04.10.2014 Views

ML193DF Gas Furnace Installation Manual - Lennox

ML193DF Gas Furnace Installation Manual - Lennox

ML193DF Gas Furnace Installation Manual - Lennox

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

UNCONDITIONED<br />

SPACE<br />

6" (152mm)<br />

Max<br />

*WALL SUPPORT<br />

OUTSIDE WALL<br />

FIELD−PROVIDED<br />

REDUCER MAY BE<br />

REQUIRED TO<br />

ADAPT LARGER<br />

VENT PIPE SIZE TO<br />

TERMINATION<br />

12" (305mm) MAX. for 2" (51mm)<br />

20" (508mm) MAX. for 3" (76mm)<br />

SIZE TER-<br />

MINATION<br />

PIPE PER<br />

TABLE 8.<br />

12" (305mm)<br />

ABOVE GRADE OR<br />

AVERAGE SNOW<br />

ACCUMULATION<br />

NOTE − If necessary the condensate trap may be installed<br />

up to 5´ away from the furnace. Use PVC pipe to connect<br />

trap to furnace condensate outlet. Piping from furnace<br />

must slope down a minimum of 1/4" per ft. toward trap.<br />

CONDENSATE TRAP AND PLUG LOCATIONS<br />

1/2" (13mm) FOAM<br />

INSULATION IN<br />

UNCONDITIONED<br />

SPACE<br />

*Use wall support every 24" (610). Use<br />

two supports if extension is greater<br />

than 24" but less than 48".<br />

FIGURE 40<br />

1/2" (13mm) FOAM<br />

INSULATION<br />

NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION EX-<br />

TENDED OR (15F74) WALL TERMINATION VENT PIPE EXTENDED<br />

Trap<br />

(same on<br />

right side)<br />

1−1/2 in.<br />

Plug<br />

(same on left<br />

side)<br />

<strong>ML193DF</strong> NON−DIRECT VENT APPLICATION<br />

USING EXISTING CHIMNEY<br />

SIZE TERMINATION<br />

PIPE PER TABLE 8.<br />

STRAIGHT−CUT OR<br />

ANGLE−CUT IN DIRECTION<br />

OF ROOF SLOPE<br />

Minimum 12" (305MM)<br />

above chimney top<br />

plate or average snow<br />

accumulation<br />

INSULATE<br />

TO FORM<br />

SEAL<br />

SHEET<br />

METAL TOP<br />

PLATE<br />

3" − 8"<br />

(76mm−<br />

203mm)<br />

3" − 8"<br />

(76mm−<br />

203mm)<br />

NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If vertical<br />

discharge through an existing unused chimney or stack is required, insert piping<br />

inside chimney until the pipe open end is above top of chimney and terminate as illustrated.<br />

In any exterior portion of chimney, the exhaust vent must be insulated.<br />

FIGURE 41<br />

EXHAUST VENT<br />

1/2" (13mm)<br />

WEATHERPROOF<br />

INSULATION<br />

SHOULDER OF FITTINGS<br />

PROVIDE SUPPORT<br />

OF PIPE ON TOP PLATE<br />

EXTERIOR<br />

PORTION OF<br />

CHIMNEY<br />

Condensate Piping<br />

This unit is designed for either right- or left-side exit of condensate<br />

piping. Refer to figure 42 for condensate trap locations.<br />

FIGURE 42<br />

1 − Determine which side condensate piping will exit the<br />

unit, location of trap, field−provided fittings and length of<br />

PVC pipe required to reach available drain.<br />

2 − Remove plug (figure 42) from the cold end header box<br />

at the appropriate location on the side of the unit. Install<br />

field−provided 1/2" NPT male fitting into cold end header<br />

box. Use teflon tape or appropriate pipe dope.<br />

3 − Install the cap over the clean out opening at the base of<br />

the trap. See figure 45.<br />

NOTE − Vinyl tubing may be used for condensate drain.<br />

Tubing must be 1−1/4" OD X 1" ID and should be attached to<br />

the drain on the trap using a hose clamp.<br />

4 − Install drain trap using appropriate PVC fittings, glue<br />

all joints. Glue the provided drain trap as shown in figure<br />

45. Route the condensate line to an open drain.<br />

NOTE − If necessary the condensate trap may be installed<br />

up to 5 feet away from the furnace. Piping from furnace<br />

must slope down a minimum of 1/4" per ft. toward trap.<br />

Page 27

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!