06.10.2014 Views

Sony - TSL

Sony - TSL

Sony - TSL

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

WinSoft<br />

The <strong>TSL</strong> UMD Configuring<br />

Program<br />

HANDBOOK<br />

Television Systems Limited.<br />

Unit 4, Kings Grove, Maidenhead, Berkshire, SL6 4DP<br />

Telephone +44 (0)1628 687200, FAX +44 (0)1628 687299<br />

WinSoft V 4.2.4.0 0 Issue 5.3


WinSoft V 4.2.4.0 1 Issue 5.3


Section B<br />

WINSOFT<br />

CONTENTS<br />

Part A<br />

1.0 Introduction<br />

1.1 Installation<br />

1.2 Important Overview Information<br />

1.3 Recommendations and Tips<br />

1.4 Making Changes<br />

1.5 Working Off-line<br />

2.0 Introduction to Creating And Setting Up The Displays<br />

2.1 Setting the Mnemonics – The Edit Menu<br />

2.1.1 Fixed Display Mnemonics<br />

2.1.2 Router Source and Bus Mnemonics<br />

2.2 Setting the Displays to be Fixed, Fixed (Router) Source, Router Source, or Router Bus<br />

Displays.<br />

2.2.1 Router Bus Priority<br />

2.3 Names<br />

2.4 Edit Display Assignment<br />

2.5 Tallies<br />

2.5.1 Direct Tallies<br />

2.5.1.1 Edit > Tallies > Edit Display Tally Enable. (Also Section 2.5.6).<br />

2.5.2 Tally Outputs<br />

2.5.3 Edit Router Source Tallies<br />

2.5.3.1 Multiple Tally In to Router Sources<br />

2.5.4 Edit Router Bus Tallies<br />

2.5.5 Edit Tally Input Attributes – Red (Left) and Green (Right) Tallies and Ext<br />

Enable. Iso Tallies.<br />

2.5.6 Edit > Tallies > Display Tally Enable<br />

2.5.7 Edit Router Source Assignment<br />

3.0 Other Menus<br />

3.1 File Menu<br />

3.2 Setup Menu<br />

3.2.1 Options<br />

3.2.2 Register IRD<br />

WinSoft V 4.2.4.0 2 Issue 5.3


3.2.3 Network Mode<br />

3.3 Control Menu<br />

3.3.1 General Parameters<br />

3.4 View Menu<br />

3.5 Comms Menu<br />

3.6 Tools Menu<br />

3.6.1 The Lists and Mnemonics<br />

3.6.2 Tally Pin Patch<br />

3.6.3 Tally Mimic.<br />

3.6.4 Router Mimic<br />

3.7 Properties Menu<br />

4.0 Associating Monitors with a Router<br />

5.0 Desktop Enhancements<br />

5.1 Making a Frame for the Monitor Stack<br />

5.2 Naming the icons<br />

6.0 General Notes for Displays<br />

7.0 Audio Monitoring Unit Setup<br />

8.0 The Help Menu<br />

8.1 About Winsoft<br />

8.2 Show Serial Comms Wind<br />

9.0 Uploading and downloading of names from routers and mixers into Winsoft<br />

9.1 Configuring the Serial Port<br />

9.2 Configure Names Options<br />

9.2.1 Router Database Options<br />

9.2.2 UMD Mnemonics Options<br />

9.2.3 Mixer Mnemonics Options<br />

9.2.4 Notes.<br />

Uploading Names into the mixer<br />

Mixer Mnemonics Only<br />

10.0 Trouble shooting<br />

WinSoft V 4.2.4.0 3 Issue 5.3


11.0 Notes on the use of the 2 x 1 Emergency C/O Router – where applicable<br />

12.0 Notes on the use of the Static S8C Displays.<br />

13.0 Timed Messages for Fixed UMDs<br />

Appendices<br />

Appendix A<br />

Multiple System Controllers - Network Mode – only supplied with appropriate orders<br />

Appendix B<br />

Multiple System Controllers - non-Network Mode – only supplied with appropriate orders<br />

Appendix C<br />

Infra-Red Controller - Network Mode – only supplied with appropriate orders<br />

Appendix D<br />

Timed Message Control – only supplied with appropriate orders<br />

Note.<br />

This manual describes the facilities available with EPROM software versions: v 750<br />

» This symbol denotes a hint or tip<br />

» A few minutes reading the opening advisory comments of this section could<br />

save hours of re-assigning displays<br />

WinSoft V 4.2.4.0 4 Issue 5.3


This Page is Blank<br />

WinSoft V 4.2.4.0 5 Issue 5.3


A Monitor Stack<br />

WinSoft V 4.2.4.0 6 Issue 5.3


This Page is Blank<br />

WinSoft V 4.2.4.0 7 Issue 5.3


Winsoft / System Controller Features<br />

This is a list of the facilities available from within Winsoft.<br />

• Configured by a standard PC running Windows 95, 98, NT4, 2000 and XP,<br />

• Stand-alone Controller.<br />

• GUI on the computer monitor – representation of the actual monitor stack or wall.<br />

• Ability to save and open different configurations (Tally, Mnemonics and router mapping details).<br />

• Mnemonic control of the dynamic UMDs<br />

• Drag and drop from mnemonic lists.<br />

• Tally control of the dynamic and static UMDs<br />

• Red/Green split tally assignments<br />

• Ability to inhibit left or right tally on any UMD<br />

• Control of UMD mnemonic and tally LED colour.<br />

• Multiviewer support.<br />

• Ability to map tallied router sources to a tally o/p pin<br />

• Ability to map tallied router buses to a tally o/p pin<br />

• Full mnemonics lists for router sources and destinations (buses).<br />

• Names lists for tallies, routers and Controllers as “aide-memoirs”.<br />

• Virtual router derived from the mixer information for PGM and PST associated UMDs<br />

• Virtual Emergency Router for UMDs on final system o/p, controlled via a tally i/p.<br />

• Ability to map cascaded routers so the o/p UMD shows the correct source mnemonic as in -<br />

• Router source to source and source to bus mapping.<br />

• External third party router control from Winsoft.<br />

• Downloading the names lists from some routers into Winsoft for display on the UMDs - where<br />

supported by the router manufacturer.<br />

• Uploading of UMD mnemonics from Winsoft into the router’s names lists – where supported by the<br />

router manufacturer.<br />

• Uploading of mnemonics from Winsoft into the mixer’s panel – where supported by the mixer<br />

manufacturer.<br />

• Multiple System Controllers on a networked system all controlled from a central Bus Controller.<br />

• Networked tallies across several System Controllers.<br />

• Networked routers across several System Controllers.<br />

• Option of opto-isolated inputs for the tally inputs.<br />

• Option of isolated relay-contacts for the tally outputs<br />

• Configuration and control of infra-red controlled devices. e.g. Satellite IRDs/STDs.<br />

• Monitoring and configuration of the <strong>TSL</strong> AMUMD range – a visual indication of bargraph activity is<br />

displayed.<br />

WinSoft V 4.2.4.0 8 Issue 5.3


1.0 Introduction<br />

This program can run on the following versions of Windows: ’95, ’98, NT4, XP and Windows 2000.<br />

For Windows 2000 users: delete the file "SNMPAPI.DLL" that is in the Winsoft directory – the program will<br />

then pick up the W2000 version in the Windows directory.<br />

The program is used to configure the System Controllers and the AMUMD range of Under Monitor Displays<br />

with audio bargraph monitoring.<br />

Router control and IRD/STB (Integrated Receiver-Decoders/Set Top Boxes) control, via the <strong>TSL</strong> LWB-1<br />

product is also possible.<br />

The computer VDU display is interactive and shows the Mnemonic and Tally conditions and the AMU<br />

bargraph level at all times.<br />

It is not necessary to have the configuring computer permanently connected to the system controller for<br />

operation.<br />

The <strong>TSL</strong> System Controllers accept Vision Mixer tally and Router cross-point information and output the<br />

appropriate tally signals and mnemonics to various types of <strong>TSL</strong> alpha-numeric UMDs (Under Monitor<br />

Displays).<br />

1.1 Installation<br />

The program is provided on CD and is designed to run on an IBM compatible PC. About 2.0Mb of hard disk<br />

space is required.<br />

Installation.<br />

Search the CD in the Winsoft Program directory and click on Setup.exe. An icon will be placed on the<br />

