C. Elevators <strong>and</strong> dumbwaiters: Details <strong>and</strong> dimensions of shaft, pit,<br />

<strong>and</strong> machine room; sizes of car plat<strong>for</strong>m <strong>and</strong> doors;<br />

D. Kitchens, laundry, refrigeration, <strong>and</strong> laboratories: These shall be<br />

detailed at a satisfactory scale to show the location, size, <strong>and</strong><br />

connection of all fixed equipment.<br />

5. Step (5) – Electrical Drawings:<br />

A. Drawings shall show electrical wiring, outlets, smoke detectors,<br />

<strong>and</strong> equipment that require electrical connections;<br />

B. Electrical service entrances with switches <strong>and</strong> feeder to the public<br />

service feeders shall be shown;<br />

C. Plan <strong>and</strong> diagram showing main switchboard, power panels, light<br />

panels, <strong>and</strong> equipment;<br />

D. Light outlets, receptacles, switches, power outlets, <strong>and</strong> circuits;<br />

E. Nurses’ call systems, either wireless systems or hardwired, with<br />

outlets <strong>for</strong> beds, duty stations, door signal lights, enunciators, <strong>and</strong><br />

wiring diagrams. If a wireless system is employed, the electrical<br />

drawing will indicate the implementation of the system including<br />

designations <strong>for</strong> residents call systems in residents’ apartments or<br />

units;<br />

F. Fire alarm system with stations, signal devices, control board, <strong>and</strong><br />

wiring diagrams;<br />

G. Emergency electrical system with outlets, transfer switch, source<br />

of supply, feeders, <strong>and</strong> circuits.<br />

6. Step (6) – Specifications: Specifications shall supplement the drawings to<br />

fully describe types, sizes, capacities, workmanship, finishes, <strong>and</strong> other<br />

characteristics of all materials <strong>and</strong> equipment, <strong>and</strong> shall include the<br />

following:<br />

A. Cover or title sheet;<br />

B. Index;<br />

C. General conditions;<br />

D. General requirements;<br />