Special functions<br />

6.16. - Always on<br />

Relay is always switched on.<br />

6.17. - Heating circuit<br />

Heat circuit pump is controlled with a fi xed hysteresis of (+/-1° for setpoint temperature).<br />

30 seconds Switch on and Switch off delay is fi xed setting to prevent unnecessary switching of the pump.<br />

RC21 room <strong>controller</strong> can be used as room temperature sensor.<br />

Settings range: On, Off<br />

6.17.1. - Room set day<br />

Room reference temperature in day mode. If this temperature is exceeded at the room temperature sensor at the set<br />

times, the relay is switched off.<br />

Settings range: 10 to 30° C<br />

Relay functions<br />

6.17.2. - Room set night<br />

Room reference temperature in night mode. If this temperature is exceeded at the room temperature sensor at the set<br />

times, the relay is switched off.<br />

Settings range: 10 to 30° C<br />

6.17.3. - Room sensor<br />

This menu determines the sensor for the room temperature.<br />

Settings range: S2 to S7, RC<br />

6.17.4. - Periods<br />

Set the desired periods of time when the heat circuit day mode should be active. 3 periods can be set per day, settings<br />

can also be copied to other days. Outside the set times the heating function is working in night mode.<br />

Setting range: from 00:00 to 23:59 /default setting: 06:00 to 22:00<br />