Desktop.<br />

If zipped files are provided, they are self extracting and should be unzipped to a new directory. Create a<br />

Winsoft directory on the hard drive to receive the files.<br />

This will be the working directory for the program. User program files will be saved by default to this<br />

directory.<br />

The Winsoft program is also<br />

available from<br />

www.televisionsystems.ltd.uk<br />

WinSoft V 4.2.4.0 9 Issue 5.3


The cable required to connect the System Controller to the computer is as follows:<br />

UMD SYSTEM CONTROLLER<br />

COMPUTER COMMS PORT<br />

MAINTENANCE PORT AT XT or PC<br />

D 9 socket D 9 socket D 25 socket<br />

2 ← 3 2<br />

3 → 2 3<br />

5 GND 5 7<br />

The cable is connected between the Maintenance Port on the System Controller and the appropriate Comms<br />

Port on the computer.<br />

Select the appropriate Comms Port on first starting the program from the Comms Menu.<br />

For Winsoft network users, please see Section B.<br />

Computer Comms Port Settings<br />

» If you need to run the same set up on a different computer to that originally used, copy the entire<br />

Winsoft directory across to the second computer so that the Names etc. are carried across.<br />

The program is deliberately directory/computer orientated. Transferring the set-up to another<br />

computer is simply a matter of copying the entire Winsoft directory across. Only registry settings then<br />

need to be re-established; however is also possible to transfer these by saving the <strong>TSL</strong> key into<br />

HKEY_USERS > software, a .reg file using regedit.exe. Run Winsoft first on the new machine.<br />

This action is only for experts.<br />

Normally, only one computer/directory should be used for the system, otherwise synchronisation<br />

issues will arise. Note that that directory can be a computer network directory if access is required<br />

from more than one workstation on a network.<br />

WinSoft V 4.2.4.0 10 Issue 5.3


Check the Winsoft Properties > System Description box to ensure that you have the correct software.<br />

The properties information will also show the appropriate functions of each rear panel connector.<br />

1.2 Important Overview Information<br />

Tallies from a vision mixer<br />

This program allows tallies from a vision mixer to be mapped to non router-associated displays, to routerassociated<br />

displays and to output pins on the System Controller.<br />

Router data and tallying router buses.<br />

Data from the router is received by the System Controller so the cross-point status is known. By assigning a<br />

UMD to the “router bus” in the System Controller and by entering the router source mnemonics in the Winsoft<br />

program, the messages on the UMD will change when the router cross-point is changed.<br />

These messages or mnemonics will, of course, match the pictures seen on the picture monitor (fed from that<br />

router bus) if the mnemonics have been correctly entered.<br />

If that router bus is tallied in the Winsoft program, done by assigning a mixer tally to the appropriate router<br />

bus, any associated UMD, whether its on that tallied bus or is a source UMD which the bus has selected, will<br />

also be tallied.<br />

Further more, any other router bus may select that live, tallied router source. Any UMD on this other bus will<br />

also be tallied. It will be seen that full cross-referencing of tallies is made in the Winsoft program.<br />

Incoming tallies to the <strong>TSL</strong> system may be observed via Tools > Tally Mimic.<br />

Router activity incoming to the <strong>TSL</strong> system may be observed via Tools > Router Mimic.<br />

Tallies to the <strong>TSL</strong> system are either pin contacts to ground (parallel input on the D37 connectors) or via serial<br />

data( via the D9 connectors). The tally mimic always shows the equivalent of decoded serial tally information.<br />

When entering the UMD display on the computer screen, using the RH mouse<br />

button, it is crucial that the correct type of display is entered as the building<br />

process progresses.<br />

If this is not done correctly it will be difficult to recover this problem in a logical manner after the monitor stack<br />

has been built. If display types subsequently need to be altered and they are early in the list, a complete<br />

rebuild will probably be necessary.<br />

WinSoft V 4.2.4.0 11 Issue 5.3


Display Terminology<br />

♦ Fixed Displays are Displays which do not change their messages (mnemonics) when router changes are<br />

made.<br />

♦ Fixed (router) Source Displays are displays which are assigned to the router inputs and show the<br />

dynamic tally states but they do not change their message (mnemonics) on router changes. They will<br />

always show the router source (input) mnemonic.<br />

♦ Router Source Displays are Displays which are assigned to a router source (input) and they will show<br />

the router bus mnemonic.<br />

♦ Router Bus Displays are Displays which are assigned to a router bus (output) and they will show the<br />

selected router source mnemonic.<br />

1.3 Recommendations and Tips<br />

It is strongly recommended that an offline design ( † -see P9) is carried out first to ensure a logical<br />

progression of displays and addresses for a new system.<br />

• The monitor stack (wall) should be “built” first and the correct UMD types added and positioned as<br />

necessary. The program will automatically assign addresses in a sequential manner and will assume<br />

that all Displays are initially Fixed Displays.<br />

• Next, type in all Names for Tally Inputs, Outputs and Router Names. On a large system this will provide<br />

invaluable help.<br />

• Next, assign the Displays as Fixed, Router Source, Fixed Router Source or Router Bus Displays etc.<br />

• Then enter the mnemonics for the Fixed Displays, Router Sources and Router Buses.<br />

• Map the Tallies to the Displays or Router Sources/Buses.<br />

• Finally, the program addresses must be copied by the Operator to the actual UMD hardware using the<br />

buttons on the UMDs. The Addresses may by seen via the View Menu.<br />

Names may be entered as required. (These are not the same as the mnemonics. Mnemonics show on the<br />

UMDs – Names do not. Names are provided as an aide-memoir).<br />

Users who are familiar with the program may find it best to set the Display types first in the Edit, Display<br />

Assignment Menu. Then, as each Display is inserted on the desktop, it will be of the correct type.<br />

Remember to save both the .mon and .umd files before going on-line as the System Controller will take<br />

control and the desktop layout will be lost temporarily.<br />

Open the .mon and .umd files again and the set-up will then be written to the System Controller.<br />

1.4 Making Changes<br />

If changes need to be made to an existing configuration, it is recommended that the programme is run off-line<br />

and the default set-up files are disabled via the Setup > Options Menu.<br />

Inspect the configuration carefully in the Edit > Display Assignment menu before saving to disc and then<br />

Writing to the System Controller.<br />

WinSoft V 4.2.4.0 12 Issue 5.3


» Remember, mnemonics stay with Display numbers, so some re-addressing of the actual hardware<br />

will probably be necessary.<br />

For example, if a Single Display is changed to a Triple, some following Displays will be subsumed<br />

into the Triple Display.<br />

For example, consider the following:<br />

A Stack consists of the following Displays; a D8C, D16C, D8C, and D8C. If the first D8C Display is<br />

changed to a Triple Display, the following D16C and D8C (Display numbers 2 and 3) will turn into the<br />

Triple Display. The Mnemonics that were for the D16C (Display number 2) are still at Display number<br />

2 but this is now the second 8 character display of the Triple Display.<br />

The actual hardware of the original second Display is still a D16C. This is now at program address<br />

002. Before the changes it was at address 001.<br />

If changes are done in the middle of a large number of mixed display types, extensive readdressing<br />

of the Monitor Stack will be necessary.<br />

It is crucial that the correct UMD type is entered in the program.<br />

Hardware Type<br />

Winsoft Type<br />

D8C/D8 – Dynamic 8<br />

D16C/D16 – Dynamic 16<br />

DD8C - Dual 8<br />

TD8 – Triple 8<br />

QD8 – Quad 8<br />

AMU1- 4BA/BD, AMUMD82A/D, AMUMD84A/D – Single 8 AMU<br />

AMUMD 2882, AMU1-8BA/BD – Dual 8 AMD<br />

AMU1-12BA/BD – Triple 8 AMU<br />

AMU1-16BA/BD – Quad 8 AMU<br />

ML1 – ML1<br />

S8C – Static S8C<br />

AMUMD16/2A/D, AMUMD 16/4A/D – Single 16 AMU<br />

Note: A or D denotes whether the unit accepts analogue or digital audio.<br />

1.5 Working Off-line<br />

† Important information for first time use when working Offline.<br />

Before working Offline, the computer must have been connected and have read the System Controller<br />

firmware once. Save an empty .mon and .umd file. This allows the computer program to match the System<br />

