<strong>iSTAR</strong> <strong>eX</strong> Tools<br />

Power Supply<br />

The <strong>iSTAR</strong> <strong>eX</strong> panel uses a UL Recognized ESD, Model SPS 6.5 power supply<br />

(12V, 6.5 amps).<br />

NOTE<br />

Not applicable for the NPS version.<br />

Power Supply/Battery Switch-over Circuitry<br />

This circuitry monitors the AC power input. If the AC power fails, the battery<br />

will power the system.<br />

NOTE<br />

Not applicable for the NPS version.<br />

Battery Charger Circuitry<br />

A minimum of 0.5 amps is reserved for charging the battery.<br />

NOTE<br />

Not applicable for the NPS version.<br />

Alarms, LEDs, <strong>and</strong> Battery (St<strong>and</strong>ard Model with Power Supply <strong>and</strong> Battery)<br />

The following alarms are sent to the GCM via the SPI interface.<br />

See “Low Battery <strong>and</strong> AC Power Fail (St<strong>and</strong>ard Power Supply Model)” on<br />

page 4-9 for an explanation of how to configure the following alarms.<br />

Power Failure Alarm<br />

If the AC power fails, an AC power failure alarm is asserted.<br />

Battery Low Alarm<br />

When the battery capacity drops to one-third of total capacity for the 12 VDC,<br />

17.2 Ah minimum capacity st<strong>and</strong>by battery, a battery low alarm is asserted.<br />