Special functions<br />

6.7. - Collector field cooling<br />

This function controls an external coolig unit to cool down the collector.<br />

Settings range: On, Off<br />

6.7.1. - Tmax field<br />

If this temperature is exceeded at the reference sensor, the relay is switched on.<br />

Settings range: 100 °C to 180 °C / Default: 120 °C<br />

6.7.2. - Hys min<br />

When the temperature falls below Tmax fi eld +Hys min, the relay is switched off.<br />

Settings range: -20 to -2°C / Default: -5<br />

6.7.3. - Hys max<br />

To protect the cooling unit itself from damage, the relay is switched off as soon as the temperature at the reference<br />

sensor reaches Tmax fi eld + Hys max<br />

Settings range: 2 to 60 °C / Default: -20<br />

6.7.4. - Field cooling sensor<br />

Reference sensor of the collector fi eld cooling function.<br />

Settings range: S1-S8, VFS1-2, active storage, RC / Default: none<br />

Caution<br />

This function does not activate the solar pump to cool the collector. Therefore, please refer to the<br />

collector protection.<br />