Controller firmware parameters. Save your work to the .umd and .mon files before closing the program.<br />

When working On-Line for the first time with a single System Controller, ensure that Node 1 is shown in the<br />

box.<br />

Select Node 1 from the<br />

drop-down box if it is not<br />

already displayed.<br />

WinSoft V 4.2.4.0 13 Issue 5.3


This is also the box which enables any one System Controller out of several System Controllers, all on a<br />

common Maintenance Bus, but not networked, to be accessed from one Computer position.<br />

See Appendix B, where appropriate.<br />

This manual is written to provide the user a “quick start” with the program.<br />

The creation of the Displays on the screen and of the Mnemonics is described first. The functions of<br />

the various Menu items are then described.<br />

It is important to remember that three distinct separate operations are required.<br />

These are:<br />

- entering and setting the Displays as fixed or router associated<br />

- entering the mnemonics<br />

- setting tallies to the Displays or to the router’s sources or buses.<br />

Be sure to save the set up to a .umd file and the layout to a .mon file before closing the program.<br />

These files are stored in the computer.<br />

WinSoft V 4.2.4.0 14 Issue 5.3


2.0 Introduction to Creating and Setting up the Displays<br />

When the program is first run the initial screen is blank. With the mouse pointer on the screen, pressing the<br />

RH button will allow a Display to be made. Be sure to save the layout to a .mon file before closing the<br />

program.<br />

The default is a D8C Display but this may be changed under the Setup > Options menu.<br />

Picture monitors, Tally Lamps or VTRs may be selected and moved in the same manner as the UMDs.<br />

Select the icon to be<br />

positioned on the<br />

Desktop from the dropdown<br />

list.<br />

Various icons can be entered<br />

via a RH mouse click:<br />

• Single Tally Out Lamps<br />

• Tally Output Relays<br />

• Clock (PC time)<br />

• VTRs<br />

Displays may be changed from the default D8 display to other types by selecting Hardware Type when the<br />

mouse pointer is over the desired UMD and then by using the RH mouse button. Select Hardware type in<br />

the drop-down box. The Edit Display Assignment dialogue box is then shown.<br />

WinSoft V 4.2.4.0 15 Issue 5.3


» To change double, triple and quad displays, the pointer must be over the extreme LH section of the<br />

Display.<br />

The selected Display is<br />

highlighted.<br />

Change the type in the dropdown<br />

box.<br />

Virtual displays can be entered onto the desktop even when all the physical displays have been used. With<br />

large UMD systems this facility may be useful as an aide-memoir for router buses where there is no actual<br />

display.<br />

The Virtual displays may be<br />

shown or hidden in this list by<br />

checking this box.<br />

WinSoft V 4.2.4.0 16 Issue 5.3


Use of the RH mouse button on a display<br />

This will allow a short cut to the display’s set up to be modified for the menu items shown.<br />

Changes the colour of<br />

the desktop display<br />

when mono-colour<br />

displays are used.<br />

The tri-colour UMD display colour and tallies may be changed from the following menu.<br />

Tallies may be enabled both on these menu paths and via the Edit > Tallies > Display Tally Enable path. If<br />

tallies do not light, check carefully that the tallies are actually enabled.<br />

» This function is only be supported from Tricolour Display software V 1.13 onwards. Justification may<br />

also be set from Winsoft.<br />

Earlier displays have the tally and mnemonic colour set-up carried out via the recessed front panel<br />

buttons on the UMD hardware.<br />

WinSoft V 4.2.4.0 17 Issue 5.3


2.1 Setting the Mnemonics – The Edit Menu<br />

The Edit menu allows access to all mnemonics:<br />

Select Edit > Mnemonics .<br />

2.1.1 Fixed Display Mnemonics<br />

These may also be set both by using the RH mouse button when the mouse pointer is over the Display and<br />

by using the Edit > Mnemonic > Fixed menu.<br />

» The easiest method is to select the individual display with the RH mouse button and edit the<br />

mnemonic.<br />

The listing provided via the Edit Menu is useful for subsequent changes and to confirm what the Display<br />

mnemonic would be if it were Fixed but is actually assigned to a Router.<br />

The Attributes of the Display on the screen may be set using the RH mouse button when the mouse pointer is<br />

over the Display.<br />

The colour and the justification of the mnemonic may be set on the screen. The actual justification must be<br />

set on the hardware if the hardware is earlier than v1.15.<br />

WinSoft V 4.2.4.0 18 Issue 5.3


The mnemonics may be edited or overtyped in the same manner as a conventional word processor.<br />

The AutoInc box will allow the cursor to move to the next lower mnemonic when is pressed on<br />

the keyboard.<br />

AutoCopy will automatically enter the previous text into the new box.<br />

» The Fixed Display Mnemonics may also be set by the Timed Message option, if provided, with the<br />

Winsoft Program. See Appendix D, where appropriate.<br />

WinSoft V 4.2.4.0 19 Issue 5.3


2.1.2 Router Source and Bus Mnemonics<br />

Select Edit > Mnemonics > Router Source/Bus.<br />

The Router Source and Bus Mnemonics are entered in exactly the same way using the appropriate menu.<br />

When more than one router is in use, the desired Router is selected at the top of the dialogue box.<br />

2.2 Setting the Displays to be Fixed, Fixed (Router) Source, Router Source, or Router Bus<br />

Displays.<br />

With the mouse pointer over the Display select the RH button. Select Set Mnemonic.<br />

For example: If this Display is to be associated with a Router Bus, select the Router Bus option. Then select<br />

both the Router and Bus with which the Display must be associated.<br />

This will allow selection of<br />

the Router number (in the<br />

case of more than one<br />

router in the system) and<br />

the Bus to which the Display<br />

is to be associated. The<br />

bus mnemonic and the bus<br />

number is shown in the box.<br />

The Router Bus mnemonic<br />

is shown in the Box.<br />

» Router Bus Displays show the Router Source Mnemonics.<br />

WinSoft V 4.2.4.0 20 Issue 5.3


For Displays which are to be set to Router Sources:<br />

The Router Source<br />

mnemonic is shown in the<br />

Source Box.<br />

These mnemonics (SRC 1<br />

etc) are the default<br />

mnemonics loaded at the<br />

factory.<br />

» Router Source Displays show the Router Bus Mnemonics.<br />

» Router Source Displays will show “-------“ when they are not selected by a Bus.<br />

Buses must have a priority set as several buses may select a common source.<br />

The UMD will then show the desired mnemonic. The higher the number, the higher priority.<br />

Virtual Router<br />

Where a virtual router facility has been provided in the firmware to allow for the naming of, say, transmission<br />

monitor picture sources on a UMD under the monitor, that UMD should be assigned to a particular Bus for<br />

the virtual router in Winsoft. Each Bus in the virtual router module will be tied to either the PGM, P/V or M/E<br />

etc. bus in the Mixer.<br />

The router source mnemonics are entered in the usual way or bus to source or source to source router<br />

mapping may be carried out to allow for automatic updates of the mnemonics. See Section 2.5.7.<br />

E.g. For a UMD to follow the mixer program bus, it must be assigned to Bus 1 on router 2 (the virtual router<br />

from the mixer).<br />

For simple systems, this virtual router will be router 2 in the Winsoft program.<br />

WinSoft V 4.2.4.0 21 Issue 5.3


2.2.1 Router Bus Priority<br />

It is possible for a router source to be selected by several router buses at once. A priority needs to be set for<br />

the router buses so that the Display attached to the router source will show the desired bus mnemonic.<br />

This is done via the Edit > Bus Priority menu.<br />

Highlight the bus to be set.<br />

Set the Priority and OK the setting.<br />

If a Source Display is selected by two Router Buses at once, the mnemonic shown will be from the Bus with<br />

the highest number.<br />

The higher the number, the higher the bus priority.<br />

» If the Priority is left at 0, no bus mnemonics or tallies on the Source Display will be shown.<br />

It is advisable only to select Buses that need to be selected/displayed.<br />

» The Router (video) Level must be set via the Control > General Menu. The UMD display brightness<br />

may also be set globally on this menu.<br />

WinSoft V 4.2.4.0 22 Issue 5.3


2.3 Names<br />

This menu allows the user to enter ordinary names as an aide memoir. Its use is optional.<br />

