />

“novaNet Bus failure”.<br />

12.1.4 Adapting alarm messages<br />

The subject line in the e-mail for alarms can be adapted. <strong>novaWeb</strong> checks whether a file<br />

named 'sub_al.txt', 'sub_ok.txt' or 'sub_ev.txt' is stored in <strong>novaWeb</strong> folder usr/local/etc.<br />

If a file with this name is present in this location, the text that it contains is placed at the<br />

start of the subject line.<br />

If an alarm occurs, the text in file 'sub_al.txt' is used; for an 'outgoing' alarm, the text in<br />

file 'sub_ok.txt' is used. For other events when an e-mail is sent, the text in file<br />

'sub_ev.txt' is used.<br />

These files can be downloaded to the <strong>novaWeb</strong> via FTP.<br />

For example, if file 'sub_al.txt' contains the text 'Incident in plant: ', the subject line of the<br />

error message shown as an example above would now look like this.<br />

Subject: Incident in plant: Alarm, VS/Office/sys.<strong>sauter</strong>.busfail.<br />

<strong>7001049003</strong> A Sauter Systems 43