Special functions<br />
6.11. - Solid fuel boiler<br />
The relay is used to control an additional solid fuel boiler.<br />
Settings range: On, Off<br />
6.11.1. - SF Tmax<br />
Maximum temperature in the storage. If this is exceeded, the relay is switched off.<br />
Settings range: Off to 100°C / Default setting: 70° C<br />
6.11.2. - SF Tmin<br />
Minimum temperature in the solid fuel boiler to switch on the pump. If the temperature at the boiler sensor is below this<br />
temperature, the relay is disabled.<br />
Settings range: 0 ° C to 100° C / Default setting: 70° C<br />
6.11.3. - ∆ T SF<br />
Switch on and Switch off condition for the temperature difference between boiler and storage.<br />
Switch on difference ∆ T SF<br />
Settings range: 5 to 20 K / Default setting: 8<br />
Switch off temperature difference ∆ T SF<br />
Settings range: 0 K to Switch ∆ T SF / Default setting: 7<br />
6.11.4. - Boiler sensor<br />
This determines the sensor, that is used as boiler sensor.<br />
Settings range: S1-S8, VFS1-2, Active storage/ Default setting: none<br />
Relay functions<br />
6.11.5. - Storage sensor<br />
This determines the sensor, that is used as storage sensor.<br />
Settings range: S1-S8, VFS1-2, Active storage/ Default setting: none<br />
6.12. - Error message<br />
The relay is switched on, when one or more protective funtion is active or a message is shown.<br />
This function can be inverted, so that the relay is alway on and switches off when a protective function or a message is<br />
shown.<br />
Settings range: On, Inverted, Off / Default setting: Off<br />
Collector alarm<br />
Collector protection<br />
System protection<br />
Frost protection<br />
Recooling<br />
Antilegionella protection<br />
Message<br />