All listed items may be given names.<br />

Names for the System Controller, tally inputs, outputs etc are entered/edited via this menu and may be<br />

anything that the operator wishes – they will not be shown on the UMDs in the system.<br />

System Controller<br />

Name: “Manual”<br />

WinSoft V 4.2.4.0 23 Issue 5.3


2.4 Edit Display Assignment<br />

The complete Display assignment may be seen via the Edit > Display Assignment selection.<br />

For router associated<br />

Displays, select the<br />

appropriate source or bus<br />

in this box.<br />

Displays may also be set up and modified via this screen.<br />

» It is important to realise that a change of hardware type that results in a re-assignation of addresses<br />

will change the current association of addresses with mnemonics. The mnemonics always stay with<br />

the Display number.<br />

This will mean that the actual hardware (which has kept it’s address) will show a different mnemonic<br />

to that previously.<br />

The Clear section, Assign and Clear All will clear the Router links.<br />

» Experienced users may find it preferable to set up the entire UMD system first with this screen for the<br />

display hardware type and router linking and then edit the mnemonics in the appropriate menus.<br />

Display Terminology<br />

<br />

<br />

<br />

<br />

Fixed Displays are Displays which do not change their messages (mnemonics) when router<br />

changes are made.<br />

Fixed (router) Source Displays are displays which are assigned to the router inputs and show the<br />

dynamic tally states but they do not change their message (mnemonics) on router changes. They will<br />

always show the router source (input) mnemonic.<br />

Router Source Displays are Displays which are assigned to a router source (input) and they will<br />

show the router bus mnemonic.<br />

Router Bus Displays are Displays which are assigned to a router bus (output) and they will show the<br />

selected router source mnemonic<br />

WinSoft V 4.2.4.0 24 Issue 5.3


2.5 Tallies<br />

Notes On Configuring Tallies in Winsoft<br />

A decision needs to be made on how the tallies are to be mapped from the tally input connector (either serial<br />

or parallel) to the output connector. i.e. how the cameras are to be tallied.<br />

Where there is a router in the system and the cameras are presented to the router sources, it is usually<br />

always better, whether or not the router (bus) feeds the Mixer or whether the router is used only for<br />

monitoring, to map the tallies to the router sources either directly or indirectly via a tallied router destination<br />

(bus). If the router bus feeds the mixer, tallies would normally be mapped to the bus.<br />

The reasoning is that tallied router sources may be connected to a physical tally output pin which in turn is<br />

linked to the Camera Control Unit.<br />

Multiple tallies may be connected to a single router source.<br />

Tallies that are designated as Green (Iso tallies) may be linked to a router source and any tallied source then<br />

may be designated as Red or Green or Red+Green and connected to different tally output pins.<br />

This shows that different router<br />

source states may be assigned<br />

to different output pins.<br />

Tallied router sources will be shown on any router destination that selects that tallied router source, so any<br />

destination UMDs will also show a tally (with Bus Tally Unique unchecked in the options dialogue box).<br />

This method of tally configuration is especially important where there is an Emergency 2 x 1 router module in<br />

Winsoft controlled by a single-pole double-throw switch (as far as Winsoft is concerned. Extra poles may well<br />

be required for actual router switching).<br />

A UMD set to the output of the 2 x 1 “router” in Winsoft will show the correct source mnemonic assuming that<br />

the correct source to destination assignments have been made under Edit > Source Assign and any tally<br />

set to the o/p will in turn, tally the Emergency 2 x 1 Router, Source 2, when the router module is driven across<br />

from its normal state from i/p 1.<br />

The main router bus is then tallied and any source which that bus selects is also tallied. Router sources<br />

connected to the Tally Outputs in Winsoft allow tallies to be taken to cameras etc.<br />

This is explained in detail in Section 11.<br />

Simple systems may only have the Tally In mapped directly to the Tally Out pins.<br />

WinSoft V 4.2.4.0 25 Issue 5.3


General<br />

The System Controller has D37 Tally Input connectors for parallel tally inputs. Pin closures to ground are<br />

required to activate the tally “on” state.<br />

A D9 connector, Control 2, is available for connection to equipment which outputs serial tally information.<br />

The Output Tally D37 connectors enable tally information to be brought out to external equipment such as<br />

VTRs and Camera heads.<br />

The output circuit can sink about 150mA to ground for switching external relays etc. This circuit cannot<br />

switch power – it is used for control only.<br />

The Edit drop-down menu offers the following:<br />

All tally assignments are carried out under this drop-down menu.<br />

» Tallies may also be mapped via the Tools > Tally Pinpatch menu. See Section 3.6.2.<br />

Direct tallies have preference over router-associated tallies.<br />

This means that a UMD that has a direct tally mapped to it which may be OFF, will not show a tally<br />

LED lit even if a live router-associated tally is also mapped to that UMD.<br />

WinSoft V 4.2.4.0 26 Issue 5.3


2.5.1 Direct Tallies<br />

These are tallies coupled directly to a UMD or Tally LED panel. They may be derived, for example, from the<br />

parallel closures from a Vision Mixer via the D37 connector on the System Controller.<br />

There is the capability of lighting the left and right tallies on the UMD from separate tally signals – i.e. split<br />

tallies.<br />

Split Tallies<br />

To set Direct Tallies<br />

• Highlight the required Display.<br />

• Enter in the left lower box the left tally assignment. The right tally assignment is filled automatically when<br />

the OK button is pressed.<br />

• If a split tally arrangement is required, enter the tally number before selecting the OK button.<br />

• Map any Tally Lamps on the Desktop (the hardware being LEDs on panels) to the appropriate Tally<br />

Output by RH Mouse clicking on the Tally Lamp on the Desktop. The actual LED will have to be hardwired<br />

to the appropriate D37 Tally Output connector.<br />

» Direct tallies may also be entered by selecting the Display on the Desktop with the RH mouse button<br />

and then selecting Set Direct Tally from the menu.<br />

» Direct tallies have preference over router-associated tallies. This means that a UMD that has a direct<br />

tally mapped to it which may be OFF, will not show a tally LED lit even if a live router-associated tally<br />

is also mapped to that UMD.<br />

The right tally must always have a tally number entered. It is not possible to assign only a left tally to a UMD.<br />

If a RH tally is not required it may be disabled via the following procedure.<br />

WinSoft V 4.2.4.0 27 Issue 5.3


2.5.1.1 Edit > Tallies > Edit Display Tally Enable. (Also Section 2.5.6).<br />

It is possible to inhibit either the left or right tally on a UMD, regardless of its association with routers etc.<br />

2.5.2 Tally Outputs<br />

The System Controller has D37 output connectors which can sink about 150mA to ground for switching<br />

external relays etc. unless the Controller has been ordered with isolated relay outputs. In this case about 1A<br />

non inductive can be switched.<br />

These connectors enable tally information to be brought out to external equipment such as VTRs, LED Tally<br />

Panels and Camera Control Units (CCUs).<br />

(Multiple tally output may be achieved by the use to the tally multiplier unit, the CTD-1S).<br />

Tallies may also be set via the Tools,<br />

Tally Pin Patch menu. See Section 3.6.2<br />

This screen sets the linking of the Tally In pin to the Tally Out pin on the System Controller D37 connectors<br />

and/or the linking of the Router Source to the Tally Out pin. The operation may be regarded as a large pin<br />

matrix.<br />

• Select which Tally In pin is required to control the Tally Out pin on the System Controller by entering<br />

the appropriate Tally In pin number.<br />

WinSoft V 4.2.4.0 28 Issue 5.3


Tallied Router Buses connected to Tally Out<br />

If a tallied Router Bus is assigned to a System Controller Tally Out Pin, actual tallies may be fed to monitor<br />

cue lights etc. Note that this only works when the Bus is tallied directly. It will not work when a Source is<br />

tallied and the Bus then receives a tally for the UMDs only.<br />

It is essential that Bus Tally Unique in Setup > Options is not checked. Please see section 3.2.1.<br />

This shows that Router Red/Green tallies<br />

are enabled and that Router 1, Bus 1 is<br />

mapped to the physical tally output pin 1.<br />

Tallied Router Sources connected to Tally Out<br />

If a tallied Router Bus is cut up on the Mixer, the Router Source is also tallied. (See Section 2.5.4). If Router<br />

