4<br />

Termination Locations<br />

A. Vent Termination Minimum Clearances<br />

HORIZONTAL<br />

OVERHANG<br />

WARNING<br />

Fire Risk.<br />

Explosion Risk.<br />

Inspect external vent cap regularly.<br />

• Ensure no debris blocks cap.<br />

• Combustible materials blocking cap may<br />

ignite.<br />

• Restricted air fl ow affects burner operation.<br />

2 FT.<br />

MIN.<br />

GAS DIRECT VENT<br />

TERMINATION CAP<br />

20 INCHES MIN.<br />

LOWEST<br />

DISCHARGE<br />

OPENING<br />

X<br />

12<br />

VERTICAL<br />

WALL<br />

ROOF PITCH<br />

IS X/ 12<br />

H (MIN.) - MINIMUM HEIGHT FROM ROOF<br />

TO LOWEST DISCHARGE OPENING<br />

WARNING<br />

Fire Risk.<br />

Explosion Risk.<br />

Maintain vent clearance to combustibles as<br />

specifi ed.<br />

• Do not pack air space with insulation or other<br />

materials.<br />

Failure to keep insulation or other materials<br />

away from vent pipe may cause fi re.<br />

Measure vertical clearances from this surface.<br />

Roof Pitch<br />

H (Min.) Ft.<br />

Flat to 6/12...........................................................1.0*<br />

Over 6/12 to 7/12 .................................................1.25*<br />

Over 7/12 to 8/12 .................................................1.5*<br />

Over 8/12 to 9/12 .................................................2.0*<br />

Over 9/12 to 10/12 ...............................................2.5<br />

Over 10/12 to 11/12 .............................................3.25<br />

Over 11/12 to 12/12 .............................................4.0<br />

Over 12/12 to 14/12 .............................................5.0<br />

Over 14/12 to 16/12 .............................................6.0<br />

Over 16/12 to 18/12 .............................................7.0<br />

Over 18/12 to 20/12 .............................................7.5<br />

Over 20/12 to 21/12 .............................................8.0<br />

* 3 foot minimum in snow regions<br />

Figure 4.2 Minimum height from roof to lowest discharge<br />

opening<br />

Figure 4.2 specifi es minimum vent heights for various<br />

pitched roofs.<br />

GAS, WOOD OR FUEL<br />

OIL TERMINATION<br />

B<br />

C<br />

GAS<br />

TERMINATION<br />

Measure horizontal clearances from this surface.<br />

A<br />

Figure 4.1<br />

(See Figure 4.4 for specific clearances)<br />

Gas<br />

Termination<br />

Wood & Fuel Oil<br />

Termination<br />

Figure 4.3 Multiple Vertical Termination<br />

Comments<br />

A 6 in. 20 in. min. Horizontal distance between terminations<br />

B 20 in. 24 in. min. Distance to perpendicular wall<br />

C 18 in. 18 in. Vertical distance between terminations<br />

10<br />