ML193DF Gas Furnace Installation Manual - Lennox
ML193DF Gas Furnace Installation Manual - Lennox
ML193DF Gas Furnace Installation Manual - Lennox
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
UNCONDITIONED<br />
SPACE<br />
6" (152mm)<br />
Max<br />
*WALL SUPPORT<br />
OUTSIDE WALL<br />
FIELD−PROVIDED<br />
REDUCER MAY BE<br />
REQUIRED TO<br />
ADAPT LARGER<br />
VENT PIPE SIZE TO<br />
TERMINATION<br />
12" (305mm) MAX. for 2" (51mm)<br />
20" (508mm) MAX. for 3" (76mm)<br />
SIZE TER-<br />
MINATION<br />
PIPE PER<br />
TABLE 8.<br />
12" (305mm)<br />
ABOVE GRADE OR<br />
AVERAGE SNOW<br />
ACCUMULATION<br />
NOTE − If necessary the condensate trap may be installed<br />
up to 5´ away from the furnace. Use PVC pipe to connect<br />
trap to furnace condensate outlet. Piping from furnace<br />
must slope down a minimum of 1/4" per ft. toward trap.<br />
CONDENSATE TRAP AND PLUG LOCATIONS<br />
1/2" (13mm) FOAM<br />
INSULATION IN<br />
UNCONDITIONED<br />
SPACE<br />
*Use wall support every 24" (610). Use<br />
two supports if extension is greater<br />
than 24" but less than 48".<br />
FIGURE 40<br />
1/2" (13mm) FOAM<br />
INSULATION<br />
NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION EX-<br />
TENDED OR (15F74) WALL TERMINATION VENT PIPE EXTENDED<br />
Trap<br />
(same on<br />
right side)<br />
1−1/2 in.<br />
Plug<br />
(same on left<br />
side)<br />
<strong>ML193DF</strong> NON−DIRECT VENT APPLICATION<br />
USING EXISTING CHIMNEY<br />
SIZE TERMINATION<br />
PIPE PER TABLE 8.<br />
STRAIGHT−CUT OR<br />
ANGLE−CUT IN DIRECTION<br />
OF ROOF SLOPE<br />
Minimum 12" (305MM)<br />
above chimney top<br />
plate or average snow<br />
accumulation<br />
INSULATE<br />
TO FORM<br />
SEAL<br />
SHEET<br />
METAL TOP<br />
PLATE<br />
3" − 8"<br />
(76mm−<br />
203mm)<br />
3" − 8"<br />
(76mm−<br />
203mm)<br />
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If vertical<br />
discharge through an existing unused chimney or stack is required, insert piping<br />
inside chimney until the pipe open end is above top of chimney and terminate as illustrated.<br />
In any exterior portion of chimney, the exhaust vent must be insulated.<br />
FIGURE 41<br />
EXHAUST VENT<br />
1/2" (13mm)<br />
WEATHERPROOF<br />
INSULATION<br />
SHOULDER OF FITTINGS<br />
PROVIDE SUPPORT<br />
OF PIPE ON TOP PLATE<br />
EXTERIOR<br />
PORTION OF<br />
CHIMNEY<br />
Condensate Piping<br />
This unit is designed for either right- or left-side exit of condensate<br />
piping. Refer to figure 42 for condensate trap locations.<br />
FIGURE 42<br />
1 − Determine which side condensate piping will exit the<br />
unit, location of trap, field−provided fittings and length of<br />
PVC pipe required to reach available drain.<br />
2 − Remove plug (figure 42) from the cold end header box<br />
at the appropriate location on the side of the unit. Install<br />
field−provided 1/2" NPT male fitting into cold end header<br />
box. Use teflon tape or appropriate pipe dope.<br />
3 − Install the cap over the clean out opening at the base of<br />
the trap. See figure 45.<br />
NOTE − Vinyl tubing may be used for condensate drain.<br />
Tubing must be 1−1/4" OD X 1" ID and should be attached to<br />
the drain on the trap using a hose clamp.<br />
4 − Install drain trap using appropriate PVC fittings, glue<br />
all joints. Glue the provided drain trap as shown in figure<br />
45. Route the condensate line to an open drain.<br />
NOTE − If necessary the condensate trap may be installed<br />
up to 5 feet away from the furnace. Piping from furnace<br />
must slope down a minimum of 1/4" per ft. toward trap.<br />
Page 27