Sources are then assigned to a System Controller Tally Out Pin, actual tallies may be fed to camera cue<br />

lights etc.<br />

Example.<br />

This is used when router buses are connected to the vision<br />

mixer inputs. The tallied bus will in turn tally the source<br />

which is then connected to physical output pins. Any other<br />

bus selecting this tallied source will also be tallied. This<br />

method of mapping should be used where there is a 2 x 1<br />

emergency router in Winsoft or where multiple tallies are<br />

required to be output on a physical tally output pin. This will<br />

ensure that the correct tally information is always output to<br />

the cameras.<br />

Select which Router Source is to tally the Physical Tally Out<br />

pin.<br />

Note: Multiple external tallies are possible via a separate<br />

tally multiplier unit - CTD-1S- if necessary.<br />

WinSoft V 4.2.4.0 29 Issue 5.3


2.5.3 Edit Router Source Tallies<br />

Tallies may also be set via the Tools, Tally Pin<br />

Patch menu. See Section 3.6.2<br />

This will provide a direct tally to selected Router Sources. i.e. linking Tally Input pins to Router sources.<br />

If a source is picked up by a Router Bus, both the Source Display (if there is one) and the Bus Display (on the<br />

Router Bus) will be tallied provided that the Bus Tally Unique box is not checked in Setup > Options. This<br />

is to indicate that the source is On Air to any Bus. See Section 3.2.1 or the Note at the end of this section for<br />

additional details on Bus tallies.<br />

Therefore, any other Display on any Router Bus (e.g. a Bus designated as Engineering Preview) which<br />

selects that On Air source, will also show that source as On Air - i.e. it’s tallies are lit.<br />

2.5.3.1 Multiple Tally In to Router Sources<br />

For multiple Tally In conditions, when, for example, there may be a camera fed to two mixers via a router and<br />

DAs, there will be two tallies available. Either Tally from the Mixers should tally the Router Source. Under<br />

these conditions, the Enable multiple tally in to (Router) source box should be enabled - see Sect. 3.2.1.<br />

The Tally In and Router Source columns change over allowing several Tally Inputs to be connected to one<br />

Router Source.<br />

The Router Bus priorities must be set for reliable operation of the Program; see the<br />

Edit > Router Bus Priority menu.<br />

WinSoft V 4.2.4.0 30 Issue 5.3


2.5.4 Edit Router Bus Tallies<br />

Tallies may also be set via the Tools, Tally Pin<br />

Patch menu. See Section 3.6.2<br />

This linking will tally the Router Bus and therefore any Bus Display.<br />

It will also tally the source selected by the Bus (as long as the priority is set – see the<br />

Edit > Router Bus Priority menu.) as the crosspoint information of the router is known by the System<br />

Controller.<br />

• Select the Router Bus to be linked with a Tally In pin.<br />

Note.<br />

The Bus Tally Unique box in Setup > Options (Section 3.2.1) determines the way router-associated tallies<br />

are displayed.<br />

When the box is not checked, a tallied Router Bus will still tally the selected Router Source. However, if that<br />

source is taken directly to air, i.e. tallied by the mixer directly, any Router Bus that selects the tallied on-air<br />

source is also tallied.<br />

In some circumstances this might be misleading as the actual Bus is not on-air.<br />

If the box is checked, a tallied Router Bus will still tally the selected Router Source but If that source is taken<br />

directly to air, i.e. tallied by the mixer directly, any Router Bus that selects the tallied on-air source is not<br />

tallied.<br />

WinSoft V 4.2.4.0 31 Issue 5.3


2.5.5 Edit Tally Input Attributes – Red (Left) and Green (Right) Tallies and Ext Enable.<br />

This screen allows the setting of red/green tallies and the external enabling of tallies.<br />

External Enable – normally set to<br />

OFF.<br />

When set to ON, tallies will only be<br />

enabled when, typically Pin 32 in<br />

the SC-11, is set low by an external<br />

connection to 0V.<br />

Inspect the Winsoft Properties<br />

information for the Ext Enable pin<br />

on SC-21 systems.<br />

Green Tally – Global Enable<br />

Red and Green Tallies or Left and Right Tallies<br />

Any Tally In may act on a Router Source or Bus. Displays assigned to either a Router Source or Bus may<br />

need to have their left and right tallies split for, for example, to indicate Iso–Recording tally information.<br />

The Left Tally on the hardware is known as a Red Tally in the Winsoft system.<br />

The Right Tally on the UMD hardware is known as a Green Tally in the Winsoft system.<br />

The actual colour of the tallies on the hardware may be set either directly via the UMD’s menu structure or via<br />

the Winsoft program, using the RH mouse click on the display to get to the Attributes > Colour ><br />

Multicolour > Edit Properties dialogue box.<br />

The Edit Tally Input Attributes screen allows Displays associated with routers to have the tally indication split.<br />

This is a similar requirement to splitting tallies under Edit > Tallies > Direct Tally > Edit Direct Tally to<br />

Display Assignment, the important difference being that the Router Sources or Buses are tallied with either<br />

or both a red and a green tally.<br />

WinSoft V 4.2.4.0 32 Issue 5.3


Note<br />

» A Green Tally assigned to a Fixed Display will light both Tallies.<br />

Tally Type may be toggled between Red and Green Tallies (i.e. left and right split tally lights).<br />

Green Tally Enable is a global enable. If this box is not checked, the system treats the two tallies (of<br />

whatever colour on the hardware) as Red/Left and both tallies will be lit from the Red/Left tally signal.<br />

The box must be checked to allow the tally split facility to be enabled. With the box checked, router tallies<br />

assigned as red will light tallies on the left-hand side LED only on the hardware, green tallies will light the RH<br />

tally LED.<br />

A red or green tally may tally a router source which in<br />

turn may be mapped to a Tally Out pin.<br />

Once the router-associated tallies are split red/green<br />

and the Enable green tallies box is checked, an<br />

additional pair of check boxes will appear in the Edit<br />

Physical Tally Out Assignment dialogue box for the<br />

option of R, G or R+G tally outputs to an output pin.<br />

If these boxes are left unchecked, no tallies will be<br />

output.<br />

So, if a router source has both a red and a green tally<br />

assigned to it, a choice may be made so that only red<br />

tallies, say, are output to a Tally Out pin.<br />

WinSoft V 4.2.4.0 33 Issue 5.3


External Enable – normally set to OFF<br />

This facility allows external (remote) enabling of any tally. It is an option and is usually provided via Pin 32 on<br />

the Tally In Connector of the SC-11 System Controller. Please check the Properties dialogue box for the<br />

External Enable pin on the SC-21 System Controllers.<br />

For normal tally use the External Enable column entries must be set to OFF.<br />

If this is used, one tally fewer will be available via the System Controller.<br />

2.5.6 Edit > Tallies > Display Tally Enable<br />

The left or right tally may be inhibited on any display, whether it is a Fixed display or a router-associated<br />

display.<br />

Display Tally Enable<br />

Select the Display(s) that are to<br />

have the left or right tallies inhibited<br />

» In the event of no tallies, check that the External Enable box entries are set to OFF, that the Left and<br />

Right tallies on the displays are enabled in Winsoft, and that the tallies are actually turned on, on the<br />

UMD hardware.<br />

WinSoft V 4.2.4.0 34 Issue 5.3


2.5.7 Edit Router Source Assignment<br />

Assign to Bus<br />

This is used when there is more than one router in the system and displays need to show the correct original<br />

source mnemonic.<br />

This screen is accessed via Edit > Source Assign.<br />

Assign to Bus selected.<br />

The Assign to Source option<br />

is enabled in the System<br />

Controller firmware.<br />

This router is mapped to<br />

this one – which is<br />

considered to be the<br />

“master”.<br />

A display on the second (main output) Router Bus needs to show the correct Router 1 source mnemonic.<br />

In the example above, Router 2 is the ‘output’ Router in the chain. Input 1 on that Router has the mnemonic<br />

“SRC 1”.<br />

This input 1 is connected to Router 1, Bus 1, which has the mnemonic “DST 1”. Router 1 will also have<br />

mnemonics assigned to it’s sources. It is these source mnemonics that will be shown on the Router 2 Bus<br />

Display.<br />

Therefore, the linking will now ensure that the Router 2 Bus Display shows the correct Router 1 Source<br />

mnemonic which is selected by Router 1, Bus 1.<br />

Bus 1 Source 1<br />

UMD<br />

Router 1<br />

Router 2<br />

Tallies may be assigned to the buses or sources as required.<br />

WinSoft V 4.2.4.0 35 Issue 5.3


Assign to Source<br />

A variation on the above is assigning Sources to Sources.<br />

When this option is selected in the Assign to box, the Display on the second router output will show the<br />

mnemonic and tally state of the assigned source. In this example, “SRCE A” will be shown, assuming that<br />

the Router 2 Bus has selected input SRCE AA.<br />

SRCE A<br />

SRCE AA<br />

UMD<br />

Router 1<br />

Router 2<br />

The mnemonics and tallies for the input to Router 2, SRCE AA, are effectively taken over by the input<br />

mnemonics and tally state to Router 1. In this example, the mnemonics and tally state shown on the UMD<br />

will be those for SRCE A. In this case SRCE A is considered to be the master source – it is to this source<br />

that tallies and tally output pins must be assigned. In the dialogue box above, Router 1 is now the master<br />

controlling source – it is to this source that tallies and tally output pins must be assigned.<br />

Therefore, in this example, only the mnemonics for Router 1 need be entered in the mnemonics lists in the<br />

Edit menu.<br />

Source to Source mapping may also be done within one router.<br />

Virtual Router<br />

Use of a second “virtual” router<br />

Where a virtual router facility has been provided in the firmware to allow for the naming of, say, transmission<br />

monitor pictures on a UMD under the monitor, that UMD should be assigned to a particular Bus for the virtual<br />

router in Winsoft. Each Bus in the virtual router module will be tied to either the PGM, P/V or M/E etc. bus in<br />

the Mixer.<br />

E.g. For a UMD to follow the mixer program bus, it must be assigned to Bus 1 on router 2 (the virtual router<br />

from the mixer).<br />

For simple systems, this virtual router will be Router 2 in the Winsoft program.<br />

Router Source to Source or Source to Destination mapping may be used to provide automatic label updates.<br />

This an option and must be ordered.<br />

WinSoft V 4.2.4.0 36 Issue 5.3


3.0 The Other Menus<br />

3.1 File<br />

This screen will allow opening and saving of the Stack Layout via the *.mon files, of the mnemonics via the<br />

*.umd files and of the router set up file via the. *rtr files. (See Section 5 for router control).<br />

Alternative mnemonics ( .umd files) may be entered and saved, for example when the cameramen’s names<br />

change.<br />

When a new layout has been created and is to be saved, both the layout (.mon) and the UMD set-up (.umd)<br />

must be saved.<br />

The opening screen display may be set up via the Setup > Options Screen. See section 3.2.<br />

Files may be saved to any directory although the default directory is the same as the one which contains the<br />

program files.<br />

Important information for first time use when working Offline.<br />

Before working Offline, the computer must have been connected and have read the System<br />

Controller firmware once. Save an empty .mon and .umd file.<br />

This then allows the computer program to match the System Controller firmware parameters.<br />

WinSoft V 4.2.4.0 37 Issue 5.3


3.2 Setup Menu<br />

3.2.1 Options<br />

Under Options, settings may be made for:<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

System Controller Auto Read on connection,<br />

the choice of Starting Offline,<br />

Enabling multi tallies in to (a Router) Source,<br />

the option of Disabling Layout Changes<br />

the Enabling of Router Control.<br />

the Router Bus Tally Unique settings<br />

Default Layouts<br />

Default Data Files<br />

UMD types<br />

Monitor types<br />

The Auto Read on connection box need only be checked if it is likely that the Winsoft settings in the<br />

computer program do not match those in the Controller.<br />

The Starting Offline box need only be checked if the computer is connected to the Controller but changes<br />

made to the settings are not to automatically update the Controller.<br />

Enabling multi tallies in to (a Router) Source would be used when, say, a camera is fed to two or more<br />

mixing points, or when both red and green tallies need to be assigned to a router source. See Section 2.5.3<br />

The Disable Layout Changes box, when checked, will prevent the accidental movement of UMDs and<br />

monitors etc. on the desktop.<br />

A double click with the LH mouse button will allow access to the router control and IRD control panel when<br />

this box is checked.<br />

The Enable Router Control box allows a monitor on the desktop to be associated with either a particular<br />

UMD or a Router Bus directly. This option is firmware dependent - see Section 4.<br />

The Bus Tally Unique box determines the way router-associated tallies are displayed.<br />

When the box is not checked, a tallied Router Bus will tally the selected Router Source. If that source is<br />

taken directly to air, i.e. tallied by the mixer directly, any Router Bus that selects the tallied on-air source is<br />

also tallied.<br />

In some circumstances this might be misleading as the actual Bus is not selected to be on-air.<br />

If the box is checked, a tallied Router Bus will still tally the selected Router Source but If that source is taken<br />

directly to air, i.e. tallied by the mixer directly, any Router Bus that selects the tallied on-air source not tallied.<br />

Default Layout sets the opening screen and there are options for clearing all UMDs from the screen and for<br />

setting the Default type of UMD.<br />

Monitors may be cleared from the screen and the Default type my be set to either 4:3 or 16:9 aspect ratio<br />

using the Radio Buttons.<br />

WinSoft V 4.2.4.0 38 Issue 5.3


3.2.2 Register IRD<br />

This is system dependent - please see Appendix C where appropriate.<br />

3.2.3 Network Mode<br />

Master/Slave Selection.<br />

In a Networked system the Slave Mode (entered via Setup > Network Mode > Start Next session as<br />

Slave) would be selected. The screen then offers a choice of the System controller to be controlled. The<br />

addressing is set in the firmware supplied with the System Controller. See Appendix A<br />

Double clicking on the appropriate System Controller - Node - will allow editing/set-up of the appropriate<br />

controller.<br />

The mode may be re-entered by clicking in the Node white bar at the top of the screen.<br />

For non-Networked Systems, the Master setting must be selected<br />

3.3 Control Menu<br />

3.3.1 General Parameters<br />

Router<br />

Level settings, Matrix Number (for Probel units) and names editing are set in this dialogue box.<br />

For details please see the appropriate router section of the manual.<br />

Set the router level<br />

This box (if present) allows<br />

access to the router names<br />

lists – router dependent<br />

This box allows access to the<br />

router baud rate etc.<br />

WinSoft V 4.2.4.0 39 Issue 5.3


Configure Router Serial Port<br />

Change the baud rate etc. <strong>TSL</strong><br />

configures the standard setting from<br />

manufacturer’s data.<br />

Brightness<br />

Three levels may be selected on a global basis.<br />

Bright on Tally is not yet available.<br />

Tally Test<br />

This will bring on all Tally Lamps when the box is checked. Tally lamps will extinguish when the box is closed.<br />

Assign Port Address (for custom use only)<br />

This custom facility allows access to, say, selected mnemonics within the Winsoft program. For example, a<br />

custom program could be supplied and usually the computer, in this instance, would be connected to Control<br />

2 on the System Controller. Several remote PCs may be connected together to this port, hence the<br />

requirement for an address. Custom external programs may also communicate with the System Controller<br />

via the Assign Protocol software. The Address set here must match that in the incoming data.<br />

Set Timed Message – see section 13<br />

Hard Reset<br />

A Hard Reset will reload the factory defaults and delete ALL user defined<br />

Set-ups. Use with Care. Save the current set-up if in doubt.<br />

3.4 View Menu<br />

This option will allow selection and display of the desktop grid, the Display numbers, Display addresses and<br />

Monitor Index numbers. (See Section 5). The screen may also be zoomed in or out.<br />

3.5 Comms Menu<br />

Select the appropriate Comms Port<br />

for the configuring computer<br />

The system may be set-up or edited Offline and then the System Controller may be updated when required.<br />

WinSoft V 4.2.4.0 40 Issue 5.3


» When the Program is set to Online, the System Controller must be written to before subsequent<br />

changes are seen on the hardware.<br />

The Menu also gives the ability to read or write to the System Controller as required.<br />

Any one of eight computer serial ports may be selected. The Network menu item is for TCP/IP addressing<br />

where controllers are accessed via an intranet system.<br />

3.6 Tools Menu<br />

Various Dialogue Boxes are available<br />

which will allow mnemonics to be<br />

dragged and dropped onto UMDs.<br />

The tally mimics will allow a tally to be<br />

forced on by clicking on the Radio Button<br />

as well as showing the status at any<br />

instant.<br />

If the mouse is dragged off the Radio<br />

Button whilst the LH button is depressed<br />

the tally will stay on until the Dialogue<br />

Box is closed<br />

WinSoft V 4.2.4.0 41 Issue 5.3


3.6.1 The Lists and Mnemonics<br />

The Lists can remain on-screen as an aide-memoir.<br />

The Custom Fixed List will be useful for dragging and dropping mnemonics directly onto Fixed Displays.<br />

To drag and drop any of the mnemonics onto Displays, double click – holding the LH mouse button down on<br />

the second click - and drag and drop onto the desired Fixed Display.<br />

3.6.2 Tally Pin Patch<br />

All tallies may be mapped via this screen rather than via the Edit > Tallies Menu, if desired. The drop-down<br />

boxes will allow access to the left and right tallies on the Fixed Displays, Router Source and Bus tallying and<br />

Tally Input/Output mapping. A zoom function is provided to enable an overview of the mapping to be seen.<br />

3.6.3 Tally Mimic.<br />

Tallies may be held on by selecting the Radio Button and whilst the LH mouse button is held pressed, the<br />

mouse is dragged off the button.<br />

3.6.4 Router Mimic<br />

The Router Mimic will show router change events from the bottom of the box upwards.<br />

WinSoft V 4.2.4.0 42 Issue 5.3


3.7 Properties Menus<br />

The Properties Menu allows inspection of the firmware parameters in the System Controller and the last UMD<br />

file that was downloaded to the Controller.<br />

Last .UMD file<br />

downloaded to the<br />

System Controller<br />

Maximum Parameters and System Description<br />

WinSoft V 4.2.4.0 43 Issue 5.3


4.0 Associating Monitors with a Router<br />

This program allows a router to be controlled via the RS422/RS232 data connection between the System<br />

Controller and the router. This will then allow different monitor/router configurations to be up-loaded via the<br />

*.umd file or, if only the router settings are required, via the *.rtr file.<br />

A RH mouse button click on a monitor will allow that monitor to be associated with a router. If a UMD is<br />

associated with a router bus the monitor may be associated with that UMD.<br />

Assign the monitor to the Router Bus, first.<br />

In the example shown, the<br />

monitor is associated with a<br />

Router Bus.<br />

In the example shown, the<br />

monitor is associated with a bus<br />

UMD.<br />

WinSoft V 4.2.4.0 44 Issue 5.3


Once the monitor is associated with a router, source selections may be made as follows.<br />

The router source is selected from the drop-down<br />

box and the selection takes effect when the TAKE<br />

button is pressed.<br />

The entire (video) router selection may be saved under File > Save > *.rtr<br />

A double click with the LH mouse button will allow access to the router control and IRD control panel when<br />

the Disable Layout Changes box is checked in the Setup > Options screen.<br />

The Router Files drop-down<br />

box is selected.<br />

» For SMS 7000 users<br />

For correct communication for router control from Winsoft, force an upload of names via Control ><br />

General > Configure Names > Upload names from router .<br />

WinSoft V 4.2.4.0 45 Issue 5.3


5.0 Desktop Enhancements<br />

5.1 Making a Frame for the Monitor Stack<br />

A frame may be made around the stack by selecting a square to the top left of the monitors, hold down the<br />

LH mouse button and pull the frame down to the lower right of the monitors.<br />

The RH mouse button will allow the frame infill colour to be changed, the frame to be re-sized and text to be<br />

inserted at the top of the frame.<br />

5.2 Naming the icons<br />

The RH mouse button, when clicked on a monitor or VTR icon etc., will allow entry of text.<br />

This example shows the Dialogue Box for<br />

single quad split monitor<br />

WinSoft V 4.2.4.0 46 Issue 5.3


6.0 General Notes for Displays<br />

It must be remembered that the Displays themselves will have to have their addresses set via the recessed<br />

buttons on the front panel.<br />

The single and dual displays require one address each whereas the triple and quad displays require two<br />

addresses each.<br />

For programming reasons Triple and Quad displays always start with an even address. This means that with<br />

a mixture of display types, not all addresses may be available.<br />

If a single D8C display is to be used as the Right display (please see the UMD Displays Manual) , i.e. it is<br />

required to display the second set of 8 characters in the 16 bytes sent, it should be entered into the program<br />

as a Dual 8 when a second line will be made available for mnemonics entry as Display 2. Only one address<br />

is needed for the LH and RH Displays, as would be the case for a genuine DD8C Display.<br />

This is a method of doubling the number of D8C Displays on the system for the set number of addresses.<br />

Using a single D16 or D16C as a combined router-associated and fixed display<br />

Sometimes it will be found useful to use a D16 display to indicate both router derived mnemonics and tallies<br />

and separately, a fixed mnemonic, so the cameraman’s name may be added to, say, the Cam 1 indication,<br />

which could be a Fixed Router Source mnemonic.<br />

The D16 display should be entered into Winsoft as a Dual 8. This will use only one address but will allow<br />

each half of the display (two times eight characters) to be separately assigned for mnemonic indication.<br />

The LH side of the display must have the required tally information mapped to it and it would normally also be<br />

the router-associated display.<br />

The RH side of the display may be used for an 8 character Fixed Mnemonic or other router mnemonic<br />

function.<br />

Displays with red/green display blocks<br />

For those special DD8 UMDs which use the first four blocks as red displays and the second as green<br />

displays (or vice versa), the unit must be treated as a Quad Display.<br />

These units will be assigned two addresses by the program, allowing separate messages to be assigned to<br />

the coloured blocks.<br />

Split Tally working for the TD8 and QD8 displays<br />

The standard Triple and Quad displays do not support split-tally working.<br />

Custom units that do support split tally working must be entered into Winsoft as the appropriate Triple or<br />

Quad display. The program will allow split tallies to be entered.<br />

However, when setting the address on the hardware, the first pair of displays will be on an even address, as<br />

shown in Winsoft, and the second display (or pair of displays in the case of a QD8) must have its address<br />

incremented by 1.<br />

E.g. A TD8 with split tallies may be at address 008. The second half of the display must be entered as 009.<br />

WinSoft V 4.2.4.0 47 Issue 5.3


7.0 Audio Monitoring Unit Setup<br />

<strong>TSL</strong> AMUs may be set up and monitored via this program.<br />

A right hand mouse button click on the LH side of the display (an AMU2882 in this example) will bring up the<br />

following menu.<br />

The selected AMU may be set-up via the Attributes menu item.<br />

View shows an AMUMD2882<br />

View shows an ML1<br />

Using the Mouse or Tab keys on the keyboard, it will be possible to select the item to be changed. When the<br />

unit is configured, the button will action the selection and clear this screen.<br />

WinSoft V 4.2.4.0 48 Issue 5.3


To save the set-up to the unit’s E-Prom, select the PowerUp Default button.<br />

The selections are as follows:<br />

• Silence Detect<br />

Delay is adjustable from 5 seconds to 255 seconds in 5 second increments.<br />

Threshold may be adjusted to any of the pre-set levels: -20,-21, -23, -26, -29dB.<br />

Panel Display globally toggles the red flashing overload LCD columns on or off.<br />

The Radio Buttons are used to switch on/off individually the red flashing overload LCD columns. The<br />

alarm outputs via the serial data information are still present.<br />

• Dynamics<br />

The Radio Buttons will allow toggling between PPM and VU bargraph meter characteristics.<br />

Peak Hold , when checked will give an approximately 1 second peak-hold time constant.<br />

• AMU Text Display<br />

The Check Box toggles the UMD part of the display on or off.<br />

Brightness is selectable from 1 (dim) to 6 (bright) and controls the text and bargraph brightness.<br />

Static UMD Text, This is the text which is displayed when there is no serial data from a System<br />

Controller.<br />

• Save To box allows:<br />

- saving the set-up to a File,<br />

- saving to the AMU’s internal prom – Power Up Default<br />

and<br />

- Loading from a File.<br />

• Edit Unit. The Radio Buttons allow selection of the required module. These are adjusted as groups of<br />

four.<br />

• Monitor Select toggles between the left and right pairs of signals on the unit selected and outputs the<br />

selected audio to the Sel Bus connector.<br />

WinSoft V 4.2.4.0 49 Issue 5.3


8.0 The Help Menu<br />

8.1 About Winsoft<br />

The Winsoft version is shown.<br />

8.2 Show Serial Comms Window<br />

This box will show all serial communications.<br />

WinSoft V 4.2.4.0 50 Issue 5.3


9.0 Uploading and downloading of names from routers and mixers into Winsoft<br />

Not all these functions may be supported with some firmware.<br />

This screen is accessed via the Control > General menu.<br />

Sets the router<br />

level<br />

Select this button<br />

to edit the router<br />

names and<br />

Winsoft<br />

mnemonics<br />

9.1 Configuring the Serial Port<br />

Select this button<br />

to change the<br />

router baud rates<br />

etc. if necessary<br />

If the baud rates etc. cannot be changed (i.e. they are fixed in the third-party hardware), these boxes will be<br />

greyed out.<br />

WinSoft V 4.2.4.0 51 Issue 5.3


9.2 Configure Names Options<br />

9.2.1 Router Database Options<br />

Allows selection of<br />

the router name<br />

table. This will<br />

change depending<br />

on the router in use<br />

Reads names from<br />

the router into a<br />

Winsoft table.<br />

Recommended on<br />

first connection<br />

Allows editing of<br />

router source names<br />

within Winsoft – see<br />

note at end of<br />

section<br />

Allows editing of<br />

router bus names<br />

within Winsoft –<br />

where supported<br />

Saves or loads the router names to<br />

the default directory<br />

9.2.2 UMD Mnemonics Options<br />

Copies the Winsoft<br />

Router Source<br />

Mnemonics to the<br />

router names lists<br />

selected in the<br />

Router name table<br />

Updates the router<br />

database names<br />

from the Mnemonics<br />

– where supported<br />

Copies the router<br />

names lists to the<br />

Winsoft Router<br />

Source Mnemonics<br />

for display on UMDs<br />

When checked –<br />

automatically<br />

updates the<br />

mnemonics when<br />

the names change in<br />

the router database.<br />

WinSoft V 4.2.4.0 52 Issue 5.3


9.2.3 Mixer Mnemonics Options<br />

Allows selection of<br />

the Mixer Button<br />

Mnemonics from a<br />

drop-down box.<br />

UMD Mnemonics<br />

are those from the<br />

Edit>Mnemonics><br />

Router Source lists.<br />

The relationship of<br />

button/bus is made<br />

by the tally mapping<br />

to the router bus<br />

selection under<br />

Edit>Tallies> Bus<br />

Tally.<br />

Selects the first 2<br />

and last 2 characters<br />

for the Mixer Button<br />

mnemonics<br />

9.2.4 Notes.<br />

Changing the Router name table field or the Assigned Button Mnemonics field will only have immediate effect<br />

if the names are subsequently uploaded – Upload names from router.<br />

Uploading Names into the mixer<br />

The router buses feeding assignable mixer inputs must have the relevant mixer tally assigned in Winsoft<br />

under Edit >Tallies >Bus Tally. Updates will occur when a route is made to that bus.<br />

The Edit button<br />

allows access to all<br />

selections except<br />

UMD Mnemonics.<br />

WinSoft V 4.2.4.0 53 Issue 5.3


Mixer Mnemonics Only<br />

Labels can (where supported) be shown for:<br />

- non-assigned mixer inputs or<br />

- where a mixer bus is fed back to a prime input, via a DVE, for example.<br />

Mixer Input Labels are<br />

edited via this button<br />

Select the Mixer<br />

Mnemonics field<br />

WinSoft V 4.2.4.0 54 Issue 5.3


Background Information<br />

The Winsoft program carries three tables or lists for the router sources.<br />

Mnemonics Names Mixer Mnemonics<br />

Shown in the<br />

user Winsoft<br />

mnemonics<br />

lists and can<br />

be displayed<br />

on the UMDs<br />

Indexing<br />

e.g. GVG<br />

7000.<br />

Possible<br />

editing<br />

Shown on<br />

the Mixer<br />

Where the router relies on the correct ASCII code for its indexing (e.g. GVG7000), any editing of the names<br />

will cause a communications failure.<br />

For correct communication for router control from Winsoft, force an upload of names via Control > General<br />

> Configure Names > Upload names from router .<br />

10.0 Trouble shooting<br />

When on-line, the program saves a defumd1.dat file to the working directory when the program is closed. If<br />

difficulty is experienced with running the program and going on-line, delete this file only from the Winsoft<br />

working directory. Winsoft should then run and read the System Controller parameters.<br />

When working off-line it is essential that the work is re-saved to the .umd file before closing the program.<br />

The defumd1.dat is only updated when the program is on-line and then closed normally.<br />

A hard reset will reload the factory conditions into the System Controller and return the unit to its original<br />

state. If re-loading the saved .umd file causes difficulty, the file must be corrupted and the configuration will<br />

have to be re-built.<br />

WinSoft V 4.2.4.0 55 Issue 5.3


11.0 Notes on the use of the 2 x 1 Emergency C/O Router<br />

This Winsoft module allows tally information to be routed from the transmission o/p back to the router<br />

sources and then out to cameras etc. in the event of a mixer malfunction as well as the ability to show the<br />

correct source mnemonic that is on-air.<br />

Please bear in mind that the drawings give a systems overview from the Winsoft viewpoint.<br />

2 x 1 Emergency Router in Winsoft<br />

From Mixer PGM<br />

UMD<br />

Router<br />

Source 2<br />

Activating Tally i/p<br />

Assign this tally to the<br />

router’s bus<br />

From Router Bus<br />

A tally set to the o/p will in turn, tally the Emergency 2 x 1 Router Source 2 when the router<br />

module is driven across from its normal state from i/p 1.<br />

The main router bus is then tallied and any source which that bus selects is also tallied.<br />

If Router sources are connected to the Tally Outputs in Winsoft, tallies may be taken to cameras<br />

etc.<br />

External C/O switch to select between Mixer and Router O/Ps.<br />

One pole needs to carry out the Winsoft control.<br />

Enabling Tally i/p to System Controller<br />

Activating Tally i/p to System Controller<br />

If the mixer tallies are Ext Enabled, when the switch is in the top position mixer tallies will<br />

be output. When the switch is in the lower position, the mixer tallies will be inhibited and<br />

the Emergency Router is driven over to i/p 2 and the tally set to its o/p bus.<br />

WinSoft V 4.2.4.0 56 Issue 5.3


12.0 Notes on the use of the Static S8C Displays.<br />

When the display is entered as a Static S8C it will be seen that it is in the Winsoft program as two displays.<br />

To make the Winsoft desktop look right for the message, right click on the display and enter a Fixed<br />

Mnemonic into the highlighted box.<br />

A RH Mouse click on<br />

Set Mnemonic ><br />

Fixed will show this<br />

screen.<br />

Tallies<br />

There are 4 tally control signals for an S8C. On "Display 1", the two tallies do the left and right tally lamps.<br />

On "Display 2", Tally 1 turns the display red and Tally 2 with Tally 1 turns the Display amber.<br />

WinSoft V 4.2.4.0 57 Issue 5.3


Setting Tallies<br />

Set tallies to the first display of the pair. If the display is not to turn red do not set any tallies to Dsp 2. This<br />

screen pix. shows the same tally is set to both the left and the right tally lamps.<br />

Only the left and right<br />

tally lamps will light.<br />

If you want the text to<br />

turn red, enter the<br />

tallies for Display 2.<br />

Then disable the RH<br />

tally on Display 2 in<br />

this menu:<br />

If the RH tally is not Inhibited, the text will turn amber/yellow.<br />

WinSoft V 4.2.4.0 58 Issue 5.3


13.0 Timed Messages for Fixed UMDs.<br />

This menu item is accessed via Control > Set Timed Message. Timed messages may be set to a UMD that<br />

is set as Fixed.<br />

Select a Display from<br />

the Select Display list.<br />

Then Add it to the<br />

main box<br />

This box will show<br />

when Add has been<br />

selected.<br />

Type in the message<br />

or select List to find a<br />

previously added<br />

message.<br />

Then Add Message to<br />

List if desired.<br />

Set the Event Time.<br />

This is PC time.<br />

The Display will<br />

change its mnemonic<br />

at the set time<br />

WinSoft V 4.2.4.0 59 Issue 5.